3. Installation of indoor unit
3) Indoor unit drain piping
• Drain piping must have downward (1/50 to 1/100): be sure
not to provide up-and-down slope to prevent reverse flow.
• During drain piping connection, be careful not to exert
extra force on the drain port on the indoor unit.
• The outside diameter of the drain connection on the indoor
unit is 32mm(1-1/4inch).
• Be sure to install heat insulation on the drain piping.
4) Drain test
• TP/TM Chassis
1. Temporarily fix two decoration panel fixing screws
(hexagon M5 screw) on the unit body. (Tighten by
amount 10mm(13/32inch) in length.)
The fixing screws (hexagon M5 screw) are included
the indoor unit box.
2. Remove the air inlet grille from the decoration panel.
(Remove the hook for the air inlet grille cord.)
3. Hook the decoration panel key hole ( ) on the
screws fixed in step above, and slide the panel so that
the screws reach the key hole edge.
4. Retighten completely two temporarily fixed screws and
other two screws. (Total 4 screws)
5. Connect the louver motor connector and display con-
nector.
6. After tightening these screws, install the air inlet grille
(including the air filter).
The decoration panel has its installation
direction.
Before installing the decoration panel, always
remove the paper template.
Decoration panel fixing screws
(hexagon M5 screws)
Temporally fitting at 2 places
(Tightening about 10mm)
Air conditioner unit
Decoration panel
Control box cover
Piping side
Louver motor
Display
Lead wire for
louver motor and
display
Inlet Grille
Decoration panel fixing screws
Decoration panel fixing screws
(Hexagon M5 screw)
(Hexagon M5 screw)
Decoration panel fixing screws
(Hexagon M5 screw)
Heat insulation material: Polyethylene foam with thick-
ness more than 10(13/32)mm(inch).
Piping material: Polyvinyl chloride pipe
25(31/32)mm(inch) and pipe fittings
Flexible drain hose
1/50~
1/100
MAX
800(31-1/2) mm(inch)
Upward
routing
not allowed
Feed water
Drain pump
Drain pan
Flexible drain hose
(Accessory)
Main
drain pipe
Glue the joint
Drain
port
Drain hose connection
use the clip (Accessory)
Flexible drain hose
Heat pump 60Hz/R410A