Heat pump 60Hz/R410A
4. Installation of outdoor unit
Installation of
Outdoor Units
SINGLE ZONE
4.6 Clearance space
SINGLE ZONE
4.6.1 Clearance around outdoor unit
300(11-13/16)
or more
300(11-13/16)
or more
300(11-13/16)
or more
Air inlet grille
Blown
air
Strong
wind
Strong
wind
300(11-13/16)
or more
600(23-5/8)
or more
500(19-11/16)
or more
Sunroof
Fence or
obstacles
300(11-13/16)
or more
300(11-13/16)
or more
300(11-13/16)
or more
Air inlet grille
Blown
air
Strong
wind
Strong
wind
300(11-13/16)
or more
600(23-5/8)
or more
500(19-11/16)
or more
Sunroof
Fence or
obstacles
• Ensure that the space around the back is more
than 300mm(11-13/16inch) on the opposite to
the PCB side and secure 600mm(23-5/8inch)
space near the compressor and PCB side of
the air conditioner for service.
h
Outdoor unit is representative. Actual appearance of outdoor unit may
be different but clearances will stay the same.
• Install the unit so that its discharge port faces to the
wall of the building. Keep a distance 500mm(19-
11/16inch) or more or more between the unit and
the wall surface.
• Supposing the wind direction during the operation
season of the air conditioner, install the unit so that
the discharge port is set at right angle to the wind
direction.
Turn the air outlet side toward the build-
ing's wall, fence or windbreak screen.
Set the outlet side at a right angle
to the direction of the wind.
h
Outdoor unit is representative. Actual appearance of outdoor unit may
be different but clearances will stay the same.
Unit : mm(inch)
Unit : mm(inch)