2.1 Sleeve and insert work
2.1.1 Positioning of the pipe holes
1. The through holes for the drain piping should be positioned such that pipes have a downward gradient (the gradient must
be at least 1/100.The thickness of the insulating materials must also be taken into consideration.)
2. The diameter of the through holes for the refrigerant piping should include an allowance for the thickness of the heat insu-
lation materials.
3. Attention should be paid to the construction of the beam themselves since there are sometimes parts of the beam which
cannot be used to accommodate through holes.
2.1.2 Selection of sleeve
Sleeve work should be performed to make a space for passing pipe through the wall or ground under
construction.
2. Guideline for each installation process
Heat pump 60Hz/R410A
_
3
Installation of
Outdoor Units
SINGLE ZONE
For example if gas pipe and liquid pipe is 1/2inch, 1/4inch the sleeve diameter is minimum 3.1 inch
* Assumption : Gas pipe insulation thickness and liquid pipe insulation thickness is 13/32 inch and 13/32 inch respectively
Gas pipe diameter 1/2"
Liquid pipe diameter 1/4"
Insulation thickness(gas pipe) 13/32" x 2
Insulation thickness(liquid pipe) 13/32" x 2
0.8inch surplus 32/25"
Total sleeve diameter 3-1/8"