3. Installation of indoor unit
3.1.4 Ceiling opening dimensions and
hanging bolt location
①
The dimensions of the paper pattern for installation are
the same as those of the ceiling opening dimensions.
②
Select and mark the position for fixing bolts and piping
hole.
③
Decide the position for fixing bolts slightly tilted to the
drain direction after considering the direction of drain
hose.
④
Drill the hole for anchor bolt on the wall.
1) Install the suspension bolts.
(Use either a W3/8” or M10 size bolt) Use a hole-in
anchor for existing ceilings, and a sunken insert, sunken
anchor or other field supplied parts for new ceilings to
reinforce the ceiling to bear the weight of the unit. Adjust
clearance from the ceiling before proceeding further.
All the above parts are field suppiled.
NOTE
Ceiling
Anchor
Long nut or turn-buckle
Suspension bolt
False ceiling
Unit:mm(inch)
TP/TM Model
875(34-7/16)
(Ceiling opening)
787(30-15/16)
(Hanging bolt)
684(26-15/16)
(Hanging bolt)
671(26-7/16)
875(34-7/16)
(Ceiling opening)
840(33)
Unit size
840(33) Unit size
Heat pump 60Hz/R410A
_
41
Installation of
Outdoor Units
SINGLE ZONE