Service Manual
59
Troubleshooting Guide
Additional gas charging
(Gas leakage)
• When refrigerant is insufficient by leakage, recharge the unit with the refrigerant up to normal operating suc-
tion pressure.
• Use the graph or the equation below to get operating suction pressure according to indoor and outdoor tem-
perature.
Suction pressure was measured at 3-way valve service port after operating the unit for 10 minutes.
The method of using graph
- Find outdoor temperature.
- Find indoor temperature onto the curve of outdoor temperature.
- Read suction pressure at the axis of ordinates.
The method of using equation
-. Calculate suction pressure after putting indoor and outdoor temperature into the equation.
13
(At operating the Unit for 10 minutes)
Suction Pressure
(Kg/cm
2
.g)
Outdoor Temp.
(˚
C)
Indoor Temp. (˚C)
12
11
10
9
8
7
6
5
5
10
15
20
25
30
35
40
50˚C
40˚C
30˚C
20˚C
10˚C
0˚C
P = 3 + 0.0123 x T
out
1.5
+ 0.8 x T
in
0.5
Where, P
: Suction Pressure(kg/cm
2
.g)
Tout : Outdoor Temperature(˚C)
Tin
: Indoor Temperature(˚C)
Operating Suction Pressure
(According to Indoor & Outdoor Temperature)
Summary of Contents for AS-C306MSeries
Page 44: ...44 Room Air Conditioner Schematic Diagram Model AS H366 Series ...
Page 45: ...Service Manual 45 Schematic Diagram 5 5 4 4 3 3 2 2 1 1 Model AS C306 Series ...
Page 46: ...46 Room Air Conditioner Schematic Diagram Model AS C366 Series ...
Page 49: ...Service Manual 49 Schematic Diagram Electronic Control Device INDOOR UNIT P W B ASSEMBLY ...
Page 51: ...Service Manual 51 Schematic Diagram DISPLAY P W B ASM ...
Page 73: ...Service Manual 73 Memo ...
Page 74: ...74 Room Air Conditioner Memo ...