Service Manual
53
Troubleshooting Guide
Pipe Length and the Elevation
* Capicity is based on standard length and maximum allowance length is the basis of
reliability.
*
Oil trap should be installed per 5~7 meters.
CAUTION
Outdoor unit
Indoor unit
A
B
A
Oil trap
Outdoor unit
Indoor unit
B
In case more than 5m
30k
5/8"
3/8"
7.5
15
30
30
(50Hz, 60Hz)
36k
3/4"
3/8"
7.5
20
30
50
(50Hz, 60Hz)
Pipe Size
Capacity
(Btu/h)
GAS
LIQUID
Additional
Refrigerant
(g/m)
Max.
Length
A (m)
Max.
Elevation
B (m)
Standard
Length
(m)