Service Manual
21
Installation
3) Connection of the drain hose
■
The drain hose can be connected at two different
positions. Use the most convenient position and, if
necessary, exchange the position of the drain
pan, rubber cap and the drain hose.
➊
Drain pan
➋
Rubber cap
➌
Drain hose
➍
Exchange if necessary
■
Remove the drain hose.
■
Securely insert both the rubber plug and drain
hose into the drain outlets.
Be sure the rubber the cap is securely fastened
so that there is no leakage.
4) Connection of piping-Outdoor
1. Align the center of the pipings and sufficiently
tighten the flare nut by hand.
2. Finally, tighten the flare nut with torque wrench
until the wrench clicks.
■
When tightening the flare nut with torque wrench,
ensure the direction for tightening follows the
arrow on the wrench.
1
2
3
4
Outdoor unit
Gas side piping
(Bigger diameter)
Liquid side
piping
(Smaller
diameter)
Torque wrench
Gas side piping
(Bigger diameter)
Liquid side piping
(Smaller diameter)
Torque wrench
30k
5/8"[6.6kg.m]
3/8"[4.2kg.m]
36k
3/4"[6.6kg.m]
3/8"[4.2kg.m]
Pipe Size[Torque]
Capacity
(Btu/h)
GAS
LIQUID
30k
36k
Summary of Contents for AS-C306MSeries
Page 44: ...44 Room Air Conditioner Schematic Diagram Model AS H366 Series ...
Page 45: ...Service Manual 45 Schematic Diagram 5 5 4 4 3 3 2 2 1 1 Model AS C306 Series ...
Page 46: ...46 Room Air Conditioner Schematic Diagram Model AS C366 Series ...
Page 49: ...Service Manual 49 Schematic Diagram Electronic Control Device INDOOR UNIT P W B ASSEMBLY ...
Page 51: ...Service Manual 51 Schematic Diagram DISPLAY P W B ASM ...
Page 73: ...Service Manual 73 Memo ...
Page 74: ...74 Room Air Conditioner Memo ...