22
Room Air Conditioner
Installation
Connecting the cable between indoor unit and outdoor unit
1) Connect the cable to the Indoor unit.
■
Connect the cable to the indoor unit by connect-
ing the wires to the terminals on the control
board individually according to the outdoor unit
connection.
(Ensure that the color of the wires of the
outdoor unit and the terminal No. are the same as
those of the indoor unit.)
RED
BLUE
BROWN
4(N)
Terminals on the indoor unit
3(L)
5
4(N)
Terminals on the outdoor unit
Color of Wires
POWER INPUT
Color of Wires
3(L)
2(N)
1(L)
5
G/Y
RED
BLUE
BROWN
G/Y
The power cord connected to the outdoor unit
should be complied with the following
specifications (Rubber insulation, type H05RN-F
approved by HAR or SAA).
The connecting cable connected to the indoor
and outdoor unit should be complied with the
following specifications (Rubber insulation, type
H07RN-F approved by HAR or SAA).
CAUTION
8.5mm
20mm
GN/YL
NORMAL
CROSS-SECTIONAL
AREA 2.5mm
2
8.5mm
20mm
GN/YL
NORMAL
CROSS-SECTIONAL
AREA 5.5mm
2
20mm
GN/YL
NORMAL
CROSS-SECTIONAL
AREA 0.75mm
2
7.5mm
30k
36k
If a power plug is not to be used,
provide a circuit breaker between
power source and the unit as
shown below.
CAUTION
Air
Conditioner
Main power source
Circuit Breaker
Use a circuit breaker
or time delay fuse.
Summary of Contents for AS-C306MSeries
Page 44: ...44 Room Air Conditioner Schematic Diagram Model AS H366 Series ...
Page 45: ...Service Manual 45 Schematic Diagram 5 5 4 4 3 3 2 2 1 1 Model AS C306 Series ...
Page 46: ...46 Room Air Conditioner Schematic Diagram Model AS C366 Series ...
Page 49: ...Service Manual 49 Schematic Diagram Electronic Control Device INDOOR UNIT P W B ASSEMBLY ...
Page 51: ...Service Manual 51 Schematic Diagram DISPLAY P W B ASM ...
Page 73: ...Service Manual 73 Memo ...
Page 74: ...74 Room Air Conditioner Memo ...