100
Universal System Air Conditioner
MPS Variable SINGLE A
8.5 Wiring Connection
1Phase
Heat Pump Model.
3Phase
Heat Pump Model.
The power cord
connected to the outdoor unit should be
complied with the following specifications (Rubber
insulation, type H05RN-F approved by HAR or SAA).
If the supply cord is damaged, it must be replaced by a special cord or assembly available from the manufacturer of its service agent.
The connecting cable
connected to the indoor and outdoor
unit should be complied with the following specifications
(Rubber insulation, type H05RN-F approved by HAR or SAA).
CAUTION
20mm
GN
/YL
NORMAL
CROSS-SECTIONAL
AREA 0.75mm
2
(12k/18k/24k/30k)
AREA 1.25mm
2
(36k/48k60k)
20mm
GN/YL
Capacity
12k BTU/h
18k BTU/h
24k BTU/h
30k BTU/h
36k BTU/h
48k BTU/h
60k BTU/h
1 Phase
1.0mm
2.5mm
2.5mm
2.5mm
-
-
-
3 Phase
-
-
-
-
2.5mm
2
3.0mm
2
3.0mm
2
NORMAL CROSS-SECTIONAL AREA
POWER
INPUT
Terminals on the indoor unit
Terminals on the outdoor unit
1(L) 2(N)
2(N)
3
1(L)
2(N)
3
4
5
1(L)
4
5
W
ARNING:
Make sure that the screws of the terminal are free from looseness.
Terminal Block
(Outdoor Unit)
Terminal Block
(Indoor Unit)
Power
Input
R
S
T
N
1(L) 2(N)
3
1(L) 2(N)
3
4
5
1. All wiring must comply with LOCAL REGULATIONS.
2. Select a power source that is capable of supplying the current as required by the air conditioner.
3. Feed the power source to the unit via a distribution switch board designed for this purpose.
4. The terminal screws inside the control box may be loose due to vibration during transport.
Check the screws for loose connection.
(Running the air conditioner with loose connection can overload and damage electrical components.)
5. Always ground the air conditioner with a grounding wire and connector to meet the LOCAL REGULATION.
Summary of Contents for ABNH186HLAC
Page 85: ...Service Manual 89 MPS Variable SINGLE A 4 Wiring Diagrams AUUH126C AUUH186C ...
Page 87: ...Electronic Control Device Service Manual 91 MPS Inverter SINGLE A AUUH368C AUUH488C ...
Page 88: ...92 Universal System Air Conditioner MPS Variable SINGLE A AUUH608C ...
Page 107: ...Electronic Control Device Service Manual 111 Ceiling Duct Type BH Series ...
Page 108: ...Electronic Control Device 112 Universal System Air Conditioner BG BR Series ...
Page 109: ...Electronic Control Device Service Manual 113 VE Series AC DC Ceiling Floor C ...
Page 110: ...Electronic Control Device 114 Universal System Air Conditioner VB VK VL Series ...
Page 113: ...Electronic Control Device Service Manual 117 Schematic Diagram Ceiling Duct Type ...
Page 134: ...Outdoor Units 138 Universal System Air Conditioner ...
Page 175: ...P No 3828A22009P Printed in Korea ...