Electronic Control Device
Service Manual
105
Electronic Parts Troubleshooting Guide
3. When cooling does not operate
Turn on Main Power
Operate "Cooling Mode( )" by setting the desired temperature of the
remote controller is less than one of the indoor temperature by 1°C at least.
When in Air Circulation Mode, Compressor/Outdoor Fan is stopped.
Check the sensor for indoor temperature is attached as close as to be
effected by the temperature of Heat Exchanger(EVA).
When the sensor circuit for indoor temperature and connector are in bad
connection or are not engaged, Compressor/Outdoor Fan is stopped.
• Check the indoor temperature sensor is disconnected or not(About 10k
Ω
/ at 25°C).
Check Relay(RY - COMP) for driving compressor.
• When the power(About AC220V/240V) is applied to the connecting wire
terminal support transferred to compressor, PWB Ass'y is normal.
• Check the circuit related to the relay.
Check point
COMP ON
COMP OFF
Below DC 1V
About DC12V
(app)
Between two pin of DC
part in relay for COMP
Summary of Contents for ABNH186HLAC
Page 85: ...Service Manual 89 MPS Variable SINGLE A 4 Wiring Diagrams AUUH126C AUUH186C ...
Page 87: ...Electronic Control Device Service Manual 91 MPS Inverter SINGLE A AUUH368C AUUH488C ...
Page 88: ...92 Universal System Air Conditioner MPS Variable SINGLE A AUUH608C ...
Page 107: ...Electronic Control Device Service Manual 111 Ceiling Duct Type BH Series ...
Page 108: ...Electronic Control Device 112 Universal System Air Conditioner BG BR Series ...
Page 109: ...Electronic Control Device Service Manual 113 VE Series AC DC Ceiling Floor C ...
Page 110: ...Electronic Control Device 114 Universal System Air Conditioner VB VK VL Series ...
Page 113: ...Electronic Control Device Service Manual 117 Schematic Diagram Ceiling Duct Type ...
Page 134: ...Outdoor Units 138 Universal System Air Conditioner ...
Page 175: ...P No 3828A22009P Printed in Korea ...