Electronic Control Device
106
Universal System Air Conditioner
Electronic Parts Troubleshooting Guide
4. When Heating does not operate
Operate “Heating Mode( )” by setting the desired temperature of the
remote control is higher than one of the indoor temperature by 2°C at
least.
In heating Mode, the indoor fan operates in case the pipe temperature
is higher than 28°C.
Check Outdoor Unit
Check the connector of intake and pipe sensor(thermistors)
• Check the indoor room temperature is disconnected or not (about
10K
Ω
/at 25°C).
• Check the indoor pipe temperature is disconnected or not (about
5K
Ω
/at 25°C).
Turn ON Main Power
Check the DC voltage on the PWB ASS’Y
• The details of check are as followings
Check point
Between two pin
of DC part in relay
for COMP.
Comp ON
Below DC 1V
Comp OFF
About DC
12V
Check point
Between two pin
of DC part in relay
for 4-way.
4-Way ON
Below DC 1V
4-Way OFF
About DC 12V
• Comp Relay.
• 4-Way Relay
Summary of Contents for ABNH186HLAC
Page 85: ...Service Manual 89 MPS Variable SINGLE A 4 Wiring Diagrams AUUH126C AUUH186C ...
Page 87: ...Electronic Control Device Service Manual 91 MPS Inverter SINGLE A AUUH368C AUUH488C ...
Page 88: ...92 Universal System Air Conditioner MPS Variable SINGLE A AUUH608C ...
Page 107: ...Electronic Control Device Service Manual 111 Ceiling Duct Type BH Series ...
Page 108: ...Electronic Control Device 112 Universal System Air Conditioner BG BR Series ...
Page 109: ...Electronic Control Device Service Manual 113 VE Series AC DC Ceiling Floor C ...
Page 110: ...Electronic Control Device 114 Universal System Air Conditioner VB VK VL Series ...
Page 113: ...Electronic Control Device Service Manual 117 Schematic Diagram Ceiling Duct Type ...
Page 134: ...Outdoor Units 138 Universal System Air Conditioner ...
Page 175: ...P No 3828A22009P Printed in Korea ...