128
Universal System Air Conditioner
Outdoor Units
Outdoor Units
1.Basic control
1.1 Normal operation
1.2 Compressor control
(1) Step Control : COMP Operation Step will be determined on the load according to the difference
between indoor Temp.and outdoor Temp.
- The general load
→
Operating in Standard Step
- Below the specified load
→
Operating in lower one step than standard step.
- The Hysterisis
→
Operating in a previous step .
Cooling mode
Heating mode
Stop state
Compressor
Fan
Phase control
Phase control
After 30sec, Off
EEV
4 way valve
Off
On
After 30sec, Off(Heating_
On/Off (1 Comp.)
Step Control (2 Comp.)
On/Off (1 Comp.)
Step Control (2 Comp.)
Stop
Target Suction super heat and
Discharge Temp. Control
Target Suction super heat and
Discharge Temp. Control
After 60sec, Full Opne
Capacity(Btu/h)
MODE
STEP1
STEP2
STEP3
B COMP
A COMP
B+A COMP
12k
Cooling
O
Heating
O
18k
Cooling
O
Heating
O
24k
Cooling
O
Heating
O
30k
Cooling
O
O
Heating
O
O
36k
Cooling
O
O
Heating
O
O
60k
Cooling
O
Heating
O
❈
Comp.Capacity Definition
1)Comp. B: 50% COMP
2)Comp. A: 50% COMP , Comp.A+B :100% COMP
Summary of Contents for ABNH186HLAC
Page 85: ...Service Manual 89 MPS Variable SINGLE A 4 Wiring Diagrams AUUH126C AUUH186C ...
Page 87: ...Electronic Control Device Service Manual 91 MPS Inverter SINGLE A AUUH368C AUUH488C ...
Page 88: ...92 Universal System Air Conditioner MPS Variable SINGLE A AUUH608C ...
Page 107: ...Electronic Control Device Service Manual 111 Ceiling Duct Type BH Series ...
Page 108: ...Electronic Control Device 112 Universal System Air Conditioner BG BR Series ...
Page 109: ...Electronic Control Device Service Manual 113 VE Series AC DC Ceiling Floor C ...
Page 110: ...Electronic Control Device 114 Universal System Air Conditioner VB VK VL Series ...
Page 113: ...Electronic Control Device Service Manual 117 Schematic Diagram Ceiling Duct Type ...
Page 134: ...Outdoor Units 138 Universal System Air Conditioner ...
Page 175: ...P No 3828A22009P Printed in Korea ...