Universal System Air Conditioner
Ceiling & Floor
■
Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.
COMP
Outdoor fan
Indoor fan
4way valve
Setting Temperature
+2
°
C(Unit Sensing)
0
°
C(Remo Sensing)
-1
°
C(Flore Install)
(Thermo ON)
Setting Temperature
+4
°
C(Unit Sensing)
+2
°
C(Remo Sensing)
+1
°
C(Flore Install)
(Thermo OFF)
Indoor unit
Heat-Exchanger
temperature
1min
Minimum
3min
1min
3min
Setting
fan
spped
Setting
fan
spped
Setting
fan
spped
ON
ON
ON
ON
Low
Low
Low
Low
Lo
Low
Off
Off
Off
ON
OFF
OFF
Low fan during 10sec
A
A
B
B
Intake Air Temperature
• Compressor-off interval
: - While the indoor Heat-Exchanger temperature is higher than 35
°
C, fan operates
at low speed, when it becomes lower than 35
°
C fan stops.
- For eluminating latent heat-loss, fan operates at low speed for 10 seconds periodically.
35
°
C
32
°
C
29
°
C
21
°
C
17
°
C
Summary of Contents for ABNH186HLAC
Page 85: ...Service Manual 89 MPS Variable SINGLE A 4 Wiring Diagrams AUUH126C AUUH186C ...
Page 87: ...Electronic Control Device Service Manual 91 MPS Inverter SINGLE A AUUH368C AUUH488C ...
Page 88: ...92 Universal System Air Conditioner MPS Variable SINGLE A AUUH608C ...
Page 107: ...Electronic Control Device Service Manual 111 Ceiling Duct Type BH Series ...
Page 108: ...Electronic Control Device 112 Universal System Air Conditioner BG BR Series ...
Page 109: ...Electronic Control Device Service Manual 113 VE Series AC DC Ceiling Floor C ...
Page 110: ...Electronic Control Device 114 Universal System Air Conditioner VB VK VL Series ...
Page 113: ...Electronic Control Device Service Manual 117 Schematic Diagram Ceiling Duct Type ...
Page 134: ...Outdoor Units 138 Universal System Air Conditioner ...
Page 175: ...P No 3828A22009P Printed in Korea ...