Service Manual
73
Ceiling Concealed Duct
Ceiling
CAUTION
1~3mm
Drainage hole
Drainage hole
U-Trap
B
C
A
≥
70mm
B
≥
2C
C
≥
2 x SP
SP = External Pressure
(mmAq)
Ex) External Pressure
= 10mmAq
A
≥
70mm
B
≥
40mm
C
≥
20mm
A
Make sure to be closed.
Unit
Drainage pipe
(Local supply)
Thermal insulator
(Local supply)
Drainage hole
CAUTION FOR GRADIENT OF
UNIT AND DRAIN PIPING
Lay the drain hose with a downware
inclination so water will drain out.
MAX 700mm
Drain Pipe
Drain Pump
1/50~1/100
1/50~1/100
Front of view
• Alway lay the drain with downward inclination
(1/50 to 1/100).
Prevent any upward flow or reverse flow in any
part.
• 5mm or thicker formed thermal insulator shall
always be provided for the drain pipe.
CORRECT
• Install the P-Trap (or U-Trap) to prevent
a water leakage caused by the blocking
of intake air filter.
Applied U-Trap Dimension
1.
Decline Installation
of indoor unit is very
important for the drain
of the duct type air conditioner.
2. Minimum thickness of the insulation for the connecting pipe should be 5mm.
• The unit must be or declined to wards drain hose while installation.
CORRECT
INCORRECT
INCORRECT
Summary of Contents for ABNH186HLAC
Page 85: ...Service Manual 89 MPS Variable SINGLE A 4 Wiring Diagrams AUUH126C AUUH186C ...
Page 87: ...Electronic Control Device Service Manual 91 MPS Inverter SINGLE A AUUH368C AUUH488C ...
Page 88: ...92 Universal System Air Conditioner MPS Variable SINGLE A AUUH608C ...
Page 107: ...Electronic Control Device Service Manual 111 Ceiling Duct Type BH Series ...
Page 108: ...Electronic Control Device 112 Universal System Air Conditioner BG BR Series ...
Page 109: ...Electronic Control Device Service Manual 113 VE Series AC DC Ceiling Floor C ...
Page 110: ...Electronic Control Device 114 Universal System Air Conditioner VB VK VL Series ...
Page 113: ...Electronic Control Device Service Manual 117 Schematic Diagram Ceiling Duct Type ...
Page 134: ...Outdoor Units 138 Universal System Air Conditioner ...
Page 175: ...P No 3828A22009P Printed in Korea ...