Part 5. Trouble Shooting
- 81 -
Copyright ©2014 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
23
DC Link High / Low Volt
• DC Link Voltage is
above 420Vdc
• DC Link Voltage is
below 140Vdc
• Check CN_(L), CN_(N) Connection
• Check Input Voltage
• Check PCB DC Link voltage sensor parts
Display
code
Title
Cause of error
Check point & Normal condition
■
Error Diagnosis and Countermeasure Flow Chart
Is Inverter PCB assembly
Power connection normal?
No
Check connection from terminal block to
Inverter PCB assembly CN(L), CN(N)
Yes
Is input voltage normal ?
No
Yes
Is Inverter PCB Normal?
No
Replace inverter PCB assembly
Recheck power and installation
condition
Yes
Check L~N Voltage is 230V±15%
WARNING
Before checking PCB or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby state
of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.