PROFINET interface
66
AMS 348
i
SSI
Leuze electronic GmbH + Co. KG
9.8.4.4 Step 4 – Transfer of the configuration to the IO controller (S7 PLC)
After the correct transfer to the IO Controller (S7 PLC), the PLC automatically carries out the
following activities:
• Check of device names
• Assignment of the IP addresses that were configured in the HW Config to the IO devices
• Establishment of a connection between the IO Controller and configured IO devices
• Cyclical data exchange
Note!
Participants without assigned device names cannot yet be addressed at this point in time!
9.8.4.5 Step 5 – Configuration of the device name – device naming
Each AMS 348
i
has an individual and unique MAC ID. The MAC ID can be found on the name
plate of the device.
Figure 9.9: MAC ID on the name plate
Note!
This figure is for illustration only and does not correspond in all details to the
AMS 348
i
. The
MAC ID in particular must be read separately from each individual device. The MAC ID is
also shown in the display of the
AMS 348
i
.
Address Link Label:
The "Address Link Label" is an additional stick-on label that is affixed to the device.