Display and control panel
Leuze electronic
BCL 504
i
79
TNT 35/7-24V
Status display of the USB interface
USB
The BCL 504
i
is connected to a PC via the USB interface.
MS
An external parameter memory is properly connected to the USB interface of the
BCL 504
i
.
Read result
The read barcode information is displayed.
Device address
Indicates the set PROFIBUS network address (default = 126).
8.2.2
LED status indicators
PWR LED
off
Device OFF
-
no supply voltage
flashes green
Device ok, initialisation phase
-
no barcode reading possible
-
voltage connected
-
self test running
-
initialisation running
green continuous light Device ok
-
barcode reading possible
-
self test successfully finished
-
device monitoring active
orange continuous light Service mode
-
barcode reading possible
-
configuration via the USB service interface
-
configuration via the display
-
no data on the host interface
flashes red
Device ok, warning set
-
barcode reading possible
-
temporary operating fault
red continuous light
Device error / parameter enable
-
no barcode reading possible