PROFIBUS interface
69
AMS 304
i
Leuze electronic
9.4.3.8
Module 7: Position limit value range 1
Description
The position limit value range 1 parameter defines a distance range with lower and upper
limits. If the measured value lies outside of the configured range, the corresponding bit is
set in module 6 or, if configured, an output is set.
Parameters
Hex code of the "position limit value range 1" parameter
The value listed in this table shows the hex coding of the default settings:
Input data
no
Output data
no
Parameter
Description
Rel.
addr.
Data
type
Value
Default
Unit
CR to
module
metr.
Inch
Lower pos.
limit 1
Specifies the lower position limit.
0…3
sign
32 bit
-999999 … +999999
0
mm
in/100 –
Upper pos.
limit 1
Specifies the upper position limit.
4…7
sign
32 bit
-999999 … +999999
0
mm
in/100 –
Parameter length: 8 bytes
a
b
Module address
Lowe
r
pos.
limit 1
Upp
e
r
pos.
limit 1
07
00 00 00 00
00 00 00 00