SSI
95
AMS 304
i
Leuze electronic
10.3
General Information to the AMS 304
i
parameters
Attention!
Using the PROFIBUS and SSI interface simultaneously
:
The SSI interface settings are performed by the PROFIBUS. If settings which differ from the
default settings for the parameters, are to be used, they must be configured via module 17
(SSI interface).
Using the SSI interface without PROFIBUS
:
For this operating mode deactivate the PROFIBUS via the display (PROFIBUS = OFF).
Default parameters are stored in the laser measurement system for the sole use of the SSI
interface. The preset default parameters can be changed at any time via the display.
This also applies when using parameters which do not relate directly to the SSI interface
(for example: I/O 1 or I/O 2, position value or others).
The SSI interface remains active even during parameter enabling. Changes to parameters
have an immediate effect.
10.4
Default settings of the SSI interface
Table 10.2:
Default settings of the SSI interface
Default parameters which apply only to the SSI interface.
SSI activation
ON
Measurement value coding
Gray
Transmission mode
24-bit measurement value + 1-bit error (error: 1 = active), error bit = LSB
Resolution
0.1 mm
Default error bit
Plausibility error or hardware error
Update rate
1,7 ms
Default parameters which apply to both PROFIBUS and SSI.
Measurement unit
Metric
Count direction
Positive (the SSI interface cannot represent negative values)
I/O 1
Output – plausibility error or hardware error
I/O 2
Output – temperature error, intensity error or laser prefailure message
Static preset
+000.000
Dynamic preset
+000.000
Position limit value range 1
Lower limit and upper limit: both 0
Position limit value range 2
Lower limit and upper limit: both 0
Error handling procedures
Position output: 0
Suppress position status: active
Position suppression time: 100 ms
Display language
English
Display illumination
OFF after 10 min.
Display contrast
Medium
Password protection
Off
Password
0000