CMVETH01B
44
Cyclic Data Access
5.7.6.6
P45x = 6, Drive RUN Status
The Drive RUN status indicates the run status the drive is currently in.
Table 18: Drive RUN Status
RUN Status Value Description
0
Drive Faulted, attempted restart & locked; Requires manual reset
1
Drive Faulted; Check P500 Fault History and correct fault condition
2
Drive has tripped into a fault and will automatically restart
3
Identification not complete
4
Forced Coast Stop
5
Drive is Stopped
6
Drive is Preparing to Run
7
Drive is in Identification State
8
Drive is in Run State
9
Drive is Accelerating
10
Drive is Decelerating
11
Drive stopped decelerating to avoid tripping HF fault, due to excessive motor regen (2 s max)
12
DC Injection brake activated
13
Flying Restart Attempt after Fault
14
Current Limit Reached
15
Fast Current Limit Overload
16
Drive is in Sleep Mode
5.7.6.7
P45x = 7, Drive Fault Status
The Drive Fault Status indicates the drive’s present fault condition.
Table 19: Drive Fault Status
Fault Codes
Fault Number
Display
Fault Description
0
NO FAULT
1
F.AF
Temperature Output Fault
2
F.OF
Over Current Fault
3
F.OF1
Ground (Short to Earth) Fault
4
F.AF
Excess Drive Temperature Fault
5
F.rF
Fly Start Fault
6
F.hF
High Bus Voltage (Over Voltage) Fault
7
F.LF
Low Bus Voltage (Under Voltage) Fault
8
F.PF
Motor Overload Fault
9
F.JF
OEM Defaults Corrupted Fault
10
F.IL
Illegal Setup Fault
11
F.dbF
Dynamic Brake Overheated Fault
12
F.SF
Single Phase Voltage Ripple to High Fault
13
F.EF
External Fault
14
F.CF
Control EEPROM Fault
15
F.UF
Start Power Loss Fault