CMVETH01B
54
Acyclic Data Access
For any explicit message the path will need to be set to route the message out the controller’s Ethernet port
to the IP address of the Drive. This path will differ with the PLC used. Consult the PLC manufacturer for
assistance with determining how to set this path if needed.
6.3 Explicit Messaging Timeout
It is often desirable to set a fault timeout condition to prevent the drive from operating in a runaway
condition. To do this while controlling the drive via explicit messaging, set P431, P433 and P434 to 0. Set
the timeout period desired (in milliseconds) in P435.