Diagnostics
LED status displays
9
EDKMF2178IB DE/EN/FR 6.0
77
l
H1_Diagnose−statusanzeige−DriveLED
9
Diagnostics
LED status displays
Pos.
Status display (LED)
Description
0
Connection status to standard device, two−colour LED (green/red)
OFF
l
The communication module is not supplied with voltage.
l
The external voltage supply is switched off.
GREEN
Blinking
The communication module is supplied with voltage, but has
no connection to the standard device.
Cause:
The standard device is ...
l
switched off;
l
in the initialisation phase;
l
not available.
Constantly ON
The communication module is supplied with voltage and is
connected to the standard device.
RED
Constantly ON
CANopen operation impossible.
Blinking
Permanently:
l
Parameters are reset to Lenze setting.
l
CANopen operation possible.
1 x blinking:
l
An error occurred while saving a value.
2 x blinking:
l
CANopen operation possible.
l
The node address/baud rate from C1850/C2350 or
C1851/C2351 could not be accepted .