Commissioning
Possible settings via DIP switch
EDKMF2178IB DE/EN/FR 6.0
68
l
H1inbet−HINW_Einst_aktivieren_KommModule
Baud rate setting
1 2 3 4 5 6 7 8 910
OPEN
ON
OFF
Bd
Address
Fig. 6
Baud rate setting
ƒ The baud rate must be the same for all CAN nodes.
ƒ The following baud rates can be set:
Baud rate
[kbps]
Switch
8
9
10
10
ON
ON
OFF
20
ON
OFF
ON
50
OFF
ON
ON
125
OFF
ON
OFF
250
OFF
OFF
ON
500
OFF
OFF
OFF
1000
ON
OFF
OFF
)
Note!
Switch off the voltage supply of the communication module, and then switch
it on again to activate the changed settings.