Electrical installation
Wiring to a host
EDKMF2178IB DE/EN/FR 6.0
57
l
H2 VerdrahtLeitrechner−Belegung_Steckerleiste_2178
Wiring to a host
{
Danger!
An additional electrical isolation is required if a safe electrical isolation
(reinforced insulation) to EN61800−5−1 is necessary.
For this purpose for instance an interface module for the master computer with an
additional electrical isolation can be used (see respective manufacturer information).
For wiring observe the electrical isolation of the supply voltage. The supply voltage is on the
same potential as the data bus.
The 5−pole plug connector with double screw connection serves to
ƒ connect the bus (
ƒ effect the external voltage supply (
CAN_L SHLD
V+
CAN_H
GND
120
W
2178CAN003
Fig. 3
5−pole plug connector with double screw connection
Designation
Explanation
GND
Reference potential for external voltage supply
CAN−GND connection
CAN_L
Data line / input for terminating resistor 120
SHIELD
Shielding
CAN_H
Data line / input for terminating resistor 120
V+
External voltage supply