• Connect the supply hose assembly (
1
) to the supply manifold-coupling (
2
).
• Connect the return hose assembly (
3
) to the return manifold-coupling (
4
).
Step 5. Turn on the flow of water to the heat exchanger, and let it run for several minutes.
Step 6. Attach the air-purging tool to the air-purging valve at the top of the heat exchanger, and place the
drain end into a 2-liter (or larger) container to catch the water and air bubbles that escape during
the filling procedure.
Figure 125. Installing the air-purging tool
Step 7. When there is a steady stream of liquid into the container from the air-purging tool, disconnect the
tool from the heat exchanger.
Attention:
If water drips from the air-purging valve after you remove the air-purging tool, reattach
the tool and disconnect it again to seal the valve.
.
Hardware removal, installation and reversion
111
Summary of Contents for ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet
Page 1: ...ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide Machine Type 7D6D ...
Page 4: ...ii ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide ...
Page 16: ...12 ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide ...
Page 23: ...Figure 19 Rising the leveling pads Chapter 3 Rack cabinet setup 19 ...
Page 146: ...142 ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide ...
Page 152: ...148 ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide ...
Page 153: ......
Page 154: ......