background image

Page 10

505095M 1/3/06

Flushing Connections

Low

Pressure

High

Pressure

Vapor Line
Service Valve

EXISTING

INDOOR COIL

XC15

UNIT

GAUGE MANIFOLD

Inverted R−22 Cylinder
(Contains clean R−22 to
be used for flushing)

Liquid Line
Service Valve

Inlet

Discharge

Tank Return

Closed

Opened

EXISTING LIQUID LINE

RECOVERY CYLINDER

NOTE − The inverted R−22 cylinder
must contain at least the same
amount of refrigerant as was recov-
ered from the existing system.

Figure 13

EXISTING VAPOR LINE

RECOVERY MACHINE

3. Make low voltage and line voltage connections to the

new outdoor unit. 

Do NOT turn on power to unit or

open the outdoor unit service valves at this time.

4. Remove the existing refrigerant flow control orifice or

thermal expansion valve before continuing with flush-
ing procedures. Existing devices are not approved for
use with R−410A refrigerant and may prevent proper
flushing. Use a field−provided fitting to reconnect  lines.

IMPORTANT

The line set and indoor coil must be flushed with
at least the same amount of clean refrigerant that
previously charged the system. Check the charge
in the flushing cylinder before proceeding.

5. Remove the pressure tap valve cores from the XC15

unit’s service valves. Connect an R−22 cylinder with
clean refrigerant to the vapor service valve. Connect
the R−22 gauge set to the liquid line valve. Connect a
recovery machine with an empty recovery tank to the
gauge set.

6. Set the recovery machine for liquid recovery and start

the recovery machine. Open the gauge set valves to
allow the recovery machine to pull a vacuum on the ex-
isting system line set and indoor coil.

7. Invert the cylinder of clean R−22 and open its valve to

allow liquid refrigerant to flow into the system through
the vapor line valve. Allow the refrigerant to pass from
the cylinder and through the line set and the indoor coil
before it enters the recovery machine.

8. After all of the liquid refrigerant has been recovered,

switch the recovery machine to vapor recovery so that

all of the R−22 vapor is recovered. Allow the recovery
machine to pull a vacuum on the system.

NOTE − A single system flush should remove all of the
mineral oil from the existing refrigerant lines and in-
door coil. A second flushing may be done (using clean
refrigerant) if insufficient amounts of mineral oil were
removed during the first flush.

 Each time the system

is flushed, you must allow the recovery machine
to pull a vacuum on the system at the end of the
procedure.

9. Close the valve on the inverted R−22 drum and the

gauge set valves. Pump the remaining refrigerant out
of the recovery machine and turn the machine off.

10. Use dry nitrogen to break the vacuum on the refriger-

ant lines and indoor coil before removing the recovery
machine, gauges and R−22 refrigerant drum. Reinstall
pressure tap valve cores into XC15 service valves.

11. Install the expansion valve in the liquid line at the in-

door coil.

Refrigerant Metering Device

XC15 units may be used in thermal expansion valve (TXV)
systems only. See the indoor coil installation instructions
and the Lennox Engineering Handbook for approved TXV
match−ups and application information. Table 2 (on
Page 6) lists liquid and vapor line sizes and correspond-
ing line sets.
Expansion valves equipped with Chatleff type fittings are
available from Lennox. Refer to the Engineering Hand-
book for expansion valves for use with specific match−ups.
If you install an expansion valve with an indoor coil that in-
cludes a fixed orifice, remove the orifice before the expan-
sion valve is installed (see figure 14).

Summary of Contents for XC15-024

Page 1: ...low voltage wiring 2 Grommets for liquid and vapor lines Check equipment for shipping damage If you find any damage immediately contact the last carrier INSTALLATION INSTRUCTIONS XC15 Series Units CON...

Page 2: ...UND REDUCTION COVER SEE PAGE 20 FOR COVER INFORMATION COMPRESSOR TERMINAL PLUG HIGH PRESSURE SWITCH Figure 1 37 940 024 thru 042 47 1194 048 and 060 21 1 8 537 024 thru 042 31 1 8 791 048 and 060 10 3...

Page 3: ...NG This product and or the indoor unit it is matched with may contain fiberglass wool Disturbing the insulation during installation main tenance or repair will expose you to fiberglass wool dust Breat...

Page 4: ...uide the LIP of top tab inward fig ure 5 Details A and C then upward into the top slot of the hinge corner post S Rotate panel to vertical to fully engage all tabs S Holding the panel s hinged side fi...

Page 5: ...for field wiring diagram A complete unit wiring dia gram is located on the back side of the access panel NOTE For proper voltages select thermostat wire gauge per the following chart Wire run length A...

Page 6: ...Refrigerant Line If refrigerant lines are routed through a wall seal and iso late the opening so vibration is not transmitted to the build ing Pay close attention to line set isolation during installa...

Page 7: ...for use with R 410A refriger ant While brazing in the line set connections wrap a wet cloth around the valve body and the copper tube stubs 4 Quench the joints with a wet cloth to prevent possible he...

Page 8: ...LIQUID LINE Refrigerant Line Sets Installing Vertical Runs new construction shown NOTE Similar installation practices should be used if line set is to be installed on exterior of outside wall PVC PIPE...

Page 9: ...maintenance service repair and disposal of appliance Approved methods of recovery recycl ing or reclaiming must be followed 1 Remove existing R 22 refrigerant using the following appropriate procedure...

Page 10: ...liquid refrigerant to flow into the system through the vapor line valve Allow the refrigerant to pass from the cylinder and through the line set and the indoor coil before it enters the recovery machi...

Page 11: ...Schrader valve from contamination and serves as the primary leak seal To Access Schrader Port 1 Remove service port cap with an adjustable wrench 2 Connect gauge to the service port 3 When testing is...

Page 12: ...the manifold gauge set Open the valve on the R 410A cylinder va por only 3 Open the high pressure side of the manifold to allow R 410A into the line set and indoor unit Weigh in a trace amount of R 4...

Page 13: ...frozen bearings or binding 2 Inspect all factory and field installed wiring for loose connections 3 After evacuation is complete open the liquid line and vapor line service valves to release the refri...

Page 14: ...arge If weighing facili ties are not available or if charging the unit during warm weather use one of the following procedures Charge Using the Approach Method Outdoor Temp 65 F 18 C The following pro...

Page 15: ...results use the same electronic thermometer to check both outdoor ambient and liquid line temperatures F 1 0 C 0 5 1 With the manifold gauge hose still on the liquid service port and the unit operatin...

Page 16: ...0 psi Filter Drier A drier is factory installed in each XC15 unit A replace ment drier is available from Lennox Refer to Lennox Re pair Part Program System Operation Monitor LSOM The diagnostic indica...

Page 17: ...not present R and C wires are reversed Thermostat demand signal Y1 is present but compres sor not running 1 Compressor protector is open 2 Outdoor unit power disconnect is open 3 Compressor circuit br...

Page 18: ...is connect switch es Unit may have multiple power supplies Maintenance and service must be performed by a qualified installer or service agency At the beginning of each cool ing season check the syste...

Page 19: ...m call your Lennox dealer for assistance IMPORTANT Turn off electrical power to the unit at the disconnect switch before performing any maintenance The unit may have multiple power supplies 3 Reusable...

Page 20: ...tch from heating mode to cooling mode to maintain predetermined comfort settings Temperature Indicator The temperature indicator displays the actual room temperature Programmable Thermostats Your Lenn...

Reviews: