Table 7

R−410A Temperature (°F) − Pressure (Psig)

°F

Psig

°F

Psig

°F

Psig

°F

Psig

32

100.8

63

178.5

94

290.8

125

445.9

33

102.9

64

181.6

95

295.1

126

451.8

34

105.0

65

184.3

96

299.4

127

457.6

35

107.1

66

187.7

97

303.8

128

463.5

36

109.2

67

190.9

98

308.2

129

469.5

37

111.4

68

194.1

99

312.7

130

475.6

38

113.6

69

197.3

100

317.2

131

481.6

39

115.8

70

200.6

101

321.8

132

487.8

40

118.0

71

203.9

102

326.4

133

494.0

41

120.3

72

207.2

103

331.0

134

500.2

42

122.6

73

210.6

104

335.7

135

506.5

43

125.0

74

214.0

105

340.5

136

512.9

44

127.3

75

217.4

106

345.3

137

519.3

45

129.7

76

220.9

107

350.1

138

525.8

46

132.2

77

224.4

108

355.0

139

532.4

47

134.6

78

228.0

109

360.0

140

539.0

48

137.1

79

231.6

110

365.0

141

545.6

49

139.6

80

235.3

111

370.0

142

552.3

50

142.2

81

239.0

112

375.1

143

559.1

51

144.8

82

242.7

113

380.2

144

565.9

52

147.4

83

246.5

114

385.4

145

572.8

53

150.1

84

250.3

115

390.7

146

579.8

54

152.8

85

254.1

116

396.0

147

586.8

55

155.5

86

258.0

117

401.3

148

593.8

56

158.2

87

262.0

118

406.7

149

601.0

57

161.0

88

266.0

119

412.2

150

608.1

58

163.9

89

270.0

120

417.7

151

615.4

59

166.7

90

274.1

121

423.2

152

622.7

60

169.6

91

278.2

122

428.8

153

630.1

61

172.6

92

282.3

123

434.5

154

637.5

62

175.4

93

286.5

124

440.2

155

645.0

System Operation

The outdoor unit and indoor blower cycle on demand from
the room thermostat. When the thermostat blower switch
is in the 

ON

 position, the indoor blower operates continu-

ously.

High Pressure Switch

XC15 units are equipped with a high pressure switch that is
located in the liquid line to the compressor. The switch is a
SPST, manual−reset switch that is normal closed. The
switch opens at 590 psi.

Low Pressure Switch

XC15 units are equipped with a low pressure switch that is
located in the vapor line to the compressor. The switch is a
SPST, auto−reset switch that is normal closed. The switch
opens at 40 psi and closes at 90 psi.

Filter Drier

A drier is factory−installed in each XC15 unit. A replace-
ment drier is available from Lennox. Refer to Lennox Re-
pair Part Program.

System Operation Monitor (LSOM)

The diagnostic indicator detects the most common fault
conditions in the air conditioning system. When an abnor-
mal condition is detected, the module communicates the
specific condition through its ALERT and TRIP lights. The
module is capable of detecting both mechanical and elec-
trical system problems. See figure 18 for the system op-
eration monitor.

System Operation Monitor

Figure 18

.25" SPADE
CONNECTOR (4)

POWER LED

Y

DATA OUTPUT
CONNECTOR

L

R

C

ALERT LED

TRIP LED

IMPORTANT

This monitor does not provide safety protection.
The monitor is a monitoring device only and cannot
control or shut down other devices

.

LSOMLED Functions

Power LED (green)

indicates

 

voltage within the range of

19−28VAC is present at the system monitor power connec-
tion.

Alert LED (yellow)

communicates an abnormal system

condition through a unique Flash Code the alert LED
flashes a number of times consecutively; then pauses;
then repeats the process. This consecutive flashing corre-
lates to a particular abnormal condition.

Trip LED (red)

indicates there is a demand signal from

the thermostat but no current to the compressor is de-
tected by the module.
Refer to table 8 for the complete explanation of trouble-
shooting codes.

Resetting alert codes

Alert codes can be reset manual-

ly or automatically:

S

Manual reset: Cycle the 24VAC power to LSOM off
and on. After power up, existing code will display for
1 minute and then clear.

S

Automatic reset: After an alert is detected, the LSOM
continues to monitor the compressor and system.
When/if conditions return to normal, the alert code is
turned off automatically.

LSOML terminal connection

The L connection is used to communicate alert  codes  to
the room thermostat. On selected Lennox SignatureStat

t

thermostats, a blinking check" LED will display on the
room thermostat and on select White-Rodgers room ther-
mostats, an icon on the display will flash. Either will flash at
the same rate as the LSOM yellow alert LED.

Summary of Contents for XC15-024

Page 1: ...low voltage wiring 2 Grommets for liquid and vapor lines Check equipment for shipping damage If you find any damage immediately contact the last carrier INSTALLATION INSTRUCTIONS XC15 Series Units CON...

Page 2: ...UND REDUCTION COVER SEE PAGE 20 FOR COVER INFORMATION COMPRESSOR TERMINAL PLUG HIGH PRESSURE SWITCH Figure 1 37 940 024 thru 042 47 1194 048 and 060 21 1 8 537 024 thru 042 31 1 8 791 048 and 060 10 3...

Page 3: ...NG This product and or the indoor unit it is matched with may contain fiberglass wool Disturbing the insulation during installation main tenance or repair will expose you to fiberglass wool dust Breat...

Page 4: ...uide the LIP of top tab inward fig ure 5 Details A and C then upward into the top slot of the hinge corner post S Rotate panel to vertical to fully engage all tabs S Holding the panel s hinged side fi...

Page 5: ...for field wiring diagram A complete unit wiring dia gram is located on the back side of the access panel NOTE For proper voltages select thermostat wire gauge per the following chart Wire run length A...

Page 6: ...Refrigerant Line If refrigerant lines are routed through a wall seal and iso late the opening so vibration is not transmitted to the build ing Pay close attention to line set isolation during installa...

Page 7: ...for use with R 410A refriger ant While brazing in the line set connections wrap a wet cloth around the valve body and the copper tube stubs 4 Quench the joints with a wet cloth to prevent possible he...

Page 8: ...LIQUID LINE Refrigerant Line Sets Installing Vertical Runs new construction shown NOTE Similar installation practices should be used if line set is to be installed on exterior of outside wall PVC PIPE...

Page 9: ...maintenance service repair and disposal of appliance Approved methods of recovery recycl ing or reclaiming must be followed 1 Remove existing R 22 refrigerant using the following appropriate procedure...

Page 10: ...liquid refrigerant to flow into the system through the vapor line valve Allow the refrigerant to pass from the cylinder and through the line set and the indoor coil before it enters the recovery machi...

Page 11: ...Schrader valve from contamination and serves as the primary leak seal To Access Schrader Port 1 Remove service port cap with an adjustable wrench 2 Connect gauge to the service port 3 When testing is...

Page 12: ...the manifold gauge set Open the valve on the R 410A cylinder va por only 3 Open the high pressure side of the manifold to allow R 410A into the line set and indoor unit Weigh in a trace amount of R 4...

Page 13: ...frozen bearings or binding 2 Inspect all factory and field installed wiring for loose connections 3 After evacuation is complete open the liquid line and vapor line service valves to release the refri...

Page 14: ...arge If weighing facili ties are not available or if charging the unit during warm weather use one of the following procedures Charge Using the Approach Method Outdoor Temp 65 F 18 C The following pro...

Page 15: ...results use the same electronic thermometer to check both outdoor ambient and liquid line temperatures F 1 0 C 0 5 1 With the manifold gauge hose still on the liquid service port and the unit operatin...

Page 16: ...0 psi Filter Drier A drier is factory installed in each XC15 unit A replace ment drier is available from Lennox Refer to Lennox Re pair Part Program System Operation Monitor LSOM The diagnostic indica...

Page 17: ...not present R and C wires are reversed Thermostat demand signal Y1 is present but compres sor not running 1 Compressor protector is open 2 Outdoor unit power disconnect is open 3 Compressor circuit br...

Page 18: ...is connect switch es Unit may have multiple power supplies Maintenance and service must be performed by a qualified installer or service agency At the beginning of each cool ing season check the syste...

Page 19: ...m call your Lennox dealer for assistance IMPORTANT Turn off electrical power to the unit at the disconnect switch before performing any maintenance The unit may have multiple power supplies 3 Reusable...

Page 20: ...tch from heating mode to cooling mode to maintain predetermined comfort settings Temperature Indicator The temperature indicator displays the actual room temperature Programmable Thermostats Your Lenn...

Reviews: