background image

Page 18

505095M 1/3/06

System Operation Monitor LED Troubleshooting Codes

Status LED Condition

Status LED Troubleshooting  Information

Status LED Description

Yellow Alert" Flash
Code 6*

Open Start Circuit 

− Current

only in run circuit

1

Run capacitor has failed.

2

Open circuit in compressor start wiring or connections.

3

Compressor start winding is damaged.

Yellow Alert" Flash
Code 7*

Open Run Circuit

 − Current

only in start circuit

1

Open circuit in compressor start wiring or connections.

2

Compressor start winding is damaged.

Yellow Alert" Flash
Code 8*

Welded Contactor 

 

Com-

pressor always runs

1

Compressor contactor failed to open.

2

Thermostat demand signal not connected to module.

Yellow Alert" Flash
Code 9*

Low Voltage 

 − Control cir-

cuit <17VAC

1

Control circuit transformer is overloaded

.

2

Low line voltage (contact utility if voltage at disconnect is low).

*Flash code number corresponds to a number of LED flashes, followed by a pause, and then repeated. Reset ALERT flash
code by removing 24VAC power from monitor; last code will display for 1 minute after monitor is powered on.

Last code will display for 1 minute when power is cycled to module. Power must be on to module for a minimum of 1 minute
for code to clear.

 

Maintenance

WARNING

Electric shock hazard. Can cause inju-
ry or death. Before attempting to per-
form any service or maintenance, turn
the electrical power to unit OFF at dis-
connect switch(es). Unit may have
multiple power supplies.

Maintenance and service must be performed by a qualified
installer or service agency. At the beginning of each cool-
ing season, check the system as follows:

NOTE − Outdoor fan motor is prelubricated and sealed. No
further lubrication is needed.

1. Clean and inspect the outdoor coil. The coil may be

flushed with a water hose. Ensure the power is turned
off before you clean the coil.

2. Check connecting lines and coils for signs of oil leaks.

3. Check wiring for loose connections.

4. Check for correct voltage at unit (unit operating).

5. Check amp−draw outdoor fan motor.

Unit nameplate _________ Actual ____________ .

NOTE − If owner reports insufficient cooling, the unit
should be gauged and refrigerant charge checked.
Refer to section on refrigerant charging section
(Page 13).

Indoor Coil

1. Clean coil, if necessary.
2. Check connecting lines and coils for signs of oil leaks.
3. Check condensate line and clean, if necessary.

Indoor Unit

1. Clean or change filters.
2. Adjust blower speed for cooling. Measure the pressure

drop over the coil to determine the correct blower CFM.
Refer to the unit information service manual for pressure
drop tables and procedure.

3. Check blower for accumulation of dirt or debris.
4. Check all wiring for loose connections
5. Check for correct voltage at unit (blower operating).
6. Check amp−draw on blower motor

Unit nameplate_________ Actual ____________.

Optional Accessories

Optional accessories for the XC15 include the following
(also, see Engineering Handbook for more details):

S

Timed-off control

S

Low ambient kit

Summary of Contents for XC15-024

Page 1: ...low voltage wiring 2 Grommets for liquid and vapor lines Check equipment for shipping damage If you find any damage immediately contact the last carrier INSTALLATION INSTRUCTIONS XC15 Series Units CON...

Page 2: ...UND REDUCTION COVER SEE PAGE 20 FOR COVER INFORMATION COMPRESSOR TERMINAL PLUG HIGH PRESSURE SWITCH Figure 1 37 940 024 thru 042 47 1194 048 and 060 21 1 8 537 024 thru 042 31 1 8 791 048 and 060 10 3...

Page 3: ...NG This product and or the indoor unit it is matched with may contain fiberglass wool Disturbing the insulation during installation main tenance or repair will expose you to fiberglass wool dust Breat...

Page 4: ...uide the LIP of top tab inward fig ure 5 Details A and C then upward into the top slot of the hinge corner post S Rotate panel to vertical to fully engage all tabs S Holding the panel s hinged side fi...

Page 5: ...for field wiring diagram A complete unit wiring dia gram is located on the back side of the access panel NOTE For proper voltages select thermostat wire gauge per the following chart Wire run length A...

Page 6: ...Refrigerant Line If refrigerant lines are routed through a wall seal and iso late the opening so vibration is not transmitted to the build ing Pay close attention to line set isolation during installa...

Page 7: ...for use with R 410A refriger ant While brazing in the line set connections wrap a wet cloth around the valve body and the copper tube stubs 4 Quench the joints with a wet cloth to prevent possible he...

Page 8: ...LIQUID LINE Refrigerant Line Sets Installing Vertical Runs new construction shown NOTE Similar installation practices should be used if line set is to be installed on exterior of outside wall PVC PIPE...

Page 9: ...maintenance service repair and disposal of appliance Approved methods of recovery recycl ing or reclaiming must be followed 1 Remove existing R 22 refrigerant using the following appropriate procedure...

Page 10: ...liquid refrigerant to flow into the system through the vapor line valve Allow the refrigerant to pass from the cylinder and through the line set and the indoor coil before it enters the recovery machi...

Page 11: ...Schrader valve from contamination and serves as the primary leak seal To Access Schrader Port 1 Remove service port cap with an adjustable wrench 2 Connect gauge to the service port 3 When testing is...

Page 12: ...the manifold gauge set Open the valve on the R 410A cylinder va por only 3 Open the high pressure side of the manifold to allow R 410A into the line set and indoor unit Weigh in a trace amount of R 4...

Page 13: ...frozen bearings or binding 2 Inspect all factory and field installed wiring for loose connections 3 After evacuation is complete open the liquid line and vapor line service valves to release the refri...

Page 14: ...arge If weighing facili ties are not available or if charging the unit during warm weather use one of the following procedures Charge Using the Approach Method Outdoor Temp 65 F 18 C The following pro...

Page 15: ...results use the same electronic thermometer to check both outdoor ambient and liquid line temperatures F 1 0 C 0 5 1 With the manifold gauge hose still on the liquid service port and the unit operatin...

Page 16: ...0 psi Filter Drier A drier is factory installed in each XC15 unit A replace ment drier is available from Lennox Refer to Lennox Re pair Part Program System Operation Monitor LSOM The diagnostic indica...

Page 17: ...not present R and C wires are reversed Thermostat demand signal Y1 is present but compres sor not running 1 Compressor protector is open 2 Outdoor unit power disconnect is open 3 Compressor circuit br...

Page 18: ...is connect switch es Unit may have multiple power supplies Maintenance and service must be performed by a qualified installer or service agency At the beginning of each cool ing season check the syste...

Page 19: ...m call your Lennox dealer for assistance IMPORTANT Turn off electrical power to the unit at the disconnect switch before performing any maintenance The unit may have multiple power supplies 3 Reusable...

Page 20: ...tch from heating mode to cooling mode to maintain predetermined comfort settings Temperature Indicator The temperature indicator displays the actual room temperature Programmable Thermostats Your Lenn...

Reviews: