background image

Page 9

XC15 SERIES

Flushing Existing Line Set & Indoor Coil

WARNING

Danger of fire. Bleeding the refriger-
ant charge from only the high side
may result in the low side shell and
suction tubing being pressurized. Ap-
plication of a brazing torch while
pressurized may result in ignition of
the refrigerant and oil mixture − check
the high and low pressures before un-
brazing.

CAUTION

This procedure should not be performed on sys-
tems which contain contaminants (Example: com-
pressor burn out).

IMPORTANT

If this unit is being matched with an approved line
set or indoor coil which was previously charged
with mineral oil, or if it is being matched with a coil
which was manufactured before January of 1999,
the coil and line set must be flushed prior to instal-
lation. Take care to empty all existing traps. Polyol
ester (POE) oils are used in Lennox units charged
with R−410A refrigerant. Residual mineral oil can
act as an insulator, preventing proper heat trans-
fer. It can also clog the expansion device, and re-
duce the system performance and capacity.
Failure to properly flush the system per the in-
structions below will void the warranty.

Required Equipment

Equipment required  to flush the existing line set and indoor
coil:

S

two clean R−22 recovery bottles,

S

oil−less recovery machine with pump-down feature,

S

2 gauge sets (one for R−22; one for R−410A).

Flushing Procedure

IMPORTANT

The Environmental Protection Agency (EPA) pro-
hibits the intentional venting of HFC refrigerants
during maintenance, service, repair  and disposal of
appliance. Approved methods of recovery, recycl-
ing or reclaiming must be followed.

1. Remove existing R−22 refrigerant using the  following,

appropriate procedure (see figure 13):

If the existing outdoor unit is not equipped with
shut−off valves, or if the unit is not operational
AND you plan to use the existing R−22 refrigerant
to flush the system −

D

Disconnect all power to the existing outdoor unit.

D

Connect to the existing unit, a 

clean

 recovery cyl-

inder and the recovery machine according to the
instructions provided with the recovery machine.

D

Remove all R−22 refrigerant from the existing sys-
tem. Check gauges after shutdown to confirm that
the entire system is completely void of refrigerant.

D

Disconnect the liquid and vapor lines from the ex-
isting outdoor unit.

If the existing outdoor unit is equipped with
manual shut−off valves AND you plan to use NEW
R−22 refrigerant to flush the system 

D

Start the existing R−22 system in the cooling mode
and close the liquid line valve.

D

Pump all of the existing R−22 refrigerant back into
the outdoor unit. (It may be necessary to bypass
the low pressure switches to ensure complete re-
frigerant evacuation.)

D

When the low side system pressures reach 0 psig,
close the vapor line valve.

D

Disconnect all power to the existing outdoor unit.
Check gauges after shutdown to confirm that the
valves are not allowing refrigerant to flow back into
the low side of the system.

D

Disconnect the liquid and vapor lines from the ex-
isting outdoor unit.

2. Remove the existing outdoor unit. Set the new R−410A

unit and follow the brazing connection procedure (see
page 7) to make line set connections.

Summary of Contents for XC15-024

Page 1: ...low voltage wiring 2 Grommets for liquid and vapor lines Check equipment for shipping damage If you find any damage immediately contact the last carrier INSTALLATION INSTRUCTIONS XC15 Series Units CON...

Page 2: ...UND REDUCTION COVER SEE PAGE 20 FOR COVER INFORMATION COMPRESSOR TERMINAL PLUG HIGH PRESSURE SWITCH Figure 1 37 940 024 thru 042 47 1194 048 and 060 21 1 8 537 024 thru 042 31 1 8 791 048 and 060 10 3...

Page 3: ...NG This product and or the indoor unit it is matched with may contain fiberglass wool Disturbing the insulation during installation main tenance or repair will expose you to fiberglass wool dust Breat...

Page 4: ...uide the LIP of top tab inward fig ure 5 Details A and C then upward into the top slot of the hinge corner post S Rotate panel to vertical to fully engage all tabs S Holding the panel s hinged side fi...

Page 5: ...for field wiring diagram A complete unit wiring dia gram is located on the back side of the access panel NOTE For proper voltages select thermostat wire gauge per the following chart Wire run length A...

Page 6: ...Refrigerant Line If refrigerant lines are routed through a wall seal and iso late the opening so vibration is not transmitted to the build ing Pay close attention to line set isolation during installa...

Page 7: ...for use with R 410A refriger ant While brazing in the line set connections wrap a wet cloth around the valve body and the copper tube stubs 4 Quench the joints with a wet cloth to prevent possible he...

Page 8: ...LIQUID LINE Refrigerant Line Sets Installing Vertical Runs new construction shown NOTE Similar installation practices should be used if line set is to be installed on exterior of outside wall PVC PIPE...

Page 9: ...maintenance service repair and disposal of appliance Approved methods of recovery recycl ing or reclaiming must be followed 1 Remove existing R 22 refrigerant using the following appropriate procedure...

Page 10: ...liquid refrigerant to flow into the system through the vapor line valve Allow the refrigerant to pass from the cylinder and through the line set and the indoor coil before it enters the recovery machi...

Page 11: ...Schrader valve from contamination and serves as the primary leak seal To Access Schrader Port 1 Remove service port cap with an adjustable wrench 2 Connect gauge to the service port 3 When testing is...

Page 12: ...the manifold gauge set Open the valve on the R 410A cylinder va por only 3 Open the high pressure side of the manifold to allow R 410A into the line set and indoor unit Weigh in a trace amount of R 4...

Page 13: ...frozen bearings or binding 2 Inspect all factory and field installed wiring for loose connections 3 After evacuation is complete open the liquid line and vapor line service valves to release the refri...

Page 14: ...arge If weighing facili ties are not available or if charging the unit during warm weather use one of the following procedures Charge Using the Approach Method Outdoor Temp 65 F 18 C The following pro...

Page 15: ...results use the same electronic thermometer to check both outdoor ambient and liquid line temperatures F 1 0 C 0 5 1 With the manifold gauge hose still on the liquid service port and the unit operatin...

Page 16: ...0 psi Filter Drier A drier is factory installed in each XC15 unit A replace ment drier is available from Lennox Refer to Lennox Re pair Part Program System Operation Monitor LSOM The diagnostic indica...

Page 17: ...not present R and C wires are reversed Thermostat demand signal Y1 is present but compres sor not running 1 Compressor protector is open 2 Outdoor unit power disconnect is open 3 Compressor circuit br...

Page 18: ...is connect switch es Unit may have multiple power supplies Maintenance and service must be performed by a qualified installer or service agency At the beginning of each cool ing season check the syste...

Page 19: ...m call your Lennox dealer for assistance IMPORTANT Turn off electrical power to the unit at the disconnect switch before performing any maintenance The unit may have multiple power supplies 3 Reusable...

Page 20: ...tch from heating mode to cooling mode to maintain predetermined comfort settings Temperature Indicator The temperature indicator displays the actual room temperature Programmable Thermostats Your Lenn...

Reviews: