Page 34
TABLE 24
G60UHV−60D−135 BLOWER MOTOR PERFORMANCE
0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range
Factory Settings: Heating Speed − 2; Cooling Speed − 4; Speed Adjust − NORM.
Return Air Options: Bottom; both sides; or bottom and one side.
Speed Switch Positions
ADJUST"
Switch
Second Stage HEAT" Speed
Second Stage COOL" Speed
Switch
Positions
1
2
3
4
1
2
3
4
Positions
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
+
1470
695
1665
785
1855
875
2050
970
1575
745
1695
800
1900
900
2140 1010
NORM
1335
630
1520
715
1695
800
1870
885
1430
675
1540
725
1745
825
1945
920
N/A
N/A
1340
630
1510
710
1675
790
1275
600
1370
645
1565
740
1735
820
ADJUST"
First Stage HEAT" Speed
First Stage COOL" Speed
ADJUST"
Switch
P
iti
1
2
3
4
1
2
3
4
S
tc
Positions
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
+
1345
635
1520
715
1710
805
1880
890
1100
520
1180
560
1330
625
1495
705
NORM
1220
575
1375
650
1545
730
1725
815
1000
475
1075
510
1205
570
1350
635
N/A
N/A
1230
580
1380
650
1535
725
900
425
670
455
1095
515
1210
570
N/A − First and second stage HEAT positions shown cannot be used on this model.
NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately
91%
of the same second stage HEAT speed position.
First stage COOL (two−stage air conditioning units only) is approximately
70%
of the same second stage COOL speed position.
Continuous Fan Only speed is approximately
38%
of the same second stage COOL speed position − minimum 500 cfm (235 L/s).
Lennox Harmony III
t
Zone Control Applications − Minimum blower speed is 495 cfm (235 L/s).
TABLE 25
G60UHV−60D−135 BLOWER MOTOR PERFORMANCE
0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range
Factory Settings: Heating Speed − 2; Cooling Speed − 4; Speed Adjust − NORM.
Return Air Options: Single side return air − Bold volumes require field−fabricated transition to accommodate
20 x 25 x 1 in. (508 x 635 x 25 mm) cleanable air filter in order to maintain proper air velocity across the filter.
Speed Switch Positions
ADJUST"
Switch
Second Stage HEAT" Speed
Second Stage COOL" Speed
Switch
Positions
1
2
3
4
1
2
3
4
Positions
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
+
1405
665
1600
755
1775
840
1965
925
1500
705
1620
765
1815
860
2040
965
NORM
N/A
N/A
1440
680
1635
770
1800
850
1360
645
1470
695
1660
785
1860
875
N/A
N/A
N/A
N/A
1445
685
1620
765
1225
580
1310
620
1490
705
1670
785
ADJUST"
First Stage HEAT" Speed
First Stage COOL" Speed
ADJUST"
Switch
P
iti
1
2
3
4
1
2
3
4
S
tc
Positions
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
+
1285
605
1450
685
1635
770
1800
850
1075
505
1150
545
1275
605
1425
675
NORM
N/A
N/A
1325
625
1485
700
1660
785
955
450
1040
490
1165
550
1300
615
N/A
N/A
N/A
N/A
1325
625
1460
690
870
410
930
440
1065
500
1175
555
N/A − First and second stage HEAT positions shown cannot be used on this model.
NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately
91%
of the same second stage HEAT speed position.
First stage COOL (two−stage air conditioning units only) is approximately
70%
of the same second stage COOL speed position.
Continuous Fan Only speed is approximately
38%
of the same second stage COOL speed position − minimum 500 cfm (235 L/s).
Lennox Harmony III
t
Zone Control Applications − Minimum blower speed is 495 cfm (235 L/s).