background image

Page 10

Equipment In Confined Space − All Air From

Outside (Inlet Air from Crawl Space and

Outlet Air to Ventilated Attic)

NOTE−THE INLET AND OUTLET AIR OPENINGS SHALL EACH HAVE A FREE
AREA OF AT LEAST ONE SQUARE INCH (6.4 SQUARE CENTIMETERS) PER 4,000
BTU (1172 W) PER HOUR OF THE TOTAL INPUT RATING OF ALL EQUIPMENT IN
THE ENCLOSURE.

VENTILATION LOUVERS
(EACH END OF ATTIC)

OUTLET
AIR

WATER
HEATER

INLET
AIR

CHIMNEY

OR OIL

VENT

VENTILATION

LOUVERS

(FOR UNHEATED

CRAWL SPACE)

Figure 11

OIL

FURNACE

OIL

FURNACE

Equipment In Confined Space − All Air From

Outside (via Ventilated Attic)

NOTE−The inlet and outlet air openings shall each have a free area of
at least one square inch (6.4 square centimeters) per 4,000 Btu (1172
W) per hour of the total input rating of all equipment in the enclosure.

CHIMNEY

OR OIL

VENT

WATER

HEATER

OUTLET

AIR

VENTILATION LOUVERS

(Each end of attic)

INLET AIR

(Ends 12" above

bottom)

Figure 12

OIL

FURNACE

When ducts are used, they shall be of the same cross−sec-
tional area as the free area of the openings to which they
connect. The minimum dimension of rectangular air ducts
shall be no less than 3" (76 mm). In calculating free area,
the blocking effect of louvers, grilles, or screens must be
considered. If the design and free area of protective cover-
ing is not known for calculating the size opening required, it
may be assumed that wood louvers will have 20 to 25 per-
cent free area and metal louvers and grilles will have 60 to
75 percent free area. Louvers and grilles must be fixed in
the open position or interlocked with the equipment so that
they are opened automatically during equipment opera-
tion.

Equipment In Confined Space − All Air From

Outside

OUTLET AIR

INLET AIR

Figure 13

NOTE−EACH AIR DUCT OPENING SHALL HAVE A FREE AREA OF AT LEAST ONE
SQUARE INCH (6.4 SQUARE CENTIMETERS) PER 2,000 BTU (586 W) PER HOUR
OF THE TOTAL INPUT RATING OF ALL EQUIPMENT IN THE ENCLOSURE. IF THE
EQUIPMENT ROOM IS LOCATED AGAINST AN OUTSIDE WALL AND THE AIR
OPENINGS COMMUNICATE DIRECTLY WITH THE OUTDOORS, EACH OPENING
SHALL HAVE A FREE AREA OF AT LEAST ONE SQUARE INCH (6.4 SQUARE
CENTIMETERS) PER 4,000 BTU (1172 W) PER HOUR OF THE TOTAL INPUT RAT-
ING OF ALL OTHER EQUIPMENT IN THE ENCLOSURE.

WATER
HEATER

WATER

HEATER

CHIMNEY

OR OIL

VENT

CAUTION

The barometric control shall be in the same atmo-
spheric pressure zone as the combustion air inlet to
the furnace. Deviation from this practice will cause
improper burner operation and may result in a fire
hazard or injury.

Direct Connection of Outdoor Air for Combus-
tion

The Beckett AFII burner was designed to allow for direct air
intake piping (4" [102 mm]). The maximum equivalent
length of pipe is 70 feet (21.3 m). A 90

 elbow equals 6feet

(1.8 m). The enclosed intake pipe ring may be used to facil-
itate direct air intake to the burner through the right side of
the cabinet. The AFG burner requires a special kit for direct
air intake. Refer to kit instructions.

To convert the AFII burner from confined space to outside
combustion air, simply remove the three screws attaching
the inlet air scoop to the burner and insert 4" (102 mm) di-
rect air intake piping.

The use of a barometric relief placed in the intake pipe is
recommended when outdoor combustion air is directly
connected to the burner. This will allow confined space air
to be used as combustion air in the event that the opening
to the outdoor air becomes blocked. Using a barometric re-
lief in the intake will reduce the chance of sooting.

CAUTION

DO NOT USE a barometric draft relief in exhaust vent
pipe if outdoor combustion air is connected directly
to the burner.

Summary of Contents for OHR23-105

Page 1: ...nes Sizing 12 Oil Supply Line Filter Connections 13 Leak Check 13 Electrical Wiring 14 Unit Start Up Adjustments 15 Service 16 Start Up Performance Checklist 17 Troubleshooting 18 RETAIN THESE INSTRUC...

Page 2: ...VIEW SIDE VIEW FRONT VIEW FLUE OUTLET 8 203 SUPPLY AIR OPENING HORIZONTAL POSITION DOWNFLOW POSITION OPTIONAL DOWNFLOW COMBUSTIBLE FLOOR BASE OPTIONAL DOWNFLOW ADDITIVE BASE Additive Base Raises Furn...

Page 3: ...RETAINING 1 4 HEX HEAD SCREW FB HEADS ASSY FOR AIR TUBE ASSY ELECTRODE HEAD NOZZLE LINE PEDESTAL ADAPTER NOZZLE AIR SCOOP INLET WHEEL BLOWER FLANGE GASKET MOTOR 4X4 BOX IGNITOR DOOR GASKET REAR ACCESS...

Page 4: ...combustible materi al as listed unit rating plate and in tables 2 or 3 Unit service and accessibility clearances take precedence over fire protection clearances Table 2 Horizontal Installation Clearan...

Page 5: ...tible materi al A minimum clearance of 1 must be maintained be tween bottom of furnace and combustible material Suspended Installation To suspend furnace remove knockouts in top of panel at warm air d...

Page 6: ...ometer Oil vacuum gauge Beckett T 500 gauge Knowledge of proper test equipment operation CAUTION Improper nozzle and or air adjustment of this unit may result in sooting problems Refer to the follow i...

Page 7: ...he chimney to determine whether repairs are necessary Make sure the chimney is properly constructed and sized according to the requirements of the National Fire Protec tion Association The smallest di...

Page 8: ...ey BAROMETRIC CONTROL IN EITHER LOCATION DRAIN FOR CONDENSATE FACTORY BUILT CHIMNEY Figure 9 BAROMETRIC CONTROL MAY BE INSTALLED IN EITHER VERTICAL OR HORI ZONTAL SECTION OF FLUE PIPE WITHIN 18 OF FLU...

Page 9: ...ted on a plat form in a confined space such as a closet or small equipment room Small leaks around the base of the unit at the platform or at the return air duct connection can cause a potentially dan...

Page 10: ...AIR Figure 13 NOTE EACH AIR DUCT OPENING SHALL HAVE A FREE AREA OF AT LEAST ONE SQUARE INCH 6 4 SQUARE CENTIMETERS PER 2 000 BTU 586 W PER HOUR OF THE TOTAL INPUT RATING OF ALL EQUIPMENT IN THE ENCLOS...

Page 11: ...efer to the manufacturers installation instruc tions for proper installation procedures and service parts information Do not use the same vent with any other appliance when using a sidewall vent syste...

Page 12: ...d a vacuum of 6 152 mm Hg or less a single stage fuel pump with a supply line and no return line should be adequate See figure 16 Manual bleeding of the fuel pump is required on initial start up Failu...

Page 13: ...erly 5 Tighten the bleed valve securely Two Pipe Systems If the installation requires a two pipe operation install the bypass plug included in the bag which is attached to the pump To convert the pump...

Page 14: ...r on thermostat ac cording to the wiring diagram sticker provided on unit 3 Install a separate fused disconnect switch near unit so power can be shut off for servicing 4 Complete line voltage wiring f...

Page 15: ...reached their highest and steadiest readings subtract the readings The difference in temper atures in the supply and return air plenums should approxi mate the temperature rise range listed in table 7...

Page 16: ...ice Servicing Filter NOTE Under no circumstances should the access panels to the blower compartment be left off or left partially open 1 Throw Away Type Filters Filters should be checked monthly and r...

Page 17: ...Burner Model No Serial Number Piping Connections Tight All Valves Open Blower Motor Lubrication OK Oil Pump Pressure recommended minimum 140 psi PROPER DRAFT Draft Reading recommended 03 to 04 inches...

Page 18: ...rner motor is de energized If heat fan has started it continues through the selected delay off period Established flame fails Burner motor is de energized and oil primary control goes into recycle mod...

Page 19: ...auxiliary limit Power Check furnace disconnect switch main disconnect Open switch Close switch switch main disconnect Blown fuse or tripped circuit breaker Replace fuse or reset circuit breaker Therm...

Page 20: ...e closed Open valve Oil Filters Oil Line Listen for pump whine Oil line filter is plugged Replace filter cartridges Oil Line Kinks or restriction in oil line Repair or replace oil line Plugged fuel pu...

Page 21: ...Cracked or burned lead insulators Replace electrode leads Ignition Transformer Connect ignition leads to the transformer Start burner and observe spark Check line voltage to transformer primary Low li...

Page 22: ...Safety Source Procedure Check Causes Correction Poor Fire If burner continues to r n does not Unbalanced fire Replace nozzle to run does not lock out of safety fault may be due to Too much air lean s...

Page 23: ...filters Clean or replace filter between line voltage connections to Burner running too slow Increase blower speed to maintain proper temp rise connections to primary control bl k hit Blower motor seiz...

Page 24: ...aks into heat exchanger around inspection door etc Correct cause of air leak CO2 if less than 10 Excessive draft Adjust barometric draft control for correct draft Incorrect burner head adjustment Corr...

Reviews: