background image

25

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

LENNOX HEARTH PRODUCTS  •  MERIT PLUS

®

 DIRECT VENT GAS FIREPLACES (MPD33/35/40/45)  •  INSTALLATION INSTRUCTIONS

NOTE: 

Remote receiver should be located in the 

wall, or if installed in the control compartment, 

pulled all the way forward and completely to the 

left or right against the corner posts. 

6.

 If wall-mounted ON/OFF control or 

thermostat is to be used, mount it in a 

convenient location on a wall near the 

fireplace.

7

.  If an optional control is to be used, wire it in 

the low voltage circuit as shown in 

Figure 

45.

NOTE: 

The supplied 15 feet of 2 conductor wire 

has one end of each conductor connected to 

the gas valve circuit and the other end of each 

conductor placed loose inside the bottom 

compartment.

8

. After the wiring is complete, replace the 

cover plate.

BLOWER CONTROL CIRCUIT WIRING

120V, 60HZ, 1PH  

Factory Wired

Ground

Field Wired

Junction Box 

Tab Intact

Tab 

Broken

Plug blower

into this 

receptacle

ne

er

G - 

dn

uor

G

* Wall-mounted

ON/ OFF Blower 

Switch or Variable 

Speed Control Switch. 

Blower

eti

h

W - 

lar

tu

eN 120 VAC - Blac

k

Green

Ground

Screw

Whit

e

Gree

n

Neutral 

Side of

Receptacle

Hot

Side of

Receptacle

Red

Black

Figure 46 - Junction Box Wiring

These appliances are equipped with a gas flex 

line for use (where permitted) in connecting the 

unit to the gas line. A gas flex line is provided to 

aid in attaching the direct vent appliance to the 

gas supply. The gas flex line can only be used 

where local codes permit. Refer to 

Figure 47

 

for flex line description. The flex line is rated 

for both natural and propane gas. A manual 

shut off valve is also provided with the flex line.

The gas control valve is located in the lower 

control compartment. 

To access the valve open the lower control 

compartment door (

see Figure 48

 

) by pushing 

in the right top corner of the door. (The door 

is hinged at the bottom.) Remove the bottom 

compartment door by sliding the hinge pin, 

located at the door’s left side, to the right until 

it disengages from the left corner post hole. 

Pull the door diagonally to the left, away from 

the fireplace.

The millivolt control valve has a 3/8" (10 mm) 

NPT thread inlet port. The electronic control 

valve has a 1/2" (13 mm) NPT thread inlet 

port and is fitted with a 1/2" x 3/8" (13 mm x 

10 mm) NPT fitting.

Secure all joints tightly using appropriate 

tools and sealing compounds (ensure propane 

resistant compounds are used in propane 

applications). Optional: Seal around the gas 

line to prevent cold air leakage. Gas line holes 

and other openings can be caulked or stuffed 

with unfaced fiberglass insulation.

All codes require a shut-off valve mounted 

in the supply line. The orientation of the 

shut-off valve should face the front. 

Figure 

47 

illustrates two methods for connecting the 

gas supply. A sediment Trap is recommended 

to prevent moisture and debris in the gas line 

for damaging the valve.

       WARNING 

Electronic models of these appli-

ances are equipped with a three-

prong (grounding) plug utilized 

in connecting the electronic 

components to the junction box 

in the lower compartment. This 

grounding plug provides protec-

tion against shock hazard and 

should be plugged directly into 

the properly grounded three-

prong receptacle. dO NOT cut 

or remove the grounding prong 

from the plug.

FBK-250 Blower Kit 

(See Figure 46)

An electrical outlet box is provided for the 

installation of the 

FBK-250

 forced air blower 

kit. Electrical power must be provided to this 

box to operate these blowers. Install the blower 

kit according to the installation instructions 

provided with the kit.

NOTE: 

The tab connecting the receptacles of 

the outlet box must be broken in FBK-100 and 

FBK-200 blower kit applications. See 

Figure 46

.

Step 7. CONNECTING GAS LINE 

Make gas line connections. All codes require a 

shut-off valve mounted in the supply line. 

Figure 

47 

illustrates two methods for connecting the 

gas supply. The flex-line method is acceptable 

in the U.S., however, Canadian requirements 

vary depending on locality. Installation must 

be in compliance with local codes. 

Step 6.

 

WIRING - OPTIONAL FORCEd AIR 

BLOWER KIT 

FBK-100 and FBK-200 Kits 

(See Figure 46)

An electrical outlet box is provided for the 

installation of the 

FBK-100

FBK-200

 forced air 

blower kits. Electrical power must be provided 

to this box to operate these blowers. Install 

the blower kits according to the installation 

instructions provided with the kits.

Summary of Contents for MPD35CNE

Page 1: ...fire or explosion may result causing property damage personal injury or death WARNING AVERTISSEMENT AVISO HOT GLASS WILL CAUSE BURNS DO NOT TOUCH GLASS UNTIL COOLED NEVER ALLOW CHILDREN TO TOUCH GLAS...

Page 2: ...cal Installation Sequence 9 Detailed Installation Steps 9 Step 1 Framing 9 Fireplace and Framing Specifications 10 Step 2 Routing Gas Line 11 Step 3 Preparing Appliance Vent Collar 12 Step 4 Installin...

Page 3: ...is appliance can cause serious injury or death from fire burns explosion or carbon monoxide poisoning WARNING Failure to position the parts in accordance with these diagrams or failure to use only par...

Page 4: ...55 0 052 19L52 MPD40 38 0 102 99K76 0 062 21L01 MPD45 37 0 104 24M10 52 0 0635 37G00 Table 4 Standard size installed at factory Part Cat Number REQUIREMENTS FOR THE COMMONWEALTHOFMASSACHUSETTS These f...

Page 5: ...the appliance Cold Climate Insulation For cold climate installations seal all cracks around your appliance with noncombustible material and wherever cold air could enter the room It is especially imp...

Page 6: ...ents Above Flat Or Sloped Roofs Ref NFPA 54 ANSI Z223 1 Roof Pitch H ft H m Flat 6 12 1 0 0 3 6 12 7 12 1 25 0 38 7 12 8 12 1 5 0 46 8 12 9 12 2 0 0 61 9 12 10 12 2 5 0 76 10 12 11 12 3 25 0 99 11 12...

Page 7: ...er 5 12 7 cm 5 12 7 cm G Clearance to inside corner 2 5 08cm minimum SV4 5HT 2 6 15 2cm minimum SV4 5HTSS 2 5 08cm minimum SV4 5HT 2 6 15 2cm minimum SV4 5HTSS H Clearancetoeachinsideofcenterlineexten...

Page 8: ...ve to conform to standard hearth extension installation requirements Shelf Height To provide for the lowest possible shelf surface use the alternate rear vent outlet the venting attached to the top ve...

Page 9: ...the framing and secure with nailing brackets IMPORTANT Bend up the appropriate header spacing standoffs for the drywall finish material thickness to be used see Figure 11 Bend up the outer pair for 1...

Page 10: ...lectrical Inlet Knockout requiring a Field Provided Junction Box either side E B D C Front View 3 76 A Header Spacing Top Standoffs Vertical Venting through the Ceiling Frame ceiling opening Use a plu...

Page 11: ...aming 6 1 2 152 mm Pipe Coupling Recommended NOTE Rear Vent Applications in Corner Installations The horizontal vent length from a to b must not exceed 28 inches 711 mm MPDT33 and MPDR33 Models Dimens...

Page 12: ...ct Venting System Horizontal or Vertical Withtheappliancesecuredinframing determine ventroutingandidentifytheexteriortermination location The following sections describe vertical roof and horizontal e...

Page 13: ...4 1 1 0 0 5 0 6 3 8 1 5 2 5 1 0 1 0 5 0 6 6 8 1 5 5 1 0 0 0 0 4 4 5 0 9 1 5 7 8 5 1 1 0 0 0 4 5 5 6 9 1 5 7 3 6 1 0 1 0 0 4 5 5 5 0 2 5 2 1 7 1 0 1 1 5 0 7 7 0 2 5 2 7 1 0 0 0 6 0 6 5 1 1 2 5 2 6 7 1...

Page 14: ...e radial alignment until the four locking dimples are aligned with the inlet of the four inclined channels on the collar refer to Figure 21 Push the vent component againstthecollaruntilitfullyengages...

Page 15: ...llar section to align with the required direction of the next vent run element Twist elbow sections in a clockwise direction only so as to avoid the possiblity of unlocking anyofthepreviouslyconnected...

Page 16: ...ou are allowed 2 feet of H horizontal run up to a maximum horizontal run of 8 feet Example If 8 feet of H horizontal vent run is needed then 4 feet minimum V vertical vent will be required TABLE A H M...

Page 17: ...6 096 4 1 219 H H1 20 feet 6 096 m Max V V1 H H1 40 ft 12 192 m Max meters meters Example If 20 feet of H horizontal vent run is needed then 4 feet minimum of V vertical vent will be required This tab...

Page 18: ...al both the inner and outer pipe elements with the same procedure Sealant and securing screws are not required NOTE An elbow may also be attached to the appliance collar Attach in the same manner as y...

Page 19: ...4 32 mm as shown in Figure 34 SVHRK Snorkel Cap The snorkel cap is designed to be fitted into a basement window box The SVHRK cap is for use with flex vent The vertical distance between the inlet and...

Page 20: ...owingwallthicknessrange when using SV4 5HT 2 termination kit HORIZONTAL Vent Figures Tables NOTE Secure Vent components rigid vent pipe and terminal are shown in the figures Secure Flex components fle...

Page 21: ...of H horizontal vent run is needed then 4 feet minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio For every 1 foot of V vertical you are allowed 5 feet of H horizontal run...

Page 22: ...al rise except where an elbow is the only vertical component in the system See Figure 36 V Minimum feet feet 5 1 524 Elbow Only 5 1 524 1 0 305 10 3 048 2 0 610 15 4 572 3 0 914 20 6 096 4 1 219 meter...

Page 23: ...No 10K81 to the inner adaptor collar approximately 1 2 inch from the end 3 Pull and extend the inner flexible vent pipe 4 Slide the inner flex pipe over the adaptor collar Ensure the flexible vent pip...

Page 24: ...t of 2 conductor wire supplied with the unit NOTE The supplied 15 feet of 2 conductor wire has one end of each conductor connected to the gas valve circuit and the other end of each conductor placed l...

Page 25: ...eplace The millivolt control valve has a 3 8 10mm NPT thread inlet port The electronic control valve has a 1 2 13 mm NPT thread inlet port and is fitted with a 1 2 x 3 8 13 mm x 10 mm NPT fitting Secu...

Page 26: ...onovertime A Light the appliance refer to the lighting instructionslabelinthecontrolcompartment or in the Care and Operation Instructions manual B Brush all joints and connections with the gas leak te...

Page 27: ...pli ances to Figure 54 for MPD35 Series appli ancesandtoFigure55forMPD40andMPD45 Series appliances WARNING DO NOT attempt to install the logs until the appliance instal lationhasbeencompleted the gas...

Page 28: ...firebox with the log s notches directly over the brackets Position the right log log no 3 by inserting the pin from the rear log into the hole on its upper end Place the left log and then the smaller...

Page 29: ...the order shown Position the rear log on the brackets at the rear of the firebox with the log s notches directly over the brackets Position the right log log no 3 by inserting the pin from the rear l...

Page 30: ...ividual logs as shown below Logs should be placed in the order shown Position the center log on the burner first then place the glowing embers as shown in Figure 52 Place the rear log both the right a...

Page 31: ...t appear sooty The following chart is provided to aid you in achieving the correct air shutter adjustment for your installation Figure 56 Removing the Glass Enclosure Panel see Figure 56 Remove the to...

Page 32: ...ireplace rod located in the lower control area Position the air shutter to the factory setting as shown in the table in Figure 60 2 Light appliance follow lighting procedure on lighting label in contr...

Page 33: ...bustible material may touch top of appliance Combustible materials NOT allowed below this point on face of appliance Header Spacing Top Standoff Top of Appliance Top of Door Frame Hood must be install...

Page 34: ...er la poussi re et les traces de graisse ou d huile Collez l tiquette sur la surface de la plaque de l interrupteur mural qui contr le le foyer Figure A ou du thermostat mural Figure B Choisissez la l...

Page 35: ...6 SV4 5HF 10 Firestop Spacer Hori zontal rigid 3 1 1 spac ing 10 Pack H2247 SV4 5VF 10 Firestop Spacer Verti cal rigid 1 1 1 spac ing 10 Pack 96K92 SV4 5SP Support Plate Installation Accessories Liste...