background image

3

LENNOX HEARTH PRODUCTS  •  MERIT PLUS

®

 DIRECT VENT GAS FIREPLACES (MPD33/35/40/45)  •  INSTALLATION INSTRUCTIONS

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

       WARNING 

Failure to comply with these 

installation instructions will 

result in an improperly installed 

and operating appliance, voiding 

its warranty. Any change to this 

appliance and/or its operating 

controls is dangerous.

       WARNING 

Clothing or other flammable 

material should not be placed 

on or near the appliance.

       AVERTISSEMENT 

On ne devrait pas placer de 

vêtements ni d’autres matières 

inflammables sur l’appareil ni à 

proximité.

NOTE: Installation and repair should be done 

by a qualified service person. The appliance 

should be inspected before use and at least 

annually by a professional service person. 

More frequent cleaning may be required due 

to excessive lint from carpeting, bedding 

material, etcetera. It is imperative that control 

compartments, burners and circulating air 

passageways of the appliance be kept clean.

Remarque: L’installation et la réparation 

devrait être confiées à un technicien 

qualifié. L’appareil devrait faire l’objet 

d’une inspection par un technicien 

professionnel avant d’être utilisé et au 

moins une fois l’an par la suite. des 

nettoyages plus fréquents peuvent être 

nécessaires si les tapis, la literie, et 

cetera produisent une quantité importante 

de pous-sière. Il est essentiel que les 

compartiments abritant les commandes, 

les brûleurs et les conduits de circulation 

d’air de l’appareil soient tenus propres.

do not use this appliance if any part has 

been under water.  Immediately call a 

qualified service technician to inspect the 

appliance and to replace any parts of the 

control system and any gas control which 

has been under water.

Ne pas utiliser cet appareil s’il a été 

plongé, même partiellement, dans 

l’eau. Appeler un technicien qualifié 

pour inspecter l’appareil et remplacer 

toute partie du système de commande 

et toute commande qui a été plongée 

dans l’eau.

Only trim kit(s) supplied by the manufacturer 

shall be used in the installation of this 

appliance.

Seules les trousses de garniture fournies 

par le fabricant doivent être utilisées pour 

l’installation de cet appareil.

Models

Input Rate (BTU/HR)

Nat. Gas

Prop. Gas

MPd33

17,500 high

11,700 low

17,500 high

14,000 low

MPd35

20,000 high

12,800 low

20,000 high

15,200 low

MPd40

27,000 high

18,500 low

27,000 high

21,500 low

MPd45

29,000 high

20,500 low

29,000 high

22,500 low

Table 1 - Input (BTU/HR) Gas Valves  

(Millivolt and Electronic)

       WARNING 

Improper installation or use of 

this appliance can cause serious 

injury or death from fire, burns, 

explosion or carbon monoxide 

poisoning.

       WARNING 

Failure to position the parts in 

accordance with these diagrams 

or failure to use only parts 

specifically approved with this 

appliance may result in property 

damage or personal injury.

       AVERTISSEMENT 

Risque de dommages ou de 

blessures si les pièces ne sont 

pas installées conformément à 

ces schémas et ou si des pièces 

autres que celles spécifiquement 

approuvées avec cet appareil sont 

utilisées.

These appliances comply with National Safety 

Standards and are tested and listed by OMNI-

Test Laboratories, Inc. (Report No. 116-F-13g-5) 

to ANSI Z21.88-2009 (in Canada, CSA-2.33-

2009), and CAN/CGA-2.17-M91(R2009) in both 

USA and Canada, as vented gas fireplace heaters.

Both millivolt and electronic versions of 

these appliances are listed by OMNI-Test 

Laboratories for installation in bedrooms 

and Manufactured Homes. 
Misc. Codes / Standards 

The Installation must conform to local codes 

or, in the absence of local codes, with the 

National Fuel Gas Code, ANSI Z223.1 / NFPA 

54 - latest edition

 (In Canada, the current CAN/

CGA-B149.1 installation code).The appliance, 

when installed, must be electrically grounded 

and wired in accordance with local codes or, in 

the absence of local codes, with the 

National 

Electrical Code, ANSI/NFPA 70 - latest edition

or the 

Canadian Electrical Code, CSA C22.1 - 

latest edition

.

Provide adequate clearances around air 

openings and adequate accessibility clearance 

for service and proper operation. Never obstruct 

the front or back openings of the appliance.

These appliances are designed to operate on 

natural or propane gas only. The use of other 

fuels or combination of fuels will degrade 

the performance of this system and may be 

dangerous.

These fireplaces are designed as supplemental 

heaters. Therefore, it is advisable to have an 

alternate primary heat source when installed 

in a dwelling.

These appliances must not be connected to a 

chimney or flue serving a separate solid fuel 

burning appliance.

Both millivolt and electronic systems can be 

operated during a power outage, and feature 

manually operated hi-low flame control. The BTU 

Input for these appliances is shown in 

Table 1.

       WARNING 

Improper installation, adjust-

ment, alteration, service or 

maintenance can cause injury 

or property damage.  Refer to 

this manual.  For assistance or 

additional information consult 

a qualified installer, service 

agency or the gas supplier.

       AVERTISSEMENT 

Tout écran ou protecteur retiré 

pour permettre l’entretien de 

l’appareil doit être remis en 

place avant de mettre l’appareil 

en marche.

       WARNING 

Any safety screen or guard 

removed for servicing the appli-

ance must be replaced prior to 

operating the appliance.

Summary of Contents for MPD35CNE

Page 1: ...fire or explosion may result causing property damage personal injury or death WARNING AVERTISSEMENT AVISO HOT GLASS WILL CAUSE BURNS DO NOT TOUCH GLASS UNTIL COOLED NEVER ALLOW CHILDREN TO TOUCH GLAS...

Page 2: ...cal Installation Sequence 9 Detailed Installation Steps 9 Step 1 Framing 9 Fireplace and Framing Specifications 10 Step 2 Routing Gas Line 11 Step 3 Preparing Appliance Vent Collar 12 Step 4 Installin...

Page 3: ...is appliance can cause serious injury or death from fire burns explosion or carbon monoxide poisoning WARNING Failure to position the parts in accordance with these diagrams or failure to use only par...

Page 4: ...55 0 052 19L52 MPD40 38 0 102 99K76 0 062 21L01 MPD45 37 0 104 24M10 52 0 0635 37G00 Table 4 Standard size installed at factory Part Cat Number REQUIREMENTS FOR THE COMMONWEALTHOFMASSACHUSETTS These f...

Page 5: ...the appliance Cold Climate Insulation For cold climate installations seal all cracks around your appliance with noncombustible material and wherever cold air could enter the room It is especially imp...

Page 6: ...ents Above Flat Or Sloped Roofs Ref NFPA 54 ANSI Z223 1 Roof Pitch H ft H m Flat 6 12 1 0 0 3 6 12 7 12 1 25 0 38 7 12 8 12 1 5 0 46 8 12 9 12 2 0 0 61 9 12 10 12 2 5 0 76 10 12 11 12 3 25 0 99 11 12...

Page 7: ...er 5 12 7 cm 5 12 7 cm G Clearance to inside corner 2 5 08cm minimum SV4 5HT 2 6 15 2cm minimum SV4 5HTSS 2 5 08cm minimum SV4 5HT 2 6 15 2cm minimum SV4 5HTSS H Clearancetoeachinsideofcenterlineexten...

Page 8: ...ve to conform to standard hearth extension installation requirements Shelf Height To provide for the lowest possible shelf surface use the alternate rear vent outlet the venting attached to the top ve...

Page 9: ...the framing and secure with nailing brackets IMPORTANT Bend up the appropriate header spacing standoffs for the drywall finish material thickness to be used see Figure 11 Bend up the outer pair for 1...

Page 10: ...lectrical Inlet Knockout requiring a Field Provided Junction Box either side E B D C Front View 3 76 A Header Spacing Top Standoffs Vertical Venting through the Ceiling Frame ceiling opening Use a plu...

Page 11: ...aming 6 1 2 152 mm Pipe Coupling Recommended NOTE Rear Vent Applications in Corner Installations The horizontal vent length from a to b must not exceed 28 inches 711 mm MPDT33 and MPDR33 Models Dimens...

Page 12: ...ct Venting System Horizontal or Vertical Withtheappliancesecuredinframing determine ventroutingandidentifytheexteriortermination location The following sections describe vertical roof and horizontal e...

Page 13: ...4 1 1 0 0 5 0 6 3 8 1 5 2 5 1 0 1 0 5 0 6 6 8 1 5 5 1 0 0 0 0 4 4 5 0 9 1 5 7 8 5 1 1 0 0 0 4 5 5 6 9 1 5 7 3 6 1 0 1 0 0 4 5 5 5 0 2 5 2 1 7 1 0 1 1 5 0 7 7 0 2 5 2 7 1 0 0 0 6 0 6 5 1 1 2 5 2 6 7 1...

Page 14: ...e radial alignment until the four locking dimples are aligned with the inlet of the four inclined channels on the collar refer to Figure 21 Push the vent component againstthecollaruntilitfullyengages...

Page 15: ...llar section to align with the required direction of the next vent run element Twist elbow sections in a clockwise direction only so as to avoid the possiblity of unlocking anyofthepreviouslyconnected...

Page 16: ...ou are allowed 2 feet of H horizontal run up to a maximum horizontal run of 8 feet Example If 8 feet of H horizontal vent run is needed then 4 feet minimum V vertical vent will be required TABLE A H M...

Page 17: ...6 096 4 1 219 H H1 20 feet 6 096 m Max V V1 H H1 40 ft 12 192 m Max meters meters Example If 20 feet of H horizontal vent run is needed then 4 feet minimum of V vertical vent will be required This tab...

Page 18: ...al both the inner and outer pipe elements with the same procedure Sealant and securing screws are not required NOTE An elbow may also be attached to the appliance collar Attach in the same manner as y...

Page 19: ...4 32 mm as shown in Figure 34 SVHRK Snorkel Cap The snorkel cap is designed to be fitted into a basement window box The SVHRK cap is for use with flex vent The vertical distance between the inlet and...

Page 20: ...owingwallthicknessrange when using SV4 5HT 2 termination kit HORIZONTAL Vent Figures Tables NOTE Secure Vent components rigid vent pipe and terminal are shown in the figures Secure Flex components fle...

Page 21: ...of H horizontal vent run is needed then 4 feet minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio For every 1 foot of V vertical you are allowed 5 feet of H horizontal run...

Page 22: ...al rise except where an elbow is the only vertical component in the system See Figure 36 V Minimum feet feet 5 1 524 Elbow Only 5 1 524 1 0 305 10 3 048 2 0 610 15 4 572 3 0 914 20 6 096 4 1 219 meter...

Page 23: ...No 10K81 to the inner adaptor collar approximately 1 2 inch from the end 3 Pull and extend the inner flexible vent pipe 4 Slide the inner flex pipe over the adaptor collar Ensure the flexible vent pip...

Page 24: ...t of 2 conductor wire supplied with the unit NOTE The supplied 15 feet of 2 conductor wire has one end of each conductor connected to the gas valve circuit and the other end of each conductor placed l...

Page 25: ...eplace The millivolt control valve has a 3 8 10mm NPT thread inlet port The electronic control valve has a 1 2 13 mm NPT thread inlet port and is fitted with a 1 2 x 3 8 13 mm x 10 mm NPT fitting Secu...

Page 26: ...onovertime A Light the appliance refer to the lighting instructionslabelinthecontrolcompartment or in the Care and Operation Instructions manual B Brush all joints and connections with the gas leak te...

Page 27: ...pli ances to Figure 54 for MPD35 Series appli ancesandtoFigure55forMPD40andMPD45 Series appliances WARNING DO NOT attempt to install the logs until the appliance instal lationhasbeencompleted the gas...

Page 28: ...firebox with the log s notches directly over the brackets Position the right log log no 3 by inserting the pin from the rear log into the hole on its upper end Place the left log and then the smaller...

Page 29: ...the order shown Position the rear log on the brackets at the rear of the firebox with the log s notches directly over the brackets Position the right log log no 3 by inserting the pin from the rear l...

Page 30: ...ividual logs as shown below Logs should be placed in the order shown Position the center log on the burner first then place the glowing embers as shown in Figure 52 Place the rear log both the right a...

Page 31: ...t appear sooty The following chart is provided to aid you in achieving the correct air shutter adjustment for your installation Figure 56 Removing the Glass Enclosure Panel see Figure 56 Remove the to...

Page 32: ...ireplace rod located in the lower control area Position the air shutter to the factory setting as shown in the table in Figure 60 2 Light appliance follow lighting procedure on lighting label in contr...

Page 33: ...bustible material may touch top of appliance Combustible materials NOT allowed below this point on face of appliance Header Spacing Top Standoff Top of Appliance Top of Door Frame Hood must be install...

Page 34: ...er la poussi re et les traces de graisse ou d huile Collez l tiquette sur la surface de la plaque de l interrupteur mural qui contr le le foyer Figure A ou du thermostat mural Figure B Choisissez la l...

Page 35: ...6 SV4 5HF 10 Firestop Spacer Hori zontal rigid 3 1 1 spac ing 10 Pack H2247 SV4 5VF 10 Firestop Spacer Verti cal rigid 1 1 1 spac ing 10 Pack 96K92 SV4 5SP Support Plate Installation Accessories Liste...

Page 36: ...T48SS Small Square Termination for flex with 48 1219 mm of compressed flex vent Ref Instr 750204M 94L09 SF HTSS Horizontal Small Square Termination for flex without flex vent Ref Instr 750204M INSTALL...

Page 37: ...pin located at the door s left side to the right until it disengages from the left corner post hole Pull the control compartment door diagonally to the left away from the fireplace Step 3 Remove the...

Page 38: ...crews previously removed Step 12 Reinstall the baffle with the two baffle securing screws Step 13 Reassemble the remaining compo nents by reversing the procedures outlined in the Steps 1 5 Step 14 Att...

Reviews: