background image

4

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

LENNOX HEARTH PRODUCTS  •  MERIT PLUS

®

 DIRECT VENT GAS FIREPLACES (MPD33/35/40/45)  •  INSTALLATION INSTRUCTIONS

Test gauge connections are provided on the 

front of the millivolt and electronic gas control 

valve (identified IN for the inlet and OUT for 

the manifold side). The control valves have a 

3/8" (10 mm) NPT thread inlet and outlet side 

of the valve (refer to 

Figures 1 and 2

)

.

Propane tanks are at pressures that will cause 

damage to valve components. Verify that the 

tanks have step down regulators to reduce the 

pressure to safe levels.

Orifice Sizes - Sea Level to High Altitude 

(All Models)

These appliances are tested and approved for 

installation at elevations of 0-4500 ft (0-1372 

m) above sea level using the standard burner 

orifice sizes (marked with an "*" in 

Table 4

)

For elevations above 4500 ft, contact your gas 

supplier or qualified service technician. 

deration - 

At higher elevations, the amount 

of BTU fuel value delivered must be reduced 

by either:

•   Using gas that has been derated by the gas 

company.

•   Changing the burner orifice to a smaller size 

as regulated by the local authorities having 

jurisdiction and by the (USA) National Fuel 

Gas Code NFPA 54 - latest edition / ANSI 

Z223.1 or, in Canada, the CAN/CGA-B149.1 

codes - latest edition.

Install the appliance according to the regulations
of the local authorities having jurisdiction and,

Fuel #

Low

High

Natural 

Gas

1.6" WC

(0.40 kPa)

3.5" WC

(0.87 kPa)

Propane

6.3" WC

(1.57 kPa)

10.0" WC

(2.49 kPa)

Table 3: Manifold Gas Supply Pressure

The appliance and its appliance main gas 

valve must be disconnected from the gas 

supply piping system during any pressure 

testing of that system at test pressures 

in 

excess of

 1/2 psi (3.5 kPa).

The appliance must be isolated from the 

gas supply piping system by closing its 

equipment shutoff valve during any pressure 

testing of the gas supply piping system at 

test pressures 

equal to or less than

 1/2 psi 

(3.5 kPa).

Fuel #

Minimum

Maximum

Natural 

Gas

4.5" WC

(1.12 kPa)

10.5" WC

(2.61 kPa)

Propane

11.0" WC

(2.74 kPa)

13.0" WC

(3.23 kPa)

Table 2: Inlet Gas Supply Pressure 

Gas Pressure - All Models

Tables 2 and 3

 

show the appliances' inlet and 

manifold gas pressure requirements:

Burner Orifice Sizes 

Elevation 0-4500 feet ( 0-1372 meters)

Model

Series

Nat.Gas

drill size (inches)

Propane

drill size (inches)

MPd33

#47 (0.0785")* 

99K74 •

0.048"

99K78 •

MPd35

#44 (0.086")*

60J80 •

#55 (0.052")*

19L52 •

MPd40

#38 (0.102") *

99K76 •

0.062"

21L01 •

MPd45

#37 (0.104")*

24M10 •

#52 (0.0635")*

37G00 •

Table 4

* Standard size installed at factory

• Part /Cat. Number

REQUIREMENTS FOR THE 

COMMONWEALTH OF MASSACHUSETTS

These fireplaces are approved for installation in 

the US state of Massachusetts if the following 

additional requirements are met:

•  Install  this  appliance  in  accordance  with 

Massachusetts Rules and Regulations 248 

C.M.R. 

•  Installation  and  repair  must  be  done  by 

a plumber or gas fitter licensed in the 

Commonwealth of Massachusetts.

•  The flexible gas line connector used shall 

not exceed 36 (92 cm) in length.

•  The  individual  manual  shut-off  must  be  a 

T-handle type valve.

Massachusetts Horizontal Vent Requirements  

in the Commonwealth of Massachusetts, 

horizontal terminations installed less than 

seven (7) feet above the finished grade 

must comply with the following additional 

requirements:

•  A  hard  wired  carbon  monoxide  detector 

with an alarm and battery back-up must be 

installed on the floor level where the gas 

fireplace is installed. The carbon monoxide 

detector must comply with NFPA 720, be 

ANSI/UL 2034 listed and be ISA certified.

•  A metal or plastic identification plate must be 

permanently mounted to the exterior of the 

building at a minimum height of eight (8) feet 

above grade and be directly in line with the 

horizontal termination. The sign must read, 

in print size no less than one-half (1/2) inch 

in size, GAS VENT DIRECTLY BELOW. KEEP 

CLEAR OF ALL OBSTRUCTIONS.

in the USA, the National Fuel Gas Code NFPA 

54 - latest edition / ANSI Z223.1 or, in Canada, 

the CAN/CGA-B149.1

 - 

latest edition.

 

Flame breadth, height and width will diminish 

4% for every 1,000 feet of altitude. 

Gas Valve 

diagrams

See 

Figure 1

 for Millivolt models 

and 

Figure 2 

For Electronic Models.

In Canada - CAN/CGA-2.17-M91 (R2009) 

(high altitude): THE CONVERSION SHALL 

BE CARRIEd OUT BY A MANUFACTURER’S 

AUTHORIZEd REPRESENTATIVE,IN 

ACCORdANCE WITH THE REQUIREMENTS 

OF THE MANUFACTURER, PROVINCIAL 

OR TERRITORIAL AUTHORITIES HAVING 

JURISdICTION ANd IN ACCORdANCE WITH 

THE REQUIREMENTS OF THE CAN/CGA-B149.1 

OR CAN/CGA-B149.2 INSTALLATION COdES.

H I 

L  O W 

H T 

P T 

H T 

P T 

P I L O 

P I 

L O 

O N 

it

O  F F 

IN  OUT 

HI/LO Variable

Flame Height

Adjustment

Figure 1 - SIT Millivolt 

Gas Valve

Manifold Pressure Tap

Inlet Pressure Tap

Pilot Adjustment

Screw

Main Gas Control Knob

OFF/PILOT/ON

Orange Wire

(from dFC Wire 

Harness)

Main Gas Inlet

3/8" NPT

Green Wire

(from dFC Wire Harness)

Inlet (IN) Test Port

Manifold (OUT) Test Port

Figure 2 - SIT Electronic Gas Valve

Hi/Lo Flame 

Control Knob

Yellow Ground Wire

(from dFC Wire Harness)

Summary of Contents for MPD35CNE

Page 1: ...fire or explosion may result causing property damage personal injury or death WARNING AVERTISSEMENT AVISO HOT GLASS WILL CAUSE BURNS DO NOT TOUCH GLASS UNTIL COOLED NEVER ALLOW CHILDREN TO TOUCH GLAS...

Page 2: ...cal Installation Sequence 9 Detailed Installation Steps 9 Step 1 Framing 9 Fireplace and Framing Specifications 10 Step 2 Routing Gas Line 11 Step 3 Preparing Appliance Vent Collar 12 Step 4 Installin...

Page 3: ...is appliance can cause serious injury or death from fire burns explosion or carbon monoxide poisoning WARNING Failure to position the parts in accordance with these diagrams or failure to use only par...

Page 4: ...55 0 052 19L52 MPD40 38 0 102 99K76 0 062 21L01 MPD45 37 0 104 24M10 52 0 0635 37G00 Table 4 Standard size installed at factory Part Cat Number REQUIREMENTS FOR THE COMMONWEALTHOFMASSACHUSETTS These f...

Page 5: ...the appliance Cold Climate Insulation For cold climate installations seal all cracks around your appliance with noncombustible material and wherever cold air could enter the room It is especially imp...

Page 6: ...ents Above Flat Or Sloped Roofs Ref NFPA 54 ANSI Z223 1 Roof Pitch H ft H m Flat 6 12 1 0 0 3 6 12 7 12 1 25 0 38 7 12 8 12 1 5 0 46 8 12 9 12 2 0 0 61 9 12 10 12 2 5 0 76 10 12 11 12 3 25 0 99 11 12...

Page 7: ...er 5 12 7 cm 5 12 7 cm G Clearance to inside corner 2 5 08cm minimum SV4 5HT 2 6 15 2cm minimum SV4 5HTSS 2 5 08cm minimum SV4 5HT 2 6 15 2cm minimum SV4 5HTSS H Clearancetoeachinsideofcenterlineexten...

Page 8: ...ve to conform to standard hearth extension installation requirements Shelf Height To provide for the lowest possible shelf surface use the alternate rear vent outlet the venting attached to the top ve...

Page 9: ...the framing and secure with nailing brackets IMPORTANT Bend up the appropriate header spacing standoffs for the drywall finish material thickness to be used see Figure 11 Bend up the outer pair for 1...

Page 10: ...lectrical Inlet Knockout requiring a Field Provided Junction Box either side E B D C Front View 3 76 A Header Spacing Top Standoffs Vertical Venting through the Ceiling Frame ceiling opening Use a plu...

Page 11: ...aming 6 1 2 152 mm Pipe Coupling Recommended NOTE Rear Vent Applications in Corner Installations The horizontal vent length from a to b must not exceed 28 inches 711 mm MPDT33 and MPDR33 Models Dimens...

Page 12: ...ct Venting System Horizontal or Vertical Withtheappliancesecuredinframing determine ventroutingandidentifytheexteriortermination location The following sections describe vertical roof and horizontal e...

Page 13: ...4 1 1 0 0 5 0 6 3 8 1 5 2 5 1 0 1 0 5 0 6 6 8 1 5 5 1 0 0 0 0 4 4 5 0 9 1 5 7 8 5 1 1 0 0 0 4 5 5 6 9 1 5 7 3 6 1 0 1 0 0 4 5 5 5 0 2 5 2 1 7 1 0 1 1 5 0 7 7 0 2 5 2 7 1 0 0 0 6 0 6 5 1 1 2 5 2 6 7 1...

Page 14: ...e radial alignment until the four locking dimples are aligned with the inlet of the four inclined channels on the collar refer to Figure 21 Push the vent component againstthecollaruntilitfullyengages...

Page 15: ...llar section to align with the required direction of the next vent run element Twist elbow sections in a clockwise direction only so as to avoid the possiblity of unlocking anyofthepreviouslyconnected...

Page 16: ...ou are allowed 2 feet of H horizontal run up to a maximum horizontal run of 8 feet Example If 8 feet of H horizontal vent run is needed then 4 feet minimum V vertical vent will be required TABLE A H M...

Page 17: ...6 096 4 1 219 H H1 20 feet 6 096 m Max V V1 H H1 40 ft 12 192 m Max meters meters Example If 20 feet of H horizontal vent run is needed then 4 feet minimum of V vertical vent will be required This tab...

Page 18: ...al both the inner and outer pipe elements with the same procedure Sealant and securing screws are not required NOTE An elbow may also be attached to the appliance collar Attach in the same manner as y...

Page 19: ...4 32 mm as shown in Figure 34 SVHRK Snorkel Cap The snorkel cap is designed to be fitted into a basement window box The SVHRK cap is for use with flex vent The vertical distance between the inlet and...

Page 20: ...owingwallthicknessrange when using SV4 5HT 2 termination kit HORIZONTAL Vent Figures Tables NOTE Secure Vent components rigid vent pipe and terminal are shown in the figures Secure Flex components fle...

Page 21: ...of H horizontal vent run is needed then 4 feet minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio For every 1 foot of V vertical you are allowed 5 feet of H horizontal run...

Page 22: ...al rise except where an elbow is the only vertical component in the system See Figure 36 V Minimum feet feet 5 1 524 Elbow Only 5 1 524 1 0 305 10 3 048 2 0 610 15 4 572 3 0 914 20 6 096 4 1 219 meter...

Page 23: ...No 10K81 to the inner adaptor collar approximately 1 2 inch from the end 3 Pull and extend the inner flexible vent pipe 4 Slide the inner flex pipe over the adaptor collar Ensure the flexible vent pip...

Page 24: ...t of 2 conductor wire supplied with the unit NOTE The supplied 15 feet of 2 conductor wire has one end of each conductor connected to the gas valve circuit and the other end of each conductor placed l...

Page 25: ...eplace The millivolt control valve has a 3 8 10mm NPT thread inlet port The electronic control valve has a 1 2 13 mm NPT thread inlet port and is fitted with a 1 2 x 3 8 13 mm x 10 mm NPT fitting Secu...

Page 26: ...onovertime A Light the appliance refer to the lighting instructionslabelinthecontrolcompartment or in the Care and Operation Instructions manual B Brush all joints and connections with the gas leak te...

Page 27: ...pli ances to Figure 54 for MPD35 Series appli ancesandtoFigure55forMPD40andMPD45 Series appliances WARNING DO NOT attempt to install the logs until the appliance instal lationhasbeencompleted the gas...

Page 28: ...firebox with the log s notches directly over the brackets Position the right log log no 3 by inserting the pin from the rear log into the hole on its upper end Place the left log and then the smaller...

Page 29: ...the order shown Position the rear log on the brackets at the rear of the firebox with the log s notches directly over the brackets Position the right log log no 3 by inserting the pin from the rear l...

Page 30: ...ividual logs as shown below Logs should be placed in the order shown Position the center log on the burner first then place the glowing embers as shown in Figure 52 Place the rear log both the right a...

Page 31: ...t appear sooty The following chart is provided to aid you in achieving the correct air shutter adjustment for your installation Figure 56 Removing the Glass Enclosure Panel see Figure 56 Remove the to...

Page 32: ...ireplace rod located in the lower control area Position the air shutter to the factory setting as shown in the table in Figure 60 2 Light appliance follow lighting procedure on lighting label in contr...

Page 33: ...bustible material may touch top of appliance Combustible materials NOT allowed below this point on face of appliance Header Spacing Top Standoff Top of Appliance Top of Door Frame Hood must be install...

Page 34: ...er la poussi re et les traces de graisse ou d huile Collez l tiquette sur la surface de la plaque de l interrupteur mural qui contr le le foyer Figure A ou du thermostat mural Figure B Choisissez la l...

Page 35: ...6 SV4 5HF 10 Firestop Spacer Hori zontal rigid 3 1 1 spac ing 10 Pack H2247 SV4 5VF 10 Firestop Spacer Verti cal rigid 1 1 1 spac ing 10 Pack 96K92 SV4 5SP Support Plate Installation Accessories Liste...

Page 36: ...T48SS Small Square Termination for flex with 48 1219 mm of compressed flex vent Ref Instr 750204M 94L09 SF HTSS Horizontal Small Square Termination for flex without flex vent Ref Instr 750204M INSTALL...

Page 37: ...pin located at the door s left side to the right until it disengages from the left corner post hole Pull the control compartment door diagonally to the left away from the fireplace Step 3 Remove the...

Page 38: ...crews previously removed Step 12 Reinstall the baffle with the two baffle securing screws Step 13 Reassemble the remaining compo nents by reversing the procedures outlined in the Steps 1 5 Step 14 Att...

Reviews: