LENNOX HEARTH PRODUCTS  •  MERIT PLUS

®

 DIRECT VENT GAS FIREPLACES (MPD33/35/40/45)  •  INSTALLATION INSTRUCTIONS

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Burner Orifice Sizes 

Elevation 0-4500 feet ( 0-1372 meters)

Model

Series

Nat.Gas

drill size (inches)

Propane

drill size (inches)

MPd33

#47 (0.0785")* 

99K74 •

0.048"

99K78 •

MPd35

#44 (0.086")*

60J80 •

#55 (0.052")*

19L52 •

MPd40

#38 (0.102") *

99K76 •

0.062"

21L01 •

MPd45

#37 (0.104")*

24M10 •

#52 (0.0635")*

37G00 •

Table 10

* Standard size installed at factory

• Part /Cat. Number

Step 4.

 Carefully remove the logs. 

Exercise 

care so as not to break the logs

.

Step 5.

 Refer to 

Figure 53, 54, or 55

A.

 Remove the grate and sub floor.

B.

 Remove the two (2) screws securing the 

burner assembly.

C.

 Remove the burner assembly with attached 

venturi tube.

Millivolt and Electronic Ignition System 

Appliances

Step 6.

 

SIT Systems

 - Refer to 

Figure 63

 

and the instructions provided with the SIT 

Regulator  Conversion  Kit.  Using  a  Torx  T20 

driver (with 1/4" shank and center hole) or 

slotted screwdriver, remove and discard the 

pressure regulator mounting screws (two 

screws for electronic models, three screws 

for millivolt models), pressure regulator tower, 

the diaphragm assembly (if applicable) and 

the spring. Discard all removed components.

Step 7.

 Install the new pressure regulator as-

sembly using the supplied screws as shown 

in 

Figure 63

. Tighten the screws to 25 in-lb.

Figure 65: Orifice

Figure 63: Regulator Conversion

Pressure

Regulator

Remove

These

Components

Electronic Valve

Millivolt Valve

Use pipe joint compound or Teflon tape on all 

pipe fittings before installing (ensure propane 

resistant compounds are used in propane ap-

plications, do not use pipe joint compounds 

on flare fittings).

Step 11.

 Retrieve the burner and hold the 

venturi tube above the orifice. Place the shutter 

adjusting rod in the slot of the shutter arm (see 

Figure 60

 on 

Page 34

). Set the burner assem-

bly into its position and secure the trapezoidal 

plate with the two screws previously removed. 

Step 12.

 Reinstall the baffle with the two baffle 

securing screws.

Step 13.

 Reassemble the remaining compo-

nents by reversing the procedures outlined in 

the 

Steps 1-5

.

Step 14

. Attach the conversion label provided 

in the conversion kit next to the rating plate on 

the appliance.

Step 15

. Turn on gas supply and test for gas 

leaks (refer to 

Page 27

).

Step 16

. Relight the main burner. The lighting 

instructions can be found on the lighting label 

in the control compartment or in the Care and 

Operation Manual provided with the appliance. 

Verify proper burner ignition and operation. See 

Burner Adjustments and Burner Flame Appear-

ance on 

Page 33

.

Step 17. 

Inspect the pilot system for proper 

flame. The pilot flame should engulf the flame 

sensor as shown in 

Figures  49  and  50

 on 

Page 27

.

Step 18

. Using a manometer, test the inlet and 

manifold gas pressures. See 

Tables 2 and 3

 

on 

Page 4

.

ALWAYS TEST PRESSURES WITH THE VALVE 

REGULATOR CONTROL AT THE HIGHEST 

SETTING.

Step 10.

 Remove the orifice from the manifold 

and replace it with the one provided in the kit. 

See 

Table 10

 for orifice sizes for natural and 

propane models. 

Figure 65 

illustrates the orifice.

Pilot

Orifice

Figure 64: Millivolt Pilot 

                 (electronic pilot is similar)

Step 8.

 Install the enclosed identification label 

to the valve body where it can be easily seen. 

Step 9.

 Refer to 

Figure 64

. Remove the pilot 

hood assembly to access the hexed pilot orifice. 

Remove and replace the orifice with the one 

provided with the kit. Exercise extreme care to 

prevent damage to or breakage of the igniter 

assembly.

Printed in U.S.A. © 2012 Lennox Hearth Products LLC

P/N  506015-07   Rev. B   06/2013

Lennox Hearth Products reserves the right to make changes at any time, without notice, in 

design, materials, specifications, and prices, and also to discontinue colors, styles, and products. 

Consult your local distributor for fireplace code information.

LENNOX

®

, the LENNOX design, DAVE LENNOX, the image of DAVE LENNOX and other related 

LENNOX marks are registered or common law trademarks of Lennox Industries Inc. and are 

used with permission.

1508 Elm Hill Pike, Suite 108 • Nashville, TN  37210

Summary of Contents for MPD35CNE

Page 1: ...fire or explosion may result causing property damage personal injury or death WARNING AVERTISSEMENT AVISO HOT GLASS WILL CAUSE BURNS DO NOT TOUCH GLASS UNTIL COOLED NEVER ALLOW CHILDREN TO TOUCH GLAS...

Page 2: ...cal Installation Sequence 9 Detailed Installation Steps 9 Step 1 Framing 9 Fireplace and Framing Specifications 10 Step 2 Routing Gas Line 11 Step 3 Preparing Appliance Vent Collar 12 Step 4 Installin...

Page 3: ...is appliance can cause serious injury or death from fire burns explosion or carbon monoxide poisoning WARNING Failure to position the parts in accordance with these diagrams or failure to use only par...

Page 4: ...55 0 052 19L52 MPD40 38 0 102 99K76 0 062 21L01 MPD45 37 0 104 24M10 52 0 0635 37G00 Table 4 Standard size installed at factory Part Cat Number REQUIREMENTS FOR THE COMMONWEALTHOFMASSACHUSETTS These f...

Page 5: ...the appliance Cold Climate Insulation For cold climate installations seal all cracks around your appliance with noncombustible material and wherever cold air could enter the room It is especially imp...

Page 6: ...ents Above Flat Or Sloped Roofs Ref NFPA 54 ANSI Z223 1 Roof Pitch H ft H m Flat 6 12 1 0 0 3 6 12 7 12 1 25 0 38 7 12 8 12 1 5 0 46 8 12 9 12 2 0 0 61 9 12 10 12 2 5 0 76 10 12 11 12 3 25 0 99 11 12...

Page 7: ...er 5 12 7 cm 5 12 7 cm G Clearance to inside corner 2 5 08cm minimum SV4 5HT 2 6 15 2cm minimum SV4 5HTSS 2 5 08cm minimum SV4 5HT 2 6 15 2cm minimum SV4 5HTSS H Clearancetoeachinsideofcenterlineexten...

Page 8: ...ve to conform to standard hearth extension installation requirements Shelf Height To provide for the lowest possible shelf surface use the alternate rear vent outlet the venting attached to the top ve...

Page 9: ...the framing and secure with nailing brackets IMPORTANT Bend up the appropriate header spacing standoffs for the drywall finish material thickness to be used see Figure 11 Bend up the outer pair for 1...

Page 10: ...lectrical Inlet Knockout requiring a Field Provided Junction Box either side E B D C Front View 3 76 A Header Spacing Top Standoffs Vertical Venting through the Ceiling Frame ceiling opening Use a plu...

Page 11: ...aming 6 1 2 152 mm Pipe Coupling Recommended NOTE Rear Vent Applications in Corner Installations The horizontal vent length from a to b must not exceed 28 inches 711 mm MPDT33 and MPDR33 Models Dimens...

Page 12: ...ct Venting System Horizontal or Vertical Withtheappliancesecuredinframing determine ventroutingandidentifytheexteriortermination location The following sections describe vertical roof and horizontal e...

Page 13: ...4 1 1 0 0 5 0 6 3 8 1 5 2 5 1 0 1 0 5 0 6 6 8 1 5 5 1 0 0 0 0 4 4 5 0 9 1 5 7 8 5 1 1 0 0 0 4 5 5 6 9 1 5 7 3 6 1 0 1 0 0 4 5 5 5 0 2 5 2 1 7 1 0 1 1 5 0 7 7 0 2 5 2 7 1 0 0 0 6 0 6 5 1 1 2 5 2 6 7 1...

Page 14: ...e radial alignment until the four locking dimples are aligned with the inlet of the four inclined channels on the collar refer to Figure 21 Push the vent component againstthecollaruntilitfullyengages...

Page 15: ...llar section to align with the required direction of the next vent run element Twist elbow sections in a clockwise direction only so as to avoid the possiblity of unlocking anyofthepreviouslyconnected...

Page 16: ...ou are allowed 2 feet of H horizontal run up to a maximum horizontal run of 8 feet Example If 8 feet of H horizontal vent run is needed then 4 feet minimum V vertical vent will be required TABLE A H M...

Page 17: ...6 096 4 1 219 H H1 20 feet 6 096 m Max V V1 H H1 40 ft 12 192 m Max meters meters Example If 20 feet of H horizontal vent run is needed then 4 feet minimum of V vertical vent will be required This tab...

Page 18: ...al both the inner and outer pipe elements with the same procedure Sealant and securing screws are not required NOTE An elbow may also be attached to the appliance collar Attach in the same manner as y...

Page 19: ...4 32 mm as shown in Figure 34 SVHRK Snorkel Cap The snorkel cap is designed to be fitted into a basement window box The SVHRK cap is for use with flex vent The vertical distance between the inlet and...

Page 20: ...owingwallthicknessrange when using SV4 5HT 2 termination kit HORIZONTAL Vent Figures Tables NOTE Secure Vent components rigid vent pipe and terminal are shown in the figures Secure Flex components fle...

Page 21: ...of H horizontal vent run is needed then 4 feet minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio For every 1 foot of V vertical you are allowed 5 feet of H horizontal run...

Page 22: ...al rise except where an elbow is the only vertical component in the system See Figure 36 V Minimum feet feet 5 1 524 Elbow Only 5 1 524 1 0 305 10 3 048 2 0 610 15 4 572 3 0 914 20 6 096 4 1 219 meter...

Page 23: ...No 10K81 to the inner adaptor collar approximately 1 2 inch from the end 3 Pull and extend the inner flexible vent pipe 4 Slide the inner flex pipe over the adaptor collar Ensure the flexible vent pip...

Page 24: ...t of 2 conductor wire supplied with the unit NOTE The supplied 15 feet of 2 conductor wire has one end of each conductor connected to the gas valve circuit and the other end of each conductor placed l...

Page 25: ...eplace The millivolt control valve has a 3 8 10mm NPT thread inlet port The electronic control valve has a 1 2 13 mm NPT thread inlet port and is fitted with a 1 2 x 3 8 13 mm x 10 mm NPT fitting Secu...

Page 26: ...onovertime A Light the appliance refer to the lighting instructionslabelinthecontrolcompartment or in the Care and Operation Instructions manual B Brush all joints and connections with the gas leak te...

Page 27: ...pli ances to Figure 54 for MPD35 Series appli ancesandtoFigure55forMPD40andMPD45 Series appliances WARNING DO NOT attempt to install the logs until the appliance instal lationhasbeencompleted the gas...

Page 28: ...firebox with the log s notches directly over the brackets Position the right log log no 3 by inserting the pin from the rear log into the hole on its upper end Place the left log and then the smaller...

Page 29: ...the order shown Position the rear log on the brackets at the rear of the firebox with the log s notches directly over the brackets Position the right log log no 3 by inserting the pin from the rear l...

Page 30: ...ividual logs as shown below Logs should be placed in the order shown Position the center log on the burner first then place the glowing embers as shown in Figure 52 Place the rear log both the right a...

Page 31: ...t appear sooty The following chart is provided to aid you in achieving the correct air shutter adjustment for your installation Figure 56 Removing the Glass Enclosure Panel see Figure 56 Remove the to...

Page 32: ...ireplace rod located in the lower control area Position the air shutter to the factory setting as shown in the table in Figure 60 2 Light appliance follow lighting procedure on lighting label in contr...

Page 33: ...bustible material may touch top of appliance Combustible materials NOT allowed below this point on face of appliance Header Spacing Top Standoff Top of Appliance Top of Door Frame Hood must be install...

Page 34: ...er la poussi re et les traces de graisse ou d huile Collez l tiquette sur la surface de la plaque de l interrupteur mural qui contr le le foyer Figure A ou du thermostat mural Figure B Choisissez la l...

Page 35: ...6 SV4 5HF 10 Firestop Spacer Hori zontal rigid 3 1 1 spac ing 10 Pack H2247 SV4 5VF 10 Firestop Spacer Verti cal rigid 1 1 1 spac ing 10 Pack 96K92 SV4 5SP Support Plate Installation Accessories Liste...

Page 36: ...T48SS Small Square Termination for flex with 48 1219 mm of compressed flex vent Ref Instr 750204M 94L09 SF HTSS Horizontal Small Square Termination for flex without flex vent Ref Instr 750204M INSTALL...

Page 37: ...pin located at the door s left side to the right until it disengages from the left corner post hole Pull the control compartment door diagonally to the left away from the fireplace Step 3 Remove the...

Page 38: ...crews previously removed Step 12 Reinstall the baffle with the two baffle securing screws Step 13 Reassemble the remaining compo nents by reversing the procedures outlined in the Steps 1 5 Step 14 Att...

Reviews: