LENNOX HEARTH PRODUCTS  •  MERIT PLUS

®

 DIRECT VENT GAS FIREPLACES (MPD33/35/40/45)  •  INSTALLATION INSTRUCTIONS

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Figure 7 - Exterior Horizontal Vent Termination Clearance Requirements

EXTERIOR HORIZONTAL VENT TERMINATION CLEARANCE REQUIREMENTS 

V

V

V

V

V

F

C

Fixed

Closed

Window

Operable

Window

B

B

A

B

H

M

I

= Area where Termination is not Permitted

= Air Supply Inlet

X

= Vent Termination

V

D

V

3 ft.

3 ft.

= 9” in U.S.

= 12” in Canada

V

L

B

J

X

V

A

G

Inside

Corner Detail

B

C

C

C

*18”

Ventilated Soffit

Horizontal

Termination

Detail D

Exterior Wall

6”

Inside Corner

See Item D in the Text Below.

V

P

V

O

N

N

Q

NOTE:  Local Codes Or Regulations

May Require Different Clearances.

NOTE:  Location Of The Vent Termination

Must Not Interfere With Access To The

Electrical Service.

E

K

X

Minimum Clearances

Canadian Installation *

US Installation **

A = Clearance above grade, veranda, porch, deck 

or balcony.

12" (30 cm) *

12" (30 cm) **

B = Clearance to window or door that may be opened 6" (15.2 cm) for appliances < 10,000 BTU/hr (3kW), 

12" (30 cm) for appliances > 10,000 BTU/hr (3kW) 

6" (15.2 cm) for appliances < 10,000 BTU/hr (3kW), 
9" (23 cm) for appliances > 10,000 BTU/hr (3kW) and 

<  50,000 BTU/hr (15kW),  12" (30 cm) for appliances > 
50,000 BTU/hr (15kW)**

C = Clearance to permanently closed window

12" (305 mm) recommended to prevent window conden-

sation

9" (229 mm) recommended to prevent window con-

densation

d = Vertical clearance to ventilated soffit located 

above the terminal within a horizontal distance of 
18" (458 mm)

18" (458 mm)

18" (458 mm)

E = Clearance to unventilated soffit

12" (30 cm)

12" (30 cm)

F = Clearance to outside corner

5" (12.7 cm)

5" (12.7 cm)

G = Clearance to inside corner

2" (5.08cm) minimum - SV4.5HT-2 •
6" (15.2cm) minimum - SV4.5HTSS •

2" (5.08cm) minimum - SV4.5HT-2 •
6" (15.2cm) minimum - SV4.5HTSS •

H = Clearance to each inside of center line extended 

above meter / regulator assembly

3 feet (91 cm) within a height of 15 feet above the meter / 

regulator assembly *

3 feet (91 cm) within a height of 15 feet above the meter 

/ regulator assembly **

I = Clearance to service regulator vent outlet

3 feet (91 cm) *

3 feet (91 cm) **

J = Clearance to non-mechanical air supply inlet 

to building or the combustion air inlet to any other 
appliance

6" (15.2 cm) for appliances < 10,000 BTU/hr (3kW), 12" 

(30 cm) for appliances > 10,000 BTU/hr (3kW) 

6" (15.2 cm) for appliances < 10,000 BTU/hr (3kW), 9" 

(23 cm) for appliances > 10,000 BTU/hr (3kW) and <  
50,000 BTU/hr (15kW),  12" (30 cm) for appliances > 
50,000 BTU/hr (15kW)**

K = Clearance to mechanical air supply inlet

6 feet (1.83 meters) *

3 feet (91 cm) above, if within 10 feet (3 m) horizontally**

L = Clearance above paved sidewalk or paved 

driveway located on public property

7 feet (2.13 m) ‡

7 feet (2.13 m) ‡

M = Clearance under veranda, porch, deck or 

balcony

12" (30 cm) * ‡

12" (30 cm)  ‡

N = depth of Alcove (Maximum)

6 feet (1.83m)*

6 feet (1.83m)**

O = Clearance to Termination (Alcove)

6" (15.2mm)*

6" (15.2mm)**

P = Width of Alcove (Minimum)

3 feet (91cm)*

3 feet (91cm)**

Q = Clearance to Combustible Above (Alcove)

18" (457mm)*

18" (457mm)**

* In accordance with the current CAN/CGA-B149.1 National Gas and Propane Installation Code.
** In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Codes.
‡ A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings.
*‡ Only permitted if veranda, porch, deck or balcony is fully open on a minimum 2 sides beneath the floor.

• 2" Clearance to Non-Combustibles for SV4.5HT-2 Only.

Summary of Contents for MPD35CNE

Page 1: ...fire or explosion may result causing property damage personal injury or death WARNING AVERTISSEMENT AVISO HOT GLASS WILL CAUSE BURNS DO NOT TOUCH GLASS UNTIL COOLED NEVER ALLOW CHILDREN TO TOUCH GLAS...

Page 2: ...cal Installation Sequence 9 Detailed Installation Steps 9 Step 1 Framing 9 Fireplace and Framing Specifications 10 Step 2 Routing Gas Line 11 Step 3 Preparing Appliance Vent Collar 12 Step 4 Installin...

Page 3: ...is appliance can cause serious injury or death from fire burns explosion or carbon monoxide poisoning WARNING Failure to position the parts in accordance with these diagrams or failure to use only par...

Page 4: ...55 0 052 19L52 MPD40 38 0 102 99K76 0 062 21L01 MPD45 37 0 104 24M10 52 0 0635 37G00 Table 4 Standard size installed at factory Part Cat Number REQUIREMENTS FOR THE COMMONWEALTHOFMASSACHUSETTS These f...

Page 5: ...the appliance Cold Climate Insulation For cold climate installations seal all cracks around your appliance with noncombustible material and wherever cold air could enter the room It is especially imp...

Page 6: ...ents Above Flat Or Sloped Roofs Ref NFPA 54 ANSI Z223 1 Roof Pitch H ft H m Flat 6 12 1 0 0 3 6 12 7 12 1 25 0 38 7 12 8 12 1 5 0 46 8 12 9 12 2 0 0 61 9 12 10 12 2 5 0 76 10 12 11 12 3 25 0 99 11 12...

Page 7: ...er 5 12 7 cm 5 12 7 cm G Clearance to inside corner 2 5 08cm minimum SV4 5HT 2 6 15 2cm minimum SV4 5HTSS 2 5 08cm minimum SV4 5HT 2 6 15 2cm minimum SV4 5HTSS H Clearancetoeachinsideofcenterlineexten...

Page 8: ...ve to conform to standard hearth extension installation requirements Shelf Height To provide for the lowest possible shelf surface use the alternate rear vent outlet the venting attached to the top ve...

Page 9: ...the framing and secure with nailing brackets IMPORTANT Bend up the appropriate header spacing standoffs for the drywall finish material thickness to be used see Figure 11 Bend up the outer pair for 1...

Page 10: ...lectrical Inlet Knockout requiring a Field Provided Junction Box either side E B D C Front View 3 76 A Header Spacing Top Standoffs Vertical Venting through the Ceiling Frame ceiling opening Use a plu...

Page 11: ...aming 6 1 2 152 mm Pipe Coupling Recommended NOTE Rear Vent Applications in Corner Installations The horizontal vent length from a to b must not exceed 28 inches 711 mm MPDT33 and MPDR33 Models Dimens...

Page 12: ...ct Venting System Horizontal or Vertical Withtheappliancesecuredinframing determine ventroutingandidentifytheexteriortermination location The following sections describe vertical roof and horizontal e...

Page 13: ...4 1 1 0 0 5 0 6 3 8 1 5 2 5 1 0 1 0 5 0 6 6 8 1 5 5 1 0 0 0 0 4 4 5 0 9 1 5 7 8 5 1 1 0 0 0 4 5 5 6 9 1 5 7 3 6 1 0 1 0 0 4 5 5 5 0 2 5 2 1 7 1 0 1 1 5 0 7 7 0 2 5 2 7 1 0 0 0 6 0 6 5 1 1 2 5 2 6 7 1...

Page 14: ...e radial alignment until the four locking dimples are aligned with the inlet of the four inclined channels on the collar refer to Figure 21 Push the vent component againstthecollaruntilitfullyengages...

Page 15: ...llar section to align with the required direction of the next vent run element Twist elbow sections in a clockwise direction only so as to avoid the possiblity of unlocking anyofthepreviouslyconnected...

Page 16: ...ou are allowed 2 feet of H horizontal run up to a maximum horizontal run of 8 feet Example If 8 feet of H horizontal vent run is needed then 4 feet minimum V vertical vent will be required TABLE A H M...

Page 17: ...6 096 4 1 219 H H1 20 feet 6 096 m Max V V1 H H1 40 ft 12 192 m Max meters meters Example If 20 feet of H horizontal vent run is needed then 4 feet minimum of V vertical vent will be required This tab...

Page 18: ...al both the inner and outer pipe elements with the same procedure Sealant and securing screws are not required NOTE An elbow may also be attached to the appliance collar Attach in the same manner as y...

Page 19: ...4 32 mm as shown in Figure 34 SVHRK Snorkel Cap The snorkel cap is designed to be fitted into a basement window box The SVHRK cap is for use with flex vent The vertical distance between the inlet and...

Page 20: ...owingwallthicknessrange when using SV4 5HT 2 termination kit HORIZONTAL Vent Figures Tables NOTE Secure Vent components rigid vent pipe and terminal are shown in the figures Secure Flex components fle...

Page 21: ...of H horizontal vent run is needed then 4 feet minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio For every 1 foot of V vertical you are allowed 5 feet of H horizontal run...

Page 22: ...al rise except where an elbow is the only vertical component in the system See Figure 36 V Minimum feet feet 5 1 524 Elbow Only 5 1 524 1 0 305 10 3 048 2 0 610 15 4 572 3 0 914 20 6 096 4 1 219 meter...

Page 23: ...No 10K81 to the inner adaptor collar approximately 1 2 inch from the end 3 Pull and extend the inner flexible vent pipe 4 Slide the inner flex pipe over the adaptor collar Ensure the flexible vent pip...

Page 24: ...t of 2 conductor wire supplied with the unit NOTE The supplied 15 feet of 2 conductor wire has one end of each conductor connected to the gas valve circuit and the other end of each conductor placed l...

Page 25: ...eplace The millivolt control valve has a 3 8 10mm NPT thread inlet port The electronic control valve has a 1 2 13 mm NPT thread inlet port and is fitted with a 1 2 x 3 8 13 mm x 10 mm NPT fitting Secu...

Page 26: ...onovertime A Light the appliance refer to the lighting instructionslabelinthecontrolcompartment or in the Care and Operation Instructions manual B Brush all joints and connections with the gas leak te...

Page 27: ...pli ances to Figure 54 for MPD35 Series appli ancesandtoFigure55forMPD40andMPD45 Series appliances WARNING DO NOT attempt to install the logs until the appliance instal lationhasbeencompleted the gas...

Page 28: ...firebox with the log s notches directly over the brackets Position the right log log no 3 by inserting the pin from the rear log into the hole on its upper end Place the left log and then the smaller...

Page 29: ...the order shown Position the rear log on the brackets at the rear of the firebox with the log s notches directly over the brackets Position the right log log no 3 by inserting the pin from the rear l...

Page 30: ...ividual logs as shown below Logs should be placed in the order shown Position the center log on the burner first then place the glowing embers as shown in Figure 52 Place the rear log both the right a...

Page 31: ...t appear sooty The following chart is provided to aid you in achieving the correct air shutter adjustment for your installation Figure 56 Removing the Glass Enclosure Panel see Figure 56 Remove the to...

Page 32: ...ireplace rod located in the lower control area Position the air shutter to the factory setting as shown in the table in Figure 60 2 Light appliance follow lighting procedure on lighting label in contr...

Page 33: ...bustible material may touch top of appliance Combustible materials NOT allowed below this point on face of appliance Header Spacing Top Standoff Top of Appliance Top of Door Frame Hood must be install...

Page 34: ...er la poussi re et les traces de graisse ou d huile Collez l tiquette sur la surface de la plaque de l interrupteur mural qui contr le le foyer Figure A ou du thermostat mural Figure B Choisissez la l...

Page 35: ...6 SV4 5HF 10 Firestop Spacer Hori zontal rigid 3 1 1 spac ing 10 Pack H2247 SV4 5VF 10 Firestop Spacer Verti cal rigid 1 1 1 spac ing 10 Pack 96K92 SV4 5SP Support Plate Installation Accessories Liste...

Page 36: ...T48SS Small Square Termination for flex with 48 1219 mm of compressed flex vent Ref Instr 750204M 94L09 SF HTSS Horizontal Small Square Termination for flex without flex vent Ref Instr 750204M INSTALL...

Page 37: ...pin located at the door s left side to the right until it disengages from the left corner post hole Pull the control compartment door diagonally to the left away from the fireplace Step 3 Remove the...

Page 38: ...crews previously removed Step 12 Reinstall the baffle with the two baffle securing screws Step 13 Reassemble the remaining compo nents by reversing the procedures outlined in the Steps 1 5 Step 14 Att...

Reviews: