Page 5
13HPD SERIES
MANIFOLD GAUGES
RECOVERY MACHINE
CLEAN RECOVERY CYLINDER
OUTDOOR UNIT
Figure 6. Typical Refrigerant Recovery (Method 1)
METHOD 2:
If the existing outdoor unit is equipped with manual shut−off
valves then:
1. Start the existing HCFC−22 system in the cooling
mode and close the liquid line valve.
2. Pump all of the existing HCFC−22 refrigerant back into
the outdoor unit.
NOTE − It may be necessary to bypass the low pressure
switches to ensure complete refrigerant evacuation.
3. When the low side system pressures reach 0 psig,
close the vapor line valve.
4. Disconnect all power to the existing outdoor unit.
Check gauges after shutdown to confirm that the
valves are not allowing refrigerant to flow back into the
low side of the system.
5. Disconnect the liquid and vapor lines from the existing
outdoor unit.
Disconnecting and Removing Old
Outdoor Unit
Perform the following task at the existing outdoor unit:
Disconnect line set at the service valves.
Disconnect electrical service at the disconnect switch.
Remove old outdoor unit.
Positioning New Outdoor Unit
CAUTION
In order to avoid injury, take proper precaution when
lifting heavy objects.
See
Unit Dimensions
on page 2 to determine the correct
mounting size slab, platform or support. Refer to figure 7
for mandatory installation clearance requirements
(SEE NOTES
BELOW
FIGURE)
SEE NOTES NOTES
BELOW FIGURE)
(SEE NOTES
BELOW FIGURE)
(SEE NOTES
BELOW
FIGURE)
Figure 7. Installation Clearances
NOTES:
Service clearance of 30 in. (762 mm) must be
maintained on one of the sides adjacent to the control
box.
Clearance to one of the other three sides must be 36
in. (914 mm)
Clearance to one of the remaining two sides may be
12 in. (305 mm) and the final side may be 6 in. (152
mm)
48 in. (1219 mm) clearance required on top of unit.
A clearance of 24 in. (610 mm) must be maintained
between two units
POSITIONING CONSIDERATIONS
Consider the following when positioning the unit:
Some localities are adopting sound ordinances based
on the unit’s sound level registered from the adjacent
property, not from the installation property. Install the
unit as far as possible from the property line.
When possible, do not install the unit directly outside
a window. Glass has a very high level of sound
transmission. For proper placement of unit in relation
to a window see the provided illustration in figure 8.
INSTALL UNIT AWAY
FROM WINDOWS
TWO 90° ELBOWS INSTALLED IN LINE SET
WILL REDUCE LINE SET VIBRATION.
Figure 8. Outside Unit Placement