Page 17
ELECTRICAL DATA
4 TON
KHA048S
1
Voltage - 60hz
208/230V - 1 Ph
208/230V - 3 Ph
460V - 3 Ph
575V - 3 Ph
Compressor 1
Rated Load Amps
21.8
13.7
6.2
4.8
Locked Rotor Amps
117
83.1
41
33
Outdoor Fan
Motors (1)
Full Load Amps (total)
1.7
1.7
1.1
0.7
Power
Exhaust
(1) 0.75 HP
Full Load Amps (total)
5
5
2.2
1.5
Service Outlet 115V GFI
15 Amps
15 Amps
15 Amps
15 Amps
Indoor
Blower
Motor
Horsepower
.5
1.5
.5
1.5
2
.5 1.5
2
.5 1.5
2
Full Load Amps
3.9
11
3.9
6.6
7.5
2
3
3.4
2
2.4 2.7
2
Maximum
Overcurrent
Protection
Unit Only
50
60
35
35
40
15 15 15 15 15 15
with (1) 0.75 HP
Power Exhaust
50
60
40
40
45
15
20 20
15 15 15
3
Minimum
Circuit
Ampacity
Unit Only
33
40
23
26
27
11 12
13
9
10 10
with (1) 0.75 HP
Power Exhaust
38
45
28
31
32
14
15 15
11
11
11
ELECTRIC HEAT DATA
Electric Heat Voltage
208
240
208
240
208
240
208
240
208
240
480 480 480
600 600 600
2
Maximum
Overcurrent
Protection
Unit +
Electric Heat
7.5 kW
80 80 80
90
50 50 50 50 50 50 25 25 25
20 20 20
15 kW
110
125
110
125 70 70 70 80 70 80 35 35 35 30 30 30
3
Minimum
Circuit
Ampacity
Unit +
Electric Heat
7.5 kW
67 72 74 80 43
46
45 48
46 49
23
24 24
18
19 19
15 kW
101 111
108
119 62
68 65 71
66
72 34 35 35 27 28 28
2
Maximum
Overcurrent
Protection
Unit +
Electric Heat
and (1) 0.75 HP
Power Exhaust
7.5 kW
80
90 90 90
50
60
50
60 60 60
25 30 30
20 20 20
15 kW
110
125 125 125 70 80 70 80 80 80
40 40 40
30 30 30
3
Minimum
Circuit
Ampacity
Unit +
Electric Heat
and (1) 0.75 HP
Power Exhaust
7.5 kW
72 77 79 85 48 51 50 53 51 54 25
26 26 20 20 20
15 kW
106 116
113
124
67 73 70 76 71 77 36 37 38
29 29 29
ELECTRICAL ACCESSORIES
Disconnect
Kit
Standard Access -
0-7.5 kW
20W15
20W16
20W15
20W15
20W15
20W15
20W15
15 kW
20W16
20W16
20W15
20W15
20W15
20W15
20W15
Hinged Access -
0-7.5 kW
20W21
20W22
20W21
20W21
20W21
20W21
20W21
15 kW
20W22
20W22
20W21
20W21
20W21
20W21
20W21
Fuse Block
Unit Only
17W97 17W98 18W02 18W02 18W03
18W06
18W06
Unit + Power Exhaust
17W97 17W98 18W03 18W03 18W04 18W06 (.5 hp)
18W07 (1.5-2 hp)
18W06
1
Extremes of operating range are plus and minus 10% of line voltage.
2
HACR type breaker or fuse.
3
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
Summary of Contents for KHA SERIES
Page 41: ...Page 41 KHA036 048 060 Y Voltage 1 2 5 9 3 11 6 7 8 4 4 5 5 8 9 9 10...
Page 42: ...Page 42 KHA036 048 060 G J Voltage 1 2 5 9 3 11 6 7 8 4 4 5 5 7 9 9 10 11...
Page 46: ...Page 46 T1EH 7 5 10 15 22 5 kW P VOLTAGE 1 3 4 5 6 7 2 4 4 4 7 7 7...
Page 47: ...Page 47 T1EHA 7 5 15 22 5kW Y VOLTAGE KHA SERIES UNITS 1 3 4 5 6 7 2 4 7...
Page 48: ...Page 48 T1EHA 7 5 15 22 5kW G J VOLTAGE KHA SERIES UNITS 1 3 4 5 6 7 2 4 7...