background image

Page 8

BLOWER DATA - DIRECT DRIVE - KHA036-048

BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE. 

FOR ALL UNITS ADD:

 

1 - Any factory installed options air resistance (economizer, wet coil, etc.) See page 14.

 

2 - Any field installed accessories air resistance (electric heat, duct resistance, diffuser, etc.) See page 14.

External Static 

Pressure (in. 

w.g.)

Air Volume (cfm) at Various Blower Speeds

208 VOLTS

230 VOLTS

460/575 VOLTS

High

Medium

Low

High

Medium

Low

High

Medium

Low

3 and 4 Ton Standard Efficiency (Downflow)

KHA036S and KHA048S

0.0

1938

1552

1119

2167

1772

1317

2136

1716

1212

0.1

1992

1586

1128

2167

1780

1315

2104

1728

1208

0.2

1915

1592

1137

2100

1792

1307

2052

1684

1197

0.3

1865

1536

1083

2043

1735

1266

1994

1647

1172

0.4

1813

1495

1033

1986

1678

1204

1918

1597

1134

0.5

1762

1444

976

1909

1621

1164

1861

1534

1096

0.6

1694

1391

899

1814

1535

1082

1765

1485

1059

0.7

1609

1331

817

1718

1478

1000

1689

1410

996

0.8

1471

1220

730

1603

1364

918

1613

1335

920

0.9

1368

1066

522

1488

1250

755

1498

1235

848

1.0

1108

869

402

1259

1021

640

1345

1036

763

3 and 4 Ton Standard Efficiency (Horizontal)

KHA036S and KHA048S

0.0

1862

1520

1070

2082

1736

1259

2085

1745

1247

0.1

1867

1530

1069

2031

1717

1246

2070

1744

1257

0.2

1804

1485

1067

1978

1672

1227

2016

1690

1225

0.3

1741

1440

1018

1907

1627

1190

1944

1643

1192

0.4

1677

1396

968

1837

1567

1128

1890

1596

1160

0.5

1614

1329

894

1749

1492

1066

1800

1533

1111

0.6

1550

1284

844

1660

1417

1016

1727

1455

1062

0.7

1455

1195

769

1554

1327

941

1655

1377

996

0.8

1329

1106

670

1448

1237

842

1511

1283

865

0.9

1202

927

496

1307

1087

718

1403

1190

784

1.0

1012

828

385

1150

973

613

1222

1002

670

Summary of Contents for KHA SERIES

Page 1: ...ation and service must be performed by a licensed professional installer or equivalent service agency or the gas supplier CAUTION Danger of sharp metallic edges Can cause injury Take care when servici...

Page 2: ...D10N 1 17W90 X K1GARD10AP1 53W22 X Hinged Access Panels O O O O O O CONTROLS Smoke Detector Supply or Return Power board and one sensor C1SNSR44AP1 53W78 X X X X X X Smoke Detector Supply and Return P...

Page 3: ...X X X X X X ELECTRIC HEAT 7 5 kW 208 230V 1ph T1EH0075AN1P 14W32 X X X X X 208 230V 3ph T1EH0075AN1Y 14W35 X X X X 460V 3ph T1EH0075AN1G 14W39 X X X X 575V 3ph T1EH0075AN1J 14W43 X X X X 10 kW 208 23...

Page 4: ...13K56 X Transitions Supply and Return Order one T1TRAN10AN1 17W53 X X X X X T1TRAN20N 1 17W54 X ROOF CURBS downFlow Cliplock 8 in height T1CURB23AN1 16W93 X X X X X 1 X K1CURB23AP1 52W20 X 14 in heigh...

Page 5: ...il Fan Motor HP 1 4 1 4 1 4 1 4 Motor rpm 825 825 825 825 Total motor watts 250 250 250 250 Diameter in No of blades 24 3 24 3 24 3 24 3 Total air volume cfm 3300 3300 3300 3300 Indoor Coil Net face a...

Page 6: ...c Expansion Valve removeable power head 5 Indoor Blower Drive Selection Nominal Motor HP 1 5 hp 6 2 hp 1 5 hp 6 2 hp 1 5 hp 2 hp Maximum Usable Motor HP 1 72 hp 2 3 hp 1 72 hp 2 3 hp 1 72 hp 2 3 hp Av...

Page 7: ...030S 0 0 1199 928 838 1379 1085 877 0 1 1229 926 813 1409 1086 872 0 2 1206 928 782 1367 1094 850 0 3 1183 881 742 1350 1047 820 0 4 1159 843 686 1321 1009 783 0 5 1136 812 643 1282 981 762 0 6 1103 7...

Page 8: ...5 1266 1994 1647 1172 0 4 1813 1495 1033 1986 1678 1204 1918 1597 1134 0 5 1762 1444 976 1909 1621 1164 1861 1534 1096 0 6 1694 1391 899 1814 1535 1082 1765 1485 1059 0 7 1609 1331 817 1718 1478 1000...

Page 9: ...1171 0 52 1213 0 55 1252 0 59 1289 0 62 1324 0 66 1300 1044 0 47 1091 0 49 1137 0 53 1181 0 56 1221 0 60 1259 0 64 1296 0 68 1330 0 71 1400 1058 0 51 1105 0 54 1150 0 57 1191 0 61 1231 0 65 1268 0 69...

Page 10: ...230 0 79 1265 0 83 1299 0 87 1332 0 91 1364 0 95 1800 1133 0 73 1174 0 77 1209 0 81 1244 0 85 1278 0 90 1311 0 94 1343 0 98 1375 1 02 1900 1156 0 80 1193 0 84 1226 0 89 1260 0 93 1293 0 97 1325 1 01 1...

Page 11: ...8 1 01 1294 1 05 1325 1 09 1351 1 14 1376 1 19 2200 1170 0 97 1206 1 01 1242 1 05 1277 1 09 1311 1 14 1341 1 18 1365 1 23 1390 1 28 2300 1193 1 06 1228 1 09 1262 1 14 1295 1 19 1327 1 24 1355 1 29 138...

Page 12: ...6 1 10 1130 1 16 1164 1 21 1197 1 26 1231 1 30 2700 1023 1 01 1057 1 08 1091 1 15 1125 1 22 1159 1 27 1192 1 32 1225 1 37 1258 1 41 2800 1053 1 13 1088 1 21 1122 1 27 1155 1 33 1188 1 39 1221 1 43 125...

Page 13: ...1 00 1 10 1 20 1 30 1 40 1 50 1 60 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Kit A04 Kit A08 1900 1126 0 77 1163 0 81 1200 0 85 1237 0 88 1273 0 92 1306 0 96 1339 1 00 1371 1 04...

Page 14: ...0 04 2000 0 05 0 18 0 06 0 05 2200 0 05 0 20 0 08 0 06 2400 0 05 0 22 0 09 0 07 2600 0 06 0 24 0 10 0 08 2800 0 06 0 26 0 11 0 09 3000 0 06 0 28 0 13 0 10 CEILING DIFFUSER AIR THROW DATA Air Volume c...

Page 15: ...ly 21 22 ELECTRIC HEAT DATA Electric Heat Voltage 208 240 208 240 2 Maximum Overcurrent Protection Unit Electric Heat 7 5 kW 60 60 60 70 10 kW 70 80 70 80 3 Minimum Circuit Ampacity Unit Electric Heat...

Page 16: ...70 70 70 70 70 35 35 35 30 30 30 3 Minimum Circuit Ampacity Unit Electric Heat 7 5 kW 61 66 68 73 39 42 41 44 42 45 22 23 24 17 17 18 15 kW 95 105 102 112 58 64 61 67 62 68 33 34 35 26 26 27 2 Maximum...

Page 17: ...70 80 35 35 35 30 30 30 3 Minimum Circuit Ampacity Unit Electric Heat 7 5 kW 67 72 74 80 43 46 45 48 46 49 23 24 24 18 19 19 15 kW 101 111 108 119 62 68 65 71 66 72 34 35 35 27 28 28 2 Maximum Overcur...

Page 18: ...0 175 90 100 90 100 50 50 40 40 3 Minimum Circuit Ampacity Unit Electric Heat 7 5 kW 81 86 51 51 52 52 26 26 20 20 15 kW 114 125 68 74 69 75 37 38 29 29 22 5 kW 148 164 88 97 89 98 48 49 38 39 2 Maxim...

Page 19: ...30 kW 125 125 125 125 70 70 50 50 3 Minimum Circuit Ampacity Unit Electric Heat 7 5 kW 53 56 54 57 28 29 22 23 15 kW 73 79 74 80 40 40 31 32 22 5 kW 92 102 93 102 51 51 40 41 30 kW 112 124 113 125 62...

Page 20: ...700 1 12 6 43 000 2 18 9 64 500 1 25 2 86 000 230 1 6 9 23 500 1 9 2 31 400 1 13 8 47 000 2 20 7 70 700 1 27 5 93 900 240 1 7 5 25 600 1 10 0 34 200 1 15 0 51 200 2 22 5 76 800 1 30 0 102 400 440 1 6...

Page 21: ...ER REVERSING VALVE DEFROST CONTROL BOARD CMC1 FILTERS 024 030 036 048 16 X 20 X 2 060S 20 X 20 X 2 TB1 LOW VOLTAGE TERMINAL BLOCK INDOOR TXV OUTDOOR TXV KHA CONTROL BOX FIGURE 2 T1 CMC1 FAN RELAY K10...

Page 22: ...e con denser fan in response to thermostat demand Single phase units use single pole double break contactors and three phase units use three pole double break con tactors 6 Low Ambient Kit Relay K58 o...

Page 23: ...ns or 14 minutes have passed If the jumper is not re moved until after the additional 5 second period has elapsed the defrost will terminate and the test option will not function again until the jumpe...

Page 24: ...FIGURE 5 EVAPORATOR COIL RETURN AIR SECTION INDOOR BLOWER SECTION ELECTRIC HEAT SECTION INDOOR EXPANSION VALVE REVERSING VALVE CONTROL SECTION COMPRESSOR DRIER PROCESS TUBE used for charging OUTDOOR...

Page 25: ...the freezestat is tripping frequently due to coil icing check the airflow filters and unit charge before allowing unit back in op eration Make sure to eliminate conditions which might pro mote indoor...

Page 26: ...de by changing speed taps Belt drive motors are equipped with sealed ball bearings Direct drive motors are equipped with sleeve bearings Units may be equipped with motors manufactured by various manuf...

Page 27: ...motor pulley Loosen Allen screw and turn adjustable pulley clock wise to increase CFM Turn counterclockwise to de crease CFM See figure 8 Do not exceed minimum and maximum number of pulley turns as sh...

Page 28: ...ngth X See figure 10 2 Apply perpendicular force to center of span X with enough pressure to deflect belt 1 64 for every inch of span length or 1 5mm per 100mm of span length MEASURE BELT TENSION FIGU...

Page 29: ...rmostat is factory set to open at 220_F 6_F 104_C 3 3_C on a temperature rise and can be manually reset when temperature falls be low 160_F 71 0_C See figure 12 for location 4 Terminal Strip TB2 Termi...

Page 30: ...2 4 208 230V 3P 50 A 250V 3 3 460V 25 A 600V 3 3 575V 20 A 600V 3 3 T1EH00225 208 230V 1P 40 A 250V 40A 250V 3 6 208 230V 3P 45 A 250V 45A 250V 3 6 460V 3P 35 A 600V 3 3 575V 3P 30 A 600V 3 3 T1EH0300...

Page 31: ...de energized in the heating mode KHA Units With Optional Electric Heat An increased heating demand W2 will energize elec tric heat Electric heat is also energized during the de frost cycle to maintai...

Page 32: ...some component in the system Correct any system problems before proceeding 6 If discharge pressure is high remove refrigerant from the system If discharge pressure is low reclaim the charge evacuate t...

Page 33: ...th temporary filters which need to be replaced before the building is occupied See table 11 for correct filter size Refer to local codes or appropriate juris diction for approved filters Approved filt...

Page 34: ...URE 14 ENDPLATE IS SECURED TO MULLION 1 Remove screws securing coil end plate to mullion 2 Remove clips connecting coils slabs and separate slabs 3 4 76 102mm 3 Clean coils with detergent or commercia...

Page 35: ...achment FIGURE 15 ASSEMBLED ROOF MOUNTING FRAME FIGURE 16 ROOF MOUNTING FRAME Extends around entire perimeter of unit FIBERGLASS INSULATION Furnished COUNTER FLASHING Field Supplied UNIT BASE BOTTOM R...

Page 36: ...OTOR A7 ENTHALPY SENSOR OTHER SIDE OF PANEL POWER EXHAUST WIRES ONLY CONNECTED WHEN UNIT IS EQUIPPED WITH POWER EXHAUST MIXED AIR SENSOR R1 AND WIRING IN THIS BUNDLE Optional Sensors An optional diffe...

Page 37: ...position can be set lower than traditional minimum air requirements when an IAQ sensor is specified Dampers will open to DCV MAX setting if CO2 is above setpoint to meet traditional ventilation requi...

Page 38: ...mostat During the occupied period dampers will open to DCV MAX when IAQ reading is above setpoint regardless of thermostat demand or outdoor air suitability DCV MAX will NOT override damper full open...

Page 39: ...ir blowers are operating See figure 21 and installation instructions for more detail H Dirty Filter Switch S27 The dirty filter switch senses static pressure increase indi cating a dirty filter condit...

Page 40: ...Page 40 VII WIRING DIAGRAMS SEQUENCE OF OPERATION KHA024 036 048 060 P Voltage 1 2 5 9 3 11 6 7 8 4 4 5 5 8 9 9 10...

Page 41: ...Page 41 KHA036 048 060 Y Voltage 1 2 5 9 3 11 6 7 8 4 4 5 5 8 9 9 10...

Page 42: ...Page 42 KHA036 048 060 G J Voltage 1 2 5 9 3 11 6 7 8 4 4 5 5 7 9 9 10 11...

Page 43: ...d after unit has been in cool ing mode indoor thermostat in HEATING mode will de energize reversing valve L1 8 Heating demand energizes W1 in the thermostat Relay K8 is energized N C K8 1 opens de ene...

Page 44: ...STAT POWER 1 Terminal strip TB1 found in the main control box supplies thermostat components with 24VAC OPERATION 2 TB1 receives data from the electronic thermostat A2 Y1 Y2 W1 W2 G and energizes the...

Page 45: ...ents with 24VAC OPERATION 2 Enthalpy sensor A7 and A62 if differential enthalpy is used communicates to the economizer control module A6 when to power the damper motor B7 3 Economizer control module A...

Page 46: ...Page 46 T1EH 7 5 10 15 22 5 kW P VOLTAGE 1 3 4 5 6 7 2 4 4 4 7 7 7...

Page 47: ...Page 47 T1EHA 7 5 15 22 5kW Y VOLTAGE KHA SERIES UNITS 1 3 4 5 6 7 2 4 7...

Page 48: ...Page 48 T1EHA 7 5 15 22 5kW G J VOLTAGE KHA SERIES UNITS 1 3 4 5 6 7 2 4 7...

Page 49: ...15 1 open de energizing HE1 15kW units K15 1 and K15 2 open de energizing HE2 and HE3 22 5kW units K15 1 K16 1 and K16 2 open de ener gizing HE4 HE5 and HE6 Sequence of Operation T1EH 7 5 15 22 5kW Y...