IV− SYSTEMS SERVICE CHECKS
Refrigerant Charge and Check
WARNING−Do not exceed nameplate charge under any condition.
This unit is factory charged and should require no further
adjustment. If the system requires charge,
reclaim the
charge,
evacuate the system and
add required name-
plate charge.
NOTE − System charging is not recommended below 60
_
F
(15
_
C). In temperatures below 60
_
F (15
_
C) ,
the charge
must
be weighed into the system.
If weighing facilities are not available, or to check the
charge, use the following procedure:
1− Attach gauge manifolds and operate unit in cooling
mode until system stabilizes (approximately five min-
utes).
2− Check each system separately with all stages operat-
ing.
3− Use a thermometer to accurately measure the outdoor
ambient temperature.
4− Apply the outdoor temperature to tables 5 through 9 to
determine normal operating pressures.
5− Compare the normal operating pressures to the pres-
sures obtained from the gauges. Minor variations in
these pressures may be expected due to differences
in installations. Significant differences could mean that
the system is not properly charged or that a problem
exists with some component in the system.
Correct
any system problems before proceeding.
6− If discharge pressure is high, remove refrigerant from
the system. If discharge pressure is low, reclaim the
charge, evacuate the system then add refrigerant.
D
Add or remove charge in increments.
D
Allow the system to stabilize each time refriger-
ant is added or removed.
7− Use the following approach method along with the nor-
mal operating pressures to confirm readings.
TABLE 5
KHA024S NORMAL OPERATING PRESSURES
Outdoor Coil
Entering Air Temp
Dis. + 10 psig
Suct. +5 psig
65
_
F
226
147
75
_
F
258
148
85
_
F
304
151
95
_
F
351
154
105
_
F
402
157
115
_
F
460
160
TABLE 6
KHA030S NORMAL OPERATING PRESSURES
Outdoor Coil
Entering Air Temp
Dis. + 10 psig
Suct. +5 psig
65
_
F
235
145
75
_
F
273
148
85
_
F
316
151
95
_
F
363
153
105
_
F
416
156
115
_
F
476
158
TABLE 7
KHA036S NORMAL OPERATING PRESSURES
Outdoor Coil
Entering Air
Temp
Dis. + 10 psig
Suct. +5 psig
65
_
F
247
140
75
_
F
289
143
85
_
F
331
145
95
_
F
381
148
105
_
F
434
151
115
_
F
492
154
TABLE 8
KHA048S NORMAL OPERATING PRESSURES
Outdoor Coil
Entering Air
Temp
Dis. + 10 psig
Suct. +5 psig
65
_
F
272
139
75
_
F
313
142
85
_
F
359
145
95
_
F
410
148
105
_
F
465
150
115
_
F
529
152
TABLE 9
KHA060S NORMAL OPERATING PRESSURES
Outdoor Coil
Entering Air
Temp
Dis. + 10 psig
Suct. +5 psig
65
_
F
265
136
75
_
F
304
139
85
_
F
348
141
95
_
F
397
144
105
_
F
447
147
115
_
F
507
149
Summary of Contents for KHA SERIES
Page 41: ...Page 41 KHA036 048 060 Y Voltage 1 2 5 9 3 11 6 7 8 4 4 5 5 8 9 9 10...
Page 42: ...Page 42 KHA036 048 060 G J Voltage 1 2 5 9 3 11 6 7 8 4 4 5 5 7 9 9 10 11...
Page 46: ...Page 46 T1EH 7 5 10 15 22 5 kW P VOLTAGE 1 3 4 5 6 7 2 4 4 4 7 7 7...
Page 47: ...Page 47 T1EHA 7 5 15 22 5kW Y VOLTAGE KHA SERIES UNITS 1 3 4 5 6 7 2 4 7...
Page 48: ...Page 48 T1EHA 7 5 15 22 5kW G J VOLTAGE KHA SERIES UNITS 1 3 4 5 6 7 2 4 7...