Page 9
BLOWER DATA - BELT DRIVE - KHA036
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 - Any factory installed options air resistance (economizer, wet coil, etc.).
2 - Any field installed accessories air resistance (duct resistance, diffuser, etc.).
See page 13 for blower motors and drives and page 14 for wet coil and options/accessory air resistance data.
DOWNFLOW
Air
Volume
cfm
External Static - in. w.g.
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Furnished
Kit A01
900
486
0.12
554
0.16
623
0.20
695
0.22
767
0.23
836
0.25
897
0.28
953
0.30
1000
508
0.15
576
0.19
643
0.22
713
0.24
783
0.26
848
0.28
907
0.30
961
0.33
1100
533
0.18
599
0.22
665
0.25
733
0.27
800
0.28
863
0.31
919
0.34
971
0.36
1200
560
0.21
625
0.25
689
0.28
755
0.30
820
0.32
879
0.34
932
0.37
983
0.40
1300
591
0.24
654
0.28
716
0.31
779
0.33
841
0.35
897
0.38
948
0.41
996
0.44
1400
631
0.26
690
0.30
748
0.34
807
0.36
864
0.39
916
0.42
964
0.46
1011
0.49
1500
676
0.28
729
0.33
782
0.36
835
0.40
887
0.43
935
0.47
981
0.50 1028 0.54
Air
Volume
cfm
External Static - in. w.g.
0.90
1.00
1.10
1.20
1.30
1.40
1.50
1.60
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Kit A01
Kit A05
900
1004
0.33 1055 0.35
1106
0.37
1152
0.40
1193
0.43 1232 0.46
1269
0.49 1305 0.52
1000
1011
0.36
1062
0.38
1111
0.41
1157
0.43
1199
0.47 1238 0.50 1276 0.53
1311
0.56
1100
1020
0.39 1070 0.41
1118
0.44
1163
0.47
1206
0.51 1245 0.54 1282 0.58 1318 0.61
1200
1031 0.43 1079 0.45
1127
0.48
1171
0.52 1213 0.55 1252 0.59 1289 0.62 1324 0.66
1300
1044
0.47
1091
0.49
1137
0.53
1181
0.56
1221
0.60 1259 0.64
1296
0.68 1330 0.71
1400
1058 0.51
1105
0.54
1150
0.57
1191
0.61 1231 0.65 1268 0.69 1303 0.73 1337 0.77
1500
1074 0.56
1120
0.59
1163
0.63 1203 0.67
1241
0.71 1277 0.75 1312 0.79 1345 0.82
HORIZONTAL
Air
Volume
cfm
External Static - in. w.g.
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Furnished
Kit A01
900
485
0.11
554
0.14
627
0.16
703
0.18
780
0.21
841
0.23
888
0.27
935
0.30
1000
509
0.13
578
0.16
649
0.19
722
0.21
796
0.23
854
0.26
900
0.29
947
0.33
1100
537
0.16
605
0.19
674
0.21
744
0.24
813
0.26
868
0.29
913
0.33
959
0.36
1200
567
0.19
633
0.22
700
0.24
768
0.27
833
0.30
884
0.33
928
0.37
974
0.40
1300
599
0.22
664
0.25
729
0.28
793
0.30
853
0.33
902
0.37
945
0.41
990
0.44
1400
634
0.26
697
0.29
758
0.31
819
0.34
875
0.38
921
0.42
964
0.46 1008 0.49
1500
669
0.30
730
0.33
789
0.36
846
0.39
897
0.42
941
0.47
983
0.51 1028 0.54
Air
Volume
cfm
External Static - in. w.g.
0.90
1.00
1.10
1.20
1.30
1.40
1.50
1.60
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Kit A01
Kit A05
900
986
0.32 1039 0.35
1090
0.37
1137
0.40
1177
0.43
1214
0.46 1248 0.49 1280 0.51
1000
997
0.35 1048 0.38 1098 0.41
1143
0.44
1184
0.47
1221
0.50 1255 0.53 1287 0.56
1100
1008 0.39 1059 0.41
1107
0.44
1150
0.47
1191
0.51 1228 0.54 1263 0.57 1295 0.60
1200
1022
0.43 1071 0.45
1117
0.48
1160
0.52
1200
0.55 1237 0.59 1271 0.62 1303 0.66
1300
1037 0.47 1085 0.50
1130
0.53
1171
0.57
1210
0.60
1246
0.64 1280 0.68 1312 0.71
1400
1054 0.52
1100
0.54
1144
0.58
1183
0.62
1221
0.66 1256 0.70
1290
0.73 1321 0.77
1500
1073 0.57
1117
0.60
1159
0.64
1197
0.67 1234 0.71 1268 0.75 1301 0.79 1332 0.83
Summary of Contents for KHA SERIES
Page 41: ...Page 41 KHA036 048 060 Y Voltage 1 2 5 9 3 11 6 7 8 4 4 5 5 8 9 9 10...
Page 42: ...Page 42 KHA036 048 060 G J Voltage 1 2 5 9 3 11 6 7 8 4 4 5 5 7 9 9 10 11...
Page 46: ...Page 46 T1EH 7 5 10 15 22 5 kW P VOLTAGE 1 3 4 5 6 7 2 4 4 4 7 7 7...
Page 47: ...Page 47 T1EHA 7 5 15 22 5kW Y VOLTAGE KHA SERIES UNITS 1 3 4 5 6 7 2 4 7...
Page 48: ...Page 48 T1EHA 7 5 15 22 5kW G J VOLTAGE KHA SERIES UNITS 1 3 4 5 6 7 2 4 7...