Page 13
BLOWER DATA - BELT DRIVE - HORIZONTAL - KHA072
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 - Any factory installed options air resistance (economizer, wet coil, etc.).
2 - Any field installed accessories air resistance (duct resistance, diffuser, etc.).
See page 13 for blower motors and drives and page 14 for wet coil and options/accessory air resistance data.
Air
Volume
cfm
External Static - in. w.g.
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Furnished
Kit A04
1900
853
0.41
886
0.46
919
0.50
952
0.55
986
0.60
1021
0.64 1056 0.69
1091
0.73
2000
883
0.48
913
0.53
944
0.57
976
0.62
1009
0.67 1043 0.71 1078 0.76
1112
0.80
2100
906
0.56
936
0.60
967
0.65
999
0.70 1033 0.75 1067 0.79
1101
0.84
1135
0.88
2200
930
0.64
960
0.68
991
0.73
1024
0.78 1058 0.83
1092
0.88
1126
0.92
1160
0.96
2300
954
0.72
985
0.77 1017 0.82 1051 0.87 1085 0.92
1119
0.96
1152
1.00
1186
1.04
2400
981
0.81 1013 0.86
1046
0.91 1079 0.96
1113
1.00
1146
1.05
1180
1.09 1213 1.13
2500
1010
0.91
1042
0.96 1075 1.00
1109
1.05
1142
1.09
1175
1.14 1207 1.18 1239 1.23
2600
1040
1.01 1073 1.05
1106
1.10
1139
1.14
1171
1.19 1203 1.23 1235 1.28
1266
1.33
2700
1072 1.10
1104
1.15
1137
1.20
1169
1.24
1201
1.29 1232 1.34 1263 1.40 1293 1.46
2800
1105
1.21
1137
1.25
1168
1.30
1200
1.35 1231 1.40
1261
1.46
1291
1.52 1321 1.59
2900
1138
1.32
1169
1.37
1200
1.42 1231 1.47
1261
1.53
1291
1.60 1321 1.66 1350 1.73
Air
Volume
cfm
External Static - in. w.g.
0.90
1.00
1.10
1.20
1.30
1.40
1.50
1.60
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Kit A04
Kit A08
1900
1126
0.77
1163
0.81
1200
0.85 1237 0.88 1273 0.92 1306 0.96 1339 1.00 1371 1.04
2000
1148
0.84
1183
0.88
1220
0.92 1257 0.96
1291
1.00 1323 1.04 1354 1.08 1385 1.12
2100
1170
0.92
1206
0.96
1242
1.00 1277 1.04 1310 1.08 1340 1.13 1371 1.17
1401
1.21
2200
1195
1.00 1230 1.04 1265 1.08
1299
1.13 1330 1.18 1359 1.23 1388 1.27 1418 1.31
2300
1220
1.08 1254 1.13 1288 1.17 1320 1.23 1350 1.28 1378 1.34
1406
1.38 1435 1.42
2400
1245 1.18 1278 1.22
1311
1.28 1341 1.33 1370 1.40 1397 1.45 1425 1.50 1454 1.54
2500
1271 1.28 1303 1.33 1334 1.39 1363 1.45 1391 1.52 1418 1.57
1446
1.62 1474 1.66
2600
1297 1.39 1328 1.45 1357 1.52 1385 1.58
1412
1.64 1439 1.70 1467 1.74 1495 1.78
2700
1323 1.52 1353 1.58
1382 1.65
1409
1.72 1435 1.77
1462
1.82
1490
1.86 1517 1.90
2800
1351 1.65 1380 1.72 1407 1.78 1434 1.85
1460
1.90 1486 1.95 1513 1.99 1541 2.02
2900
1379 1.79 1407 1.86 1434 1.92
1460
1.98 1485 2.04
1511
2.08 1538 2.12 1565 2.15
BELT DRIVE KIT SPECIFICATIONS
Model No.
Blower Motor Choice (HP)
Drive Kit No.
RPM Range
Nominal
Maximum
Nominal
Maximum
036
1.5
1.72
2
2.3
A01
673 - 1010 rpm
A05
897 - 1346 rpm
048
1.5
1.72
2
2.3
A02
745 - 1117 rpm
A06
1071 - 1429 rpm
060
1.5
1.72
2
2.3
A03
833 - 1250 rpm
A07
1212 - 1548 rpm
072
1.5
1.72
2
2.3
A04
968 - 1340 rpm
A08
1193 - 1591 rpm
NOTE - Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor hp required. Maximum usable hp of
motors furnished are shown. In Canada, nominal motor hp is also maximum usable motor hp. If motors of comparable hp are used, be sure to keep within the service
factor limitations outlined on the motor nameplate.
Summary of Contents for KHA SERIES
Page 41: ...Page 41 KHA036 048 060 Y Voltage 1 2 5 9 3 11 6 7 8 4 4 5 5 8 9 9 10...
Page 42: ...Page 42 KHA036 048 060 G J Voltage 1 2 5 9 3 11 6 7 8 4 4 5 5 7 9 9 10 11...
Page 46: ...Page 46 T1EH 7 5 10 15 22 5 kW P VOLTAGE 1 3 4 5 6 7 2 4 4 4 7 7 7...
Page 47: ...Page 47 T1EHA 7 5 15 22 5kW Y VOLTAGE KHA SERIES UNITS 1 3 4 5 6 7 2 4 7...
Page 48: ...Page 48 T1EHA 7 5 15 22 5kW G J VOLTAGE KHA SERIES UNITS 1 3 4 5 6 7 2 4 7...