BLOWER DATA - BELT DRIVE - KHA060
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 - Any factory installed options air resistance (economizer, wet coil, etc.).
2 - Any field installed accessories air resistance (duct resistance, diffuser, etc.).
See page 13 for blower motors and drives and page 14 for wet coil and options/accessory air resistance data.
DOWNFLOW
Air
Volume
cfm
External Static - in. w.g.
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Furnished
Kit A03
1600
665
0.30
716
0.34
768
0.38
819
0.41
879
0.44
937
0.46
985
0.49
1022
0.52
1700
723
0.31
768
0.35
814
0.39
860
0.43
910
0.47
959
0.50
1001
0.54 1037 0.58
1800
779
0.32
818
0.37
857
0.41
897
0.46
939
0.50
980
0.55 1018 0.59 1054 0.64
1900
826
0.36
859
0.41
894
0.45
928
0.50
964
0.56
1000
0.61 1036 0.66 1072 0.70
2000
857
0.42
889
0.47
920
0.52
952
0.57
986
0.62
1020
0.68 1055 0.73
1091
0.77
2100
878
0.49
909
0.54
940
0.59
973
0.64
1006
0.70
1041
0.75 1076 0.80
1112
0.85
2200
897
0.55
929
0.61
961
0.66
994
0.72
1028
0.78 1063 0.83
1099
0.89
1134
0.93
2300
918
0.62
950
0.68
983
0.74 1017 0.80
1052
0.86 1087 0.92
1122
0.97
1157
1.02
2400
941
0.70
974
0.77 1008 0.83
1042
0.90
1077
0.96
1111
1.01
1146
1.06
1181
1.11
Air
Volume
cfm
External Static - in. w.g.
0.90
1.00
1.10
1.20
1.30
1.40
1.50
1.60
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Kit A03
Kit A07
1600
1059 0.57 1098 0.61
1138
0.65
1177
0.68
1218
0.71 1257 0.75
1290
0.79 1319 0.83
1700
1074 0.62
1113
0.66
1152
0.70
1190
0.74
1231
0.77 1268 0.80
1299
0.84 1328 0.89
1800
1091
0.68
1129
0.72
1167
0.76 1205 0.80
1244
0.83 1280 0.87 1310 0.91 1338 0.95
1900
1109
0.75
1146
0.79
1183
0.82
1221
0.86
1260
0.90
1294
0.94 1323 0.98 1349 1.02
2000
1128
0.82
1164
0.86
1201
0.89 1239 0.93
1276
0.97 1310 1.01 1336 1.06 1362 1.10
2100
1148
0.89
1185
0.93
1221
0.97 1258 1.01
1294
1.05 1325 1.09 1351 1.14 1376 1.19
2200
1170
0.97
1206
1.01
1242
1.05 1277 1.09
1311
1.14 1341 1.18 1365 1.23 1390 1.28
2300
1193
1.06 1228 1.09
1262
1.14 1295 1.19
1327
1.24 1355 1.29 1380 1.33
1406
1.37
2400
1216
1.15 1250 1.19 1282 1.24 1313 1.30
1343
1.36 1371 1.40 1396 1.44 1423 1.48
HORIZONTAL
Air
Volume
cfm
External Static - in. w.g.
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Furnished
Kit A03
1600
712
0.29
758
0.32
807
0.36
855
0.39
906
0.43
955
0.46
997
0.50 1035 0.54
1700
766
0.32
808
0.36
850
0.40
892
0.44
936
0.47
978
0.51
1016
0.56 1052 0.60
1800
814
0.36
851
0.40
888
0.44
925
0.49
963
0.53
1000
0.57 1035 0.62 1071 0.66
1900
853
0.41
886
0.46
919
0.50
952
0.55
986
0.60
1021
0.64 1056 0.69
1091
0.73
2000
883
0.48
913
0.53
944
0.57
976
0.62
1009
0.67 1043 0.71 1078 0.76
1112
0.80
2100
906
0.56
936
0.60
967
0.65
999
0.70
1033
0.75 1067 0.79
1101
0.84
1135
0.88
2200
930
0.64
960
0.68
991
0.73
1024
0.78
1058
0.83
1092
0.88
1126
0.92
1160
0.96
2300
954
0.72
985
0.77 1017 0.82 1051 0.87
1085
0.92
1119
0.96
1152
1.00
1186
1.04
2400
981
0.81 1013 0.86
1046
0.91 1079 0.96
1113
1.00
1146
1.05
1180
1.09 1213 1.13
Air
Volume
cfm
External Static - in. w.g.
0.90
1.00
1.10
1.20
1.30
1.40
1.50
1.60
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Kit A03
Kit A07
1600
1071 0.58
1109
0.62
1147
0.66
1186
0.69
1225
0.72 1263 0.76
1299
0.80 1334 0.83
1700
1088 0.64
1126
0.68
1164
0.72
1202
0.75
1240
0.78 1276 0.82
1311
0.86 1345 0.90
1800
1107
0.70
1143
0.74
1181
0.78
1219
0.81
1256
0.85
1291
0.89 1324 0.93 1357 0.97
1900
1126
0.77
1163
0.81
1200
0.85 1237 0.88
1273
0.92 1306 0.96 1339 1.00 1371 1.04
2000
1148
0.84
1183
0.88
1220
0.92 1257 0.96
1291
1.00 1323 1.04 1354 1.08 1385 1.12
2100
1170
0.92
1206
0.96
1242
1.00 1277 1.04
1310
1.08 1340 1.13 1371 1.17
1401
1.21
2200
1195
1.00 1230 1.04 1265 1.08
1299
1.13
1330
1.18 1359 1.23 1388 1.27 1418 1.31
2300
1220
1.08 1254 1.13 1288 1.17 1320 1.23
1350
1.28 1378 1.34
1406
1.38 1435 1.42
2400
1245 1.18 1278 1.22
1311
1.28 1341 1.33
1370
1.40 1397 1.45 1425 1.50 1454 1.54
Summary of Contents for KHA SERIES
Page 41: ...Page 41 KHA036 048 060 Y Voltage 1 2 5 9 3 11 6 7 8 4 4 5 5 8 9 9 10...
Page 42: ...Page 42 KHA036 048 060 G J Voltage 1 2 5 9 3 11 6 7 8 4 4 5 5 7 9 9 10 11...
Page 46: ...Page 46 T1EH 7 5 10 15 22 5 kW P VOLTAGE 1 3 4 5 6 7 2 4 4 4 7 7 7...
Page 47: ...Page 47 T1EHA 7 5 15 22 5kW Y VOLTAGE KHA SERIES UNITS 1 3 4 5 6 7 2 4 7...
Page 48: ...Page 48 T1EHA 7 5 15 22 5kW G J VOLTAGE KHA SERIES UNITS 1 3 4 5 6 7 2 4 7...