background image

Page 9

HSXA16 SERIES

Flushing Connections

Low

Pressure

High

Pressure

Vapor Line
Service Valve

EXISTING

INDOOR COIL

HSXA16

UNIT

GAUGE MANIFOLD

Inverted HCFC−22 Cylin-
der
(Contains clean
HCFC−22 to be used for
flushing)

Liquid Line
Service Valve

Inlet

Discharge

Tank Return

Closed

Opened

EXISTING LIQUID LINE

RECOVERY CYLINDER

NOTE − The inverted HCFC−22 cyl-
inder must contain at least the
same amount of refrigerant as was
recovered from the existing sys-
tem.

Figure 10

EXISTING VAPOR LINE

RECOVERY MACHINE

2. Remove the existing outdoor unit. Set the new

HFC−410A unit and follow the brazing connection pro-
cedure which begins on the previous page to make line
set connections.

 DO NOT install metering device at

this time.

Make low voltage and line voltage connections to the
new outdoor unit. 

DO NOT turn on power to the unit

or open the outdoor unit service valves at this
time.

3. Remove the existing refrigerant flow control orifice or

thermostatic expansion valve before continuing with
flushing procedures. The existing devices are not ap-
proved for use with HFC−410A refrigerant and may
prevent proper flushing. Use a field−provided fitting to
reconnect the lines.

IMPORTANT

The line set and indoor coil must be flushed with
at least the same amount of clean refrigerant that
previously charged the system. Check the charge
in the flushing cylinder before proceeding.

4. Remove the pressure tap valve cores from the HSX-

A16 unit’s service valves. Connect an HCFC−22 cylin-
der with clean refrigerant to the vapor service valve.
Connect the HCFC−22 gauge set to the liquid line valve
and connect a recovery machine with an empty recov-
ery tank to the gauge set.

5. Set the recovery machine for liquid recovery and start

the recovery machine. Open the gauge set valves to
allow the recovery machine to pull a vacuum on the ex-
isting system line set and indoor coil.

6. Invert the cylinder of clean HCFC−22 and open its

valve to allow liquid refrigerant to flow into the system

through the vapor line valve. Allow the refrigerant to
pass from the cylinder and through the line set and the
indoor coil before it enters the recovery machine.

7. After all of the liquid refrigerant has been recovered,

switch the recovery machine to vapor recovery so that
all of the HCFC−22 vapor is recovered. Allow the re-
covery machine to pull a vacuum on the system.

NOTE − A single system flush should remove all of the
mineral oil from the existing refrigerant lines and in-
door coil. A second flushing may be done (using clean
refrigerant) if insufficient amounts of mineral oil were
removed during the first flush.

 Each time the system

is flushed, you must allow the recovery machine
to pull a vacuum on the system at the end of the
procedure.

8. Close the valve on the inverted HCFC−22 drum and

the gauge set valves. Pump the remaining refrigerant
out of the recovery machine and turn the machine off.

9. Use dry nitrogen to break the vacuum on the refriger-

ant lines and indoor coil before removing the recovery
machine, gauges and HCFC−22 refrigerant drum. Re-
install pressure tap valve cores into HSXA16 service
valves.

10. Install the field−provided expansion valve (approved

for use with HFC−410A refrigerant) in the liquid line at
the indoor coil.

Manifold Gauge Set

Manifold gauge sets used with systems charged with
HFC−410A refrigerant must be capable of handling the
higher system operating pressures. The gauges should be
rated for use with pressures of 0 − 800 on the high side and
a low side of 30" vacuum to 250 psi with dampened speed
to 500 psi. Gauge hoses must be rated for use at up to 800
psi of pressure with a 4000 psi burst rating.

Summary of Contents for HSXA16 Series

Page 1: ...IONS HSXA16 Series Units CONDENSING UNITS 504 953M 07 06 Supersedes 03 06 Table of Contents HSXA16 Outdoor Unit 1 Shipping Packing List 1 General Information 2 Unit Dimensions 2 Setting The Unit 3 Ele...

Page 2: ...tallation main tenance or repair will expose you to fiberglass wool dust Breathing this may cause lung cancer Fiber glass wool is known to the State of California to cause cancer Fiberglass wool may a...

Page 3: ...lectrical WARNING Electric Shock Hazard Can cause injury or death Unit must be grounded in accordance with national and local codes Line voltage is present at all compo nents when unit is not in opera...

Page 4: ...de wall or where it can be affected by sunlight drafts or vibrations 4 Install low voltage wiring from outdoor to indoor unit and from thermostat to indoor unit NOTE For proper voltages select thermos...

Page 5: ...SXA16 Matched with New Indoor Coil and Line Set If an existing indoor coil that was equipped with an RFCI metering device is being replaced the liquid line must also be replaced prior to the installat...

Page 6: ...eavy nylon wire ties Figure 6 8 feet 8 feet Strap the vapor line to the joist or rafter at 8 ft intervals then strap the liquid line to the vapor line FLOOR JOIST OR ROOF RAFTER Refrigerant Line Sets...

Page 7: ...ends The pipe must remain round do not pinch end of the line 2 Before making line set connections use dry nitrogen to purge the refrigerant piping This will help to prevent oxidation and the introduc...

Page 8: ...system per the in structions below will void the warranty IMPORTANT The Environmental Protection Agency EPA pro hibits the intentional venting of HFC refrigerants during maintenance service repair and...

Page 9: ...d start the recovery machine Open the gauge set valves to allow the recovery machine to pull a vacuum on the ex isting system line set and indoor coil 6 Invert the cylinder of clean HCFC 22 and open i...

Page 10: ...the stem cap Tighten finger tight then torque per table 1 Page 2 To Close Front Seated Service Valves 1 Remove the stem cap with an adjustable wrench 2 Use a service wrench with a hex head extension 3...

Page 11: ...s been add ed fordetection refrigerantrequirements willvarywith line lengths Checkalljoints for leaks Purge drynitro gen and HFC 410A mixture Correct any leaks and re check IMPORTANT Leak detector mus...

Page 12: ...d with a dip tube This system is charged with HFC 410A refrigerant which operates at much higher pressures than HCFC 22 This unit is NOT approved for use with coils which include me tering orifices or...

Page 13: ...d A tem perature pressure chart for HFC 410A refrigerant is provided in table 5 for your convenience Verify ad justed charge using the approach method 4 Use the same digital thermometer you used to ch...

Page 14: ...ervice port and the unit operating stably use a digital ther mometer to record the liquid line temperature 2 At the same time record the liquid line pressure reading 3 Use the temperature pressure cha...

Page 15: ...insufficient cooling the unit should be gauged and refrigerant charge checked Re fer to section on refrigerant charging in this instruction NOTE Outdoor fan motor is prelubricated and sealed No furthe...

Page 16: ...ntinuous in door blower operation regardless of whether the com pressor or furnace is operating This mode is required when constant air circulation or filtering is desired System Switch Set the system...

Reviews: