background image

Page 12

504953M 03/06

WARNING

Danger of Equipment Damage. Avoid deep vacu-
um operation. Do not use compressors to evacu-
ate a system. Extremely low vacuums can cause
internal arcing and compressor failure. Damage
caused by deep vacuum operation will void war-
ranty.

8. Shut off the dry nitrogen cylinder and remove the man-

ifold gauge hose from the cylinder. Open the manifold
gauge valves to release the dry nitrogen from the line
set and indoor unit.

9. Reconnect the manifold gauge to the vacuum pump,

turn the pump on, and continue to evacuate the line set
and indoor unit until the absolute pressure does not
rise above 500 microns (29.9 inches of mercury) within
a 20−minute period after shutting off the vacuum pump
and closing the manifold gauge valves.

10. When the absolute pressure requirement above has

been met, disconnect the manifold hose from the vac-
uum pump and connect it to an upright cylinder of
HFC−410A refrigerant. Open the manifold gauge
valves to break the vacuum from 1 to 2 psig positive
pressure in the line set and indoor unit. Close manifold
gauge valves and shut off the HFC−410A cylinder and
remove the manifold gauge set.

Start−Up

1. Rotate fan to check for frozen bearings or binding.

2. Inspect all factory− and field−installed wiring for loose

connections.

3. After evacuation is complete, open the liquid line and

vapor line service valves to release the refrigerant
charge (contained in outdoor unit) into the system.

4. Replace the stem caps and secure finger tight, then

tighten an additional one-sixth (1/6) of a turn.

5. Check voltage supply at the disconnect switch. The

voltage must be within the range listed on the unit’s
nameplate. If not, do not start the equipment until you
have consulted the power company and the voltage
condition has been corrected.

6. Set the thermostat for a high stage cooling demand

(Y1 and Y2 demand). Turn on power to the indoor
blower and close the outdoor unit disconnect switch to
start the unit.

7. Recheck voltage while the unit is running. Power must

be within range shown on the nameplate.

Refrigerant Charging

IMPORTANT

Some HFC−410A cylinders are equipped with a dip
tube which allows you to draw liquid refrigerant
from the bottom of the cylinder without turning the
cylinder upside−down. The cylinder will be marked
if it is equipped with a dip tube.

This system is charged with HFC−410A refrigerant which
operates at much higher pressures than HCFC−22. This
unit is NOT approved for use with coils which include me-
tering orifices or capillary tubes.

Factory Charge

Units are factory charged with the amount of HFC−410A re-
frigerant indicated on the unit rating plate. This charge is
based on a matching indoor coil and outdoor coil with 15
feet (4.6 m) line set. For varying lengths of line set, refer to
table 3 for refrigerant charge adjustment.

Table 3

Refrigerant Charge per Line Set Lengths

Liquid Line
Set Diameter

Ounces per 5 feet (grams per 1.52 meter)
adjust from 15 ft. (4.57m) line set*

3/8 in. (9.5mm)

3 ounces per 5 feet (85 grams per 1.52 me-
ter)

*Add the amount shown if line length is greater than 15’ (4.57m), sub-
tract the amount shown if less than 15’.

Units Delivered Void of Charge

IMPORTANT

Mineral oils are not compatible with HFC−410A. If
oil must be added, it must be a polyol ester oil.

The compressor is charged with sufficient polyol
ester oil for approved line set lengths.

If the system is void of refrigerant,

 clean the system us-

ing the following procedure:

1. Use dry nitrogen to pressurize the system and check

for leaks. Repair leaks, if possible.

2. Evacuate the system to remove as much of the mois-

ture as possible (triple evacuation).

3. Evacuate the system again. Then, weigh the appropri-

ate amount of HFC−410A refrigerant (listed on unit
nameplate) into the system.

4. Start the unit and monitor the system to determine the

amount of moisture remaining in the oil. Use test kit
10N46 to verify that the moisture content is within the
kit’s dry color range.

5. If the moisture content is not within the dry color range,

add a new filter drier between the liquid valve and the
TXV.

 

You may have to add a new filter drier several

times to achieve the required level of dryness. 

If system dryness is not verified, the compressor
will fail in the future.

Checking Charge

The outdoor unit should be charged during warm weather.
However, applications arise in which charging must occur
in the colder months. 

The method of charging is deter-

mined by the outdoor ambient temperature.

Measure the liquid line temperature and the outdoor ambi-
ent temperature as outlined below:

1. Connect the manifold gauge set to the service valves:

low pressure gauge to 

vapor 

valve service port

high pressure gauge to 

liquid 

valve service port

2. Connect the center manifold hose to an upright cylin-

der of HFC−410A. Close manifold gauge set valves.

Summary of Contents for HSXA16 Series

Page 1: ...IONS HSXA16 Series Units CONDENSING UNITS 504 953M 07 06 Supersedes 03 06 Table of Contents HSXA16 Outdoor Unit 1 Shipping Packing List 1 General Information 2 Unit Dimensions 2 Setting The Unit 3 Ele...

Page 2: ...tallation main tenance or repair will expose you to fiberglass wool dust Breathing this may cause lung cancer Fiber glass wool is known to the State of California to cause cancer Fiberglass wool may a...

Page 3: ...lectrical WARNING Electric Shock Hazard Can cause injury or death Unit must be grounded in accordance with national and local codes Line voltage is present at all compo nents when unit is not in opera...

Page 4: ...de wall or where it can be affected by sunlight drafts or vibrations 4 Install low voltage wiring from outdoor to indoor unit and from thermostat to indoor unit NOTE For proper voltages select thermos...

Page 5: ...SXA16 Matched with New Indoor Coil and Line Set If an existing indoor coil that was equipped with an RFCI metering device is being replaced the liquid line must also be replaced prior to the installat...

Page 6: ...eavy nylon wire ties Figure 6 8 feet 8 feet Strap the vapor line to the joist or rafter at 8 ft intervals then strap the liquid line to the vapor line FLOOR JOIST OR ROOF RAFTER Refrigerant Line Sets...

Page 7: ...ends The pipe must remain round do not pinch end of the line 2 Before making line set connections use dry nitrogen to purge the refrigerant piping This will help to prevent oxidation and the introduc...

Page 8: ...system per the in structions below will void the warranty IMPORTANT The Environmental Protection Agency EPA pro hibits the intentional venting of HFC refrigerants during maintenance service repair and...

Page 9: ...d start the recovery machine Open the gauge set valves to allow the recovery machine to pull a vacuum on the ex isting system line set and indoor coil 6 Invert the cylinder of clean HCFC 22 and open i...

Page 10: ...the stem cap Tighten finger tight then torque per table 1 Page 2 To Close Front Seated Service Valves 1 Remove the stem cap with an adjustable wrench 2 Use a service wrench with a hex head extension 3...

Page 11: ...s been add ed fordetection refrigerantrequirements willvarywith line lengths Checkalljoints for leaks Purge drynitro gen and HFC 410A mixture Correct any leaks and re check IMPORTANT Leak detector mus...

Page 12: ...d with a dip tube This system is charged with HFC 410A refrigerant which operates at much higher pressures than HCFC 22 This unit is NOT approved for use with coils which include me tering orifices or...

Page 13: ...d A tem perature pressure chart for HFC 410A refrigerant is provided in table 5 for your convenience Verify ad justed charge using the approach method 4 Use the same digital thermometer you used to ch...

Page 14: ...ervice port and the unit operating stably use a digital ther mometer to record the liquid line temperature 2 At the same time record the liquid line pressure reading 3 Use the temperature pressure cha...

Page 15: ...insufficient cooling the unit should be gauged and refrigerant charge checked Re fer to section on refrigerant charging in this instruction NOTE Outdoor fan motor is prelubricated and sealed No furthe...

Page 16: ...ntinuous in door blower operation regardless of whether the com pressor or furnace is operating This mode is required when constant air circulation or filtering is desired System Switch Set the system...

Reviews: