background image

Page 8

504953M 03/06

Refrigerant Metering Device

HSXA16 units are used in thermostatic expansion valve
(TXV) systems only. See the Lennox Engineering Hand-
book for approved TXV match-ups and application infor-
mation.

Check expansion valves equipped with Chatleff fittings are
available from Lennox. Refer to the Engineering Hand-
book for applicable expansion valves for use with specific
match-ups.

If you install a thermostatic expansion valve (TXV)
with an indoor coil that includes a fixed orifice, re-
move the orifice before installing the TXV. 

See figure 9

for installation of the TXV.

EXPANSION VALVE &
O−RING (See NOTE)

Metering Device Installation

STRAINER

LIQUID LINE
STUB

DISTRIBUTOR

Figure 9

O−RING

NOTE − If necessary, remove HCFC−22 flow control device (fixed
orifice/thermostatic expansion valve) from existing line set before
installing HFC−410A approved expansion valve and o−ring.

Flushing Existing Line Set & Indoor Coil

WARNING

Danger of fire. Bleeding the refriger-
ant charge from only the high side
may result in the low side shell and
suction tubing being pressurized. Ap-
plication of a brazing torch while
pressurized may result in ignition of
the refrigerant and oil mixture − check
the high and low pressures before un-
brazing.

NOTE − If the indoor unit line and set is new, skip this sec-
tion and go on to the Manifold Gauge Set section.

IMPORTANT

If this unit is being matched with an approved line
set or indoor coil which was previously charged
with mineral oil, or if it is being matched with a coil
which was manufactured before January of 1999,
the coil and line set must be flushed prior to instal-
lation. Take care to empty all existing traps. Polyol
ester (POE) oils are used in Lennox units charged
with HFC−410A refrigerant. Residual mineral oil
can act as an insulator, preventing proper heat
transfer. It can also clog the expansion device, and
reduce the system performance and capacity.
Failure to properly flush the system per the in-
structions below will void the warranty.

IMPORTANT

The Environmental Protection Agency (EPA) pro-
hibits the intentional venting of HFC refrigerants
during maintenance, service, repair  and disposal of
appliance. Approved methods of recovery, recycl-
ing or reclaiming must be followed.

CAUTION

This procedure should not be performed on sys-
tems which contain contaminants (Example: com-
pressor burn out).

Required Equipment

You will need the following equipment in order to flush the
existing line set and indoor coil: two clean HCFC−22 recov-
ery bottles, an oilless recovery machine with a pump down
feature, and two sets of gauges (one for use with HCFC−22
and one for use with the HFC−410A).

Flushing Procedure

1. Remove existing HCFC−22 refrigerant using the ap-

propriate procedure below (see figure 10):

If the existing outdoor unit is not equipped with
shut−off valves, or if the unit is not operational
AND you plan to use the existing HCFC−22 refrig-
erant to flush the system −

Disconnect all power to the existing outdoor unit.

Connect to the existing unit, a 

clean

 recovery cyl-

inder and the recovery machine according to the
instructions provided with the recovery machine.

Remove all HCFC−22 refrigerant from the existing
system. Check gauges after shutdown to confirm
that the entire system is completely void of refrig-
erant.

Disconnect the liquid and vapor lines from the ex-
isting outdoor unit.

If the existing outdoor unit is equipped with
manual shut−off valves AND you plan to use NEW
HCFC−22 refrigerant to flush the system 

Start the existing HCFC−22 system in the cooling
mode and close the liquid line valve.

Pump all of the existing HCFC−22 refrigerant back
into the outdoor unit. (It may be necessary to by-
pass the low pressure switches to ensure com-
plete refrigerant evacuation.)

When the low side system pressures reach 0 psig,
close the vapor line valve.

Disconnect all power to the existing outdoor unit.
Check gauges after shutdown to confirm that the
valves are not allowing refrigerant to flow back into
the low side of the system.

Disconnect the liquid and vapor lines from the ex-
isting outdoor unit.

Summary of Contents for HSXA16 Series

Page 1: ...IONS HSXA16 Series Units CONDENSING UNITS 504 953M 07 06 Supersedes 03 06 Table of Contents HSXA16 Outdoor Unit 1 Shipping Packing List 1 General Information 2 Unit Dimensions 2 Setting The Unit 3 Ele...

Page 2: ...tallation main tenance or repair will expose you to fiberglass wool dust Breathing this may cause lung cancer Fiber glass wool is known to the State of California to cause cancer Fiberglass wool may a...

Page 3: ...lectrical WARNING Electric Shock Hazard Can cause injury or death Unit must be grounded in accordance with national and local codes Line voltage is present at all compo nents when unit is not in opera...

Page 4: ...de wall or where it can be affected by sunlight drafts or vibrations 4 Install low voltage wiring from outdoor to indoor unit and from thermostat to indoor unit NOTE For proper voltages select thermos...

Page 5: ...SXA16 Matched with New Indoor Coil and Line Set If an existing indoor coil that was equipped with an RFCI metering device is being replaced the liquid line must also be replaced prior to the installat...

Page 6: ...eavy nylon wire ties Figure 6 8 feet 8 feet Strap the vapor line to the joist or rafter at 8 ft intervals then strap the liquid line to the vapor line FLOOR JOIST OR ROOF RAFTER Refrigerant Line Sets...

Page 7: ...ends The pipe must remain round do not pinch end of the line 2 Before making line set connections use dry nitrogen to purge the refrigerant piping This will help to prevent oxidation and the introduc...

Page 8: ...system per the in structions below will void the warranty IMPORTANT The Environmental Protection Agency EPA pro hibits the intentional venting of HFC refrigerants during maintenance service repair and...

Page 9: ...d start the recovery machine Open the gauge set valves to allow the recovery machine to pull a vacuum on the ex isting system line set and indoor coil 6 Invert the cylinder of clean HCFC 22 and open i...

Page 10: ...the stem cap Tighten finger tight then torque per table 1 Page 2 To Close Front Seated Service Valves 1 Remove the stem cap with an adjustable wrench 2 Use a service wrench with a hex head extension 3...

Page 11: ...s been add ed fordetection refrigerantrequirements willvarywith line lengths Checkalljoints for leaks Purge drynitro gen and HFC 410A mixture Correct any leaks and re check IMPORTANT Leak detector mus...

Page 12: ...d with a dip tube This system is charged with HFC 410A refrigerant which operates at much higher pressures than HCFC 22 This unit is NOT approved for use with coils which include me tering orifices or...

Page 13: ...d A tem perature pressure chart for HFC 410A refrigerant is provided in table 5 for your convenience Verify ad justed charge using the approach method 4 Use the same digital thermometer you used to ch...

Page 14: ...ervice port and the unit operating stably use a digital ther mometer to record the liquid line temperature 2 At the same time record the liquid line pressure reading 3 Use the temperature pressure cha...

Page 15: ...insufficient cooling the unit should be gauged and refrigerant charge checked Re fer to section on refrigerant charging in this instruction NOTE Outdoor fan motor is prelubricated and sealed No furthe...

Page 16: ...ntinuous in door blower operation regardless of whether the com pressor or furnace is operating This mode is required when constant air circulation or filtering is desired System Switch Set the system...

Reviews: