background image

Page 11

HSXA16 SERIES

Leak Testing

After the line set has been connected to the indoor and out-
door units, the line set connections and indoor unit must be
checked for leaks.

WARNING

Refrigerant can be harmful if it is inhaled. Refriger-
ant must be used and recovered responsibly.

Failure to follow this warning may result in personal
injury or death.

WARNING

Fire, Explosion and Personal Safety
Hazard.

Failure to follow this warning could
result in damage, personal injury or
death.

Never use oxygen to pressurize or
purge refrigeration lines. Oxygen,
when exposed to a spark or open
flame, can cause damage by fire and/
or an explosion, that could result in
personal injury or death.

WARNING

When using a high pressure gas such
as dry nitrogen to pressurize a refrig-
eration or air conditioning system,
use a regulator that can control the
pressure down to 1 or 2 psig (6.9 to
13.8 kPa).

Using an Electronic Leak Detector

1. Connect the high pressure hose of the manifold gauge

set to the vapor valve service port. 

(Normally, the high

pressure hose is connected to the liquid line port, how-
ever, connecting it to the vapor port helps to protect the
manifold gauge set from damage caused by high pres-
sure.)

2. With both manifold valves closed, connect the cylinder

of HFC−410A refrigerant. Open the valve on the
HFC−410A cylinder (vapor only).

3. Open the high pressure side of the manifold to allow

HFC−410A into the line set and indoor unit. Weigh in
a trace amount of HFC−410A.

 [A trace amount is a

maximum of 2 ounces (57 g) refrigerant or 3 pounds
(31 kPa) pressure.] 

Close the valve on the HFC−410A

cylinder and the valve on the high pressure side of the
manifold gauge set. Disconnect HFC−410A cylinder.

4. Connect a cylinder of dry nitrogen with a pressure reg-

ulating valve to the center port of the manifold gauge
set.

5. Adjust dry nitrogen pressure to 150 psig (1034 kPa).

Open the valve on the high side of the manifold gauge

set in order to pressurize the line set and the indoor
coil.

6. After a few minutes, open a refrigerant port to check

that an adequate amount of refrigerant has been add-
ed for detection (refrigerant requirements will vary with
line lengths). Check all joints for leaks. Purge dry nitro-
gen and HFC−410A mixture. Correct any leaks and re-
check.

IMPORTANT

Leak detector must be capable of sensing HFC re-
frigerant.

Evacuation

Evacuating the system of noncondensables is critical for
proper operation of the unit. Noncondensables are defined
as any gas that will not condense under temperatures and
pressures present during operation of an air conditioning
system. Noncondensables and water vapor combine with
refrigerant to produce substances that corrode copper pip-
ing and compressor parts.

IMPORTANT

Use a thermocouple or thermistor electronic vacuum
gauge that is calibrated in microns. Use an instrument
that reads from 50 microns to at least 23,000 microns.

1. Connect manifold gauge set to the service valve ports:

low pressure gauge to 

vapor 

line service valve

high pressure gauge to 

liquid 

line service valve

2. Close manifold gauge set valves. Connect the center

manifold hose to an upright cylinder of HFC−410A .

3. Connect micron gauge.
4. Connect the vacuum pump (with vacuum gauge) to

the center port of the manifold gauge set.

5. Open both manifold valves and start the vacuum

pump.

6. Evacuate the line set and indoor unit to an 

absolute

pressure

 of 23,000 microns (29.01 inches of mercu-

ry). During the early stages of evacuation, it is desir-
able to close the manifold gauge valve at least once to
determine if there is a rapid rise in 

absolute pressure

.

A rapid rise in pressure indicates a relatively large
leak. If this occurs, repeat the leak testing procedure.

NOTE − The term 

absolute pressure

 means the total

actual pressure within a given volume or system,
above the absolute zero of pressure. Absolute pres-
sure in a vacuum is equal to atmospheric pressure mi-
nus vacuum pressure.

7. When the absolute pressure reaches 23,000 microns

(29.01 inches of mercury), close the manifold gauge
valves, turn off the vacuum pump and disconnect the
manifold gauge center port hose from vacuum pump.
Attach the manifold center port hose to a dry nitrogen
cylinder with pressure regulator set to 150 psig (1034
kPa) and purge the hose. Open the manifold gauge
valves to break the vacuum in the line set and indoor
unit. Close the manifold gauge valves.

Summary of Contents for HSXA16 Series

Page 1: ...IONS HSXA16 Series Units CONDENSING UNITS 504 953M 07 06 Supersedes 03 06 Table of Contents HSXA16 Outdoor Unit 1 Shipping Packing List 1 General Information 2 Unit Dimensions 2 Setting The Unit 3 Ele...

Page 2: ...tallation main tenance or repair will expose you to fiberglass wool dust Breathing this may cause lung cancer Fiber glass wool is known to the State of California to cause cancer Fiberglass wool may a...

Page 3: ...lectrical WARNING Electric Shock Hazard Can cause injury or death Unit must be grounded in accordance with national and local codes Line voltage is present at all compo nents when unit is not in opera...

Page 4: ...de wall or where it can be affected by sunlight drafts or vibrations 4 Install low voltage wiring from outdoor to indoor unit and from thermostat to indoor unit NOTE For proper voltages select thermos...

Page 5: ...SXA16 Matched with New Indoor Coil and Line Set If an existing indoor coil that was equipped with an RFCI metering device is being replaced the liquid line must also be replaced prior to the installat...

Page 6: ...eavy nylon wire ties Figure 6 8 feet 8 feet Strap the vapor line to the joist or rafter at 8 ft intervals then strap the liquid line to the vapor line FLOOR JOIST OR ROOF RAFTER Refrigerant Line Sets...

Page 7: ...ends The pipe must remain round do not pinch end of the line 2 Before making line set connections use dry nitrogen to purge the refrigerant piping This will help to prevent oxidation and the introduc...

Page 8: ...system per the in structions below will void the warranty IMPORTANT The Environmental Protection Agency EPA pro hibits the intentional venting of HFC refrigerants during maintenance service repair and...

Page 9: ...d start the recovery machine Open the gauge set valves to allow the recovery machine to pull a vacuum on the ex isting system line set and indoor coil 6 Invert the cylinder of clean HCFC 22 and open i...

Page 10: ...the stem cap Tighten finger tight then torque per table 1 Page 2 To Close Front Seated Service Valves 1 Remove the stem cap with an adjustable wrench 2 Use a service wrench with a hex head extension 3...

Page 11: ...s been add ed fordetection refrigerantrequirements willvarywith line lengths Checkalljoints for leaks Purge drynitro gen and HFC 410A mixture Correct any leaks and re check IMPORTANT Leak detector mus...

Page 12: ...d with a dip tube This system is charged with HFC 410A refrigerant which operates at much higher pressures than HCFC 22 This unit is NOT approved for use with coils which include me tering orifices or...

Page 13: ...d A tem perature pressure chart for HFC 410A refrigerant is provided in table 5 for your convenience Verify ad justed charge using the approach method 4 Use the same digital thermometer you used to ch...

Page 14: ...ervice port and the unit operating stably use a digital ther mometer to record the liquid line temperature 2 At the same time record the liquid line pressure reading 3 Use the temperature pressure cha...

Page 15: ...insufficient cooling the unit should be gauged and refrigerant charge checked Re fer to section on refrigerant charging in this instruction NOTE Outdoor fan motor is prelubricated and sealed No furthe...

Page 16: ...ntinuous in door blower operation regardless of whether the com pressor or furnace is operating This mode is required when constant air circulation or filtering is desired System Switch Set the system...

Reviews: