background image

Page 12

 XP14 SERIES

A -

Run 24VAC control wires through cutout with grommet.

B -

Run 24VAC control wires through wire tie.

C -

Make 24VAC control wire connections using field provided
wire nuts.

D -

Tighten wire tie to security 24V control wiring.

HIGH VOLTAGE FIELD WIRING

LOW VOLTAGE (24V) FIELD WIRING

FACTORY WIRING

CUTOUT WITH

GROMMET

NOTE -

 FOR PROPER VOLTAGES, SELECT THERMOSTAT WIRE (CONTROL

WIRES) GAUGE PER TABLE ABOVE.

WIRE RUN LENGTH

AWG#   INSULATION TYPE

LESS THAN 100' (30 METERS)

18      TEMPERATURE RATING

MORE THAN 100' (30 METERS)

16       35ºC MINIMUM.

WIRE NUTS

BLACK

24V CONTROL WIRES

YELLOW

TIGHTEN WIRE TIE

Unit Low Voltage Wiring

NOTE -

 DO NOT BUNDLE ANY EXCESS 24VAC CONTROL WIRES INSIDE

CONTROL BOX.

NOTE -

 WIRE TIE PROVIDES LOW VOLTAGE WIRE STRAIN RELIEF AND

MAINTAINS SEPARATION OF FIELD-INSTALLED LOW AND HIGH VOLTAGE
CIRCUITS.

A

B

C

D

3

FIGURE 13

Typical 24VAC Control Wiring Diagrams (Field Installed)

THERMOSTAT

INDOOR UNIT

R

C

W1

Y1

O

G

R

C

W1

W2

W3

G

R

C

W1

Y1

O

COMMON

1ST‐STAGE

AUXILIARY

HEAT

INDOOR BLOWER

COMPRESSOR

24V POWER

REVERSING VALVE

COMMON

1ST‐STAGE

AUXILIARY

HEAT

24V POWER

(SOME CONNECTIONS MAY NOT APPLY. REFER
TO SPECIFIC THERMOSTAT AND INDOOR UNIT.)

OUTDOOR UNIT

R

C

W1

Y1

O

G

R

C

W1

W2

W3

G

E

R

C

W1

Y1

O

EMERGENCY

HEAT

EMERGENCY

HEAT RELAY

OUTDOOR
THERMOSTAT

THERMOSTAT

INDOOR UNIT

OUTDOOR UNIT

COMMON

1ST‐STAGE

AUXILIARY

HEAT

INDOOR BLOWER

COMPRESSOR

COMMON

1ST‐STAGE

AUXILIARY

HEAT

24V POWER

24V POWER

(SOME CONNECTIONS MAY NOT APPLY. REFER TO
SPECIFIC THERMOSTAT AND INDOOR UNIT.)

REVERSING VALVE

WARNING! - ELECTRIC SHOCK HAZARD. Can cause INJURY
or DEATH. Unit must be grounded in accordance with national
and local codes.

NOTE -

 For use with copper conductors only. Refer to unit rating

plate for minimum circuit ampacity and maximum over‐current
protection size.

FIGURE 14

Summary of Contents for Elite XP14-018-230

Page 1: ...stment alteration service or maintenance can cause property damage personal in jury or loss of life Installation and service must be performed by a li censed professional installer or equivalent or se...

Page 2: ...Unit Placement NOTICE Roof Damage This system contains both refrigerant and oil Some rubber roofing material may absorb oil causing the rubber to degrade Failure to follow this notice could result in...

Page 3: ...or expansion valve approved for use with HFC 410A refrigerant must be ordered separately and installed prior to operating the system LEG DETAIL BASE 2 50 8MM SCH 40 FEMALE THREADED ADAPTER ELEVATED SL...

Page 4: ...ated NOTE Some applications may require a field provided 7 8 to 1 1 8 adapter NOTE When installing refrigerant lines longer than 50 feet refer to the Refrigerant Piping Design and Fabrica tion Guideli...

Page 5: ...eflon rings H Use a field provided fitting to temporarily reconnect the liquid line to the indoor unit s liquid line orifice housing LOW HIGH EXISTING INDOOR UNIT GAUGE MANIFOLD CYLINDER CONTAINING CL...

Page 6: ...r the ends The pipe must remain round Do not crimp end of the line Remove service cap and core from both the vapor and liquid line service ports 1 2 LIQUID LINE SERVICE VALVE SERVICE PORT CORE SERVICE...

Page 7: ...oths WHEN BRAZING LINE SET TO SERVICE VALVES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WRAP SERVICE VALVES To help protect service valve seals during brazing wrap water saturated...

Page 8: ...mounted external to the coil casing sensing bulb installation for bulb positioning STUB END TEFLON RING LIQUID LINE ASSEMBLY WITH BRASS NUT DISTRIBUTOR ASSEMBLY 3 Install one of the provided Teflon r...

Page 9: ...e to 150 psig 1034 kPa Open the valve on the high side of the manifold gauge set in order to pressurize the line set and the indoor unit E After a few minutes open one of the service valve ports and v...

Page 10: ...pump and closing the manifold gauge valves F When the absolute pressure requirement above has been met disconnect the manifold hose from the vacuum pump and connect it to a cylinder of HFC 410A positi...

Page 11: ...ith this product CAUTION Failure to use properly sized wiring and circuit breaker may result in property damage Size wiring and circuit breaker s per Product Specifications bulletin EHB and unit ratin...

Page 12: ...AND HIGH VOLTAGE CIRCUITS A B C D 3 FIGURE 13 Typical 24VAC Control Wiring Diagrams Field Installed THERMOSTAT INDOOR UNIT R C W1 Y1 O G R C W1 W2 W3 G R C W1 Y1 O COMMON 1ST STAGE AUXILIARY HEAT IND...

Page 13: ...rvice port which has a factory installed valve stem Figures 15 and 16 provide information on how to access and operate both angle and ball type service valves Torque Requirements When servicing or rep...

Page 14: ...clockwise ACCESS SERVICE PORT FIGURE 17 Checking Refrigerant Charge The XP14 unit is factory charged with enough HFC 410A refrigerant to accommodate a 15 foot length of refrigerant piping Charge shoul...

Page 15: ...ed the unit will remain in forced defrost mode until defrost thermostat opens or termin ated on maximum defrost time 14 minutes If the jumper is not removed once 5 seconds has elapsed 7 seconds total...

Page 16: ...the snow level below the louvered panels NOTE The filter and all access panels must be in place any time the unit is in operation If you are unsure about the filter required for your system call your...

Page 17: ...con firm that pipes are not rubbing copper to copper Also ensure that refrigerant pipes are not being af fected by indoor air contamination Check condition of insulation on the refrigerant lines Repai...

Page 18: ...e Supply Air Temperature Ambient Temperature Return Air Temperature System Refrigerant Charge Refer to manufacturer s information on unit or installation instructions for required subcooling and appro...

Reviews: