NOTE: DIAGRAMS AND ILLUSTRATIONS ARE REPRESENTATIVE AND ARE NOT DRAWN TO SCALE.

6

Distance from Unit Base

to Bottom of Recessed 

Shelf (see table)

Do NOT insulate space

between appliance and

area above it.

~

MINIMUM CLEARANCES  

TO COMBUSTIBLES

The appliance is approved with zero clearance 

to combustible materials on both sides (see 

Figure 6-1

), 

with the following exceptions

:

• When unit is installed with one side flush 

with a wall, the wall on the other side of unit 

must not extend beyond unit front edge.

• When unit is recessed, the side walls sur-

rounding the unit must not extend beyond 

unit front edge (see 

Figure 6-4

).

LENNOX HEARTH PRODUCTS  •  ELITE LINEAR VIEW DIRECT-VENT GAS FIREPLACE (MODELS LDV42, LDV54)  •  INSTALLATION INSTRUCTIONS

CLEARANCES

5 (127)

8-1/4

(209)

14

(356)

12 (305)

17 (431)

Figure 6-4: Minimum Clearances to Unprotected Side Wall

Top View of 

fireplace

 45

o

Protected wall shown in white

Inches (millimeters)

Combustible materials may 

project  beyond  one  side 

of  the  fireplace  opening 

as  long  as  they  are  kept 

within  the  shaded  areas 

illustrated  here.

Combustible Materials 

Allowed In Shaded Area 

“Safe Zone”
Combustible Walls 

shown in dark gray

At 14" minimum 

side wall clearance, 

a combustible wall 

can project to any 

length.

At 8-1/4" side 

wall clearance, a 

combustible wall 

can project 12"

MANTELS

Non-Combustible Mantels

Mantels  constructed  of  non-combustible 

material may be installed at any height above 

the appliance opening; however, do NOT allow 

anything  to  hang  below  the  top  edge  of  the 

fireplace door.

Combustible Mantels

Clearances  to  combustible  mantels  vary  ac-

cording to mantel depth. 

See Figure 6-3 for 

details.

  

Note:

 Use high-temperature paint (rated 175°F 

or higher) on the underside of the mantel.

UNPROTECTED SIDE WALL

See 

Figure  6-4 

for  minimum  clearances  to 

unprotected side walls.

fINISh/SURROUND

 IMPORTANT! The factory- supplied 

non-com bustible fiber board MUST be 

installed around the fireplace opening. 

See 

Page 32

 for details.

MINIMUM CLEARANCES  

TO COMBUSTIBLES 

Back

1/2" (12.7 mm) to unit
0" (0 mm) to spacers

Sides

1/2" (12.7 mm) to unit
0" (0 mm) to spacers 

Top Spacers

0" (0 mm)

floor

0" (0 mm)

Unit Bottom to Ceiling 65" (1651 mm)
Vent Pipe

Top: 3" (76 mm) 

Sides: 1" (25.4 mm)

Bottom: 1" (25.4 mm) 

SERVICE CLEARANCES

front

36

"

 (152.4 mm)

 

3"  (76  mm)  above  any  horizontal/

inclined vent component.

 

See 

"Framing the Fireplace," Page 7,

 

for clearance requirements to nailing 

flanges on unit sides and any adjacent 

screw heads.

RECESSED ShELf

These  direct-vent  appliances  are  suitable  for 

installations with a recessed shelf above the 

fireplace. See 

Figure 6-2

 for clearances from 

the  appliance  base  to  the  underside  of  any 

combustible material used to construct such 

a shelf.

Note:
•  Do NOT insulate the space between 

the appliance and the area above it. 

•  This is a heat-producing appliance. 

Objects  placed  above  the  unit  are 

exposed to elevated temperatures.

18 (457)

2

(51)

4

(102)

6

(152)

8

(203)

10

(254)

12

(305)

20 (508)

24 (610)

28 (711)

26 (660)

22 (559)

Top of 

Appliance

inches 

(millimeters)

Mantel Depth

Figure 6-3: Minimum Clearances to Combustible Mantel

header

MIN. CLEARANCE TO  

COMBUSTIBLE RECESSED ShELf

fireplace  

Model

Secure Vent

in (mm)

Secure flex 

(elbow)   

in (mm)

LDV42

51-1/4 (1299)

53 (1345)

LDV54

55 (1400)*

56-3/4 (1441)*

*Includes 3" clearance to combustibles required 

above vent components.

Figure 6-2: Minimum Clearance to 

Combustible Recessed Shelf

6" straight  

vent section  

required  

before 90°

elbow.

hEARTh ExTENSION

A  hearth  extension  is  not  required  with  this 

appliance. Any installed hearth extension would 

be for appearance only and does not have to 

conform to standard hearth extension installa-

tion requirements.

Figure 6-1

Summary of Contents for ELITE LDV42N

Page 1: ...is or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from...

Page 2: ...allation Instructions this manual Care and Operation Instructions Safety in Operation Warnings Warranty Vent restrictor assembly Remote control kit handheld remote control transmitter remote control r...

Page 3: ...proper installation or use of this appliance can cause serious injury or death from fire burns explosion or carbon monoxide poisoning Do not attempt to alter or modify the construction of the applianc...

Page 4: ...e ON OFF function only Efficiencies Fireplace Model Natural Gas Propane AFUE EnerGuide P4 AFUE EnerGuide P4 ldv42 66 7 54 2 69 6 59 4 ldv54 71 9 63 2 72 1 65 5 AFUE Annual Fuel Utilization Efficiency...

Page 5: ...with certain vent runs 16 Reinstall baffle if removed for vent restrictor installation 28 Install media 27 Install glass door 29 12 Verify appliance operation 30 Lighting instructions 31 Air shutter a...

Page 6: ...of the mantel UNPROTECTED Side Wall See Figure 6 4 for minimum clearances to unprotected side walls FINISH SURROUND IMPORTANT The factory supplied non com bustible fiber board MUST be installed aroun...

Page 7: ...fireplace the nailing flanges MUST be adjusted according to finish cleanface or surround and wall finish material thickness This is critical to ensure proper fireplace location especially if installi...

Page 8: ...or dimension information only Fireplace must be adequately framed and supp A Required frame opening width 1 2 of A horizontal centerline of fireplace and vent framing opening B Required frame opening...

Page 9: ...vertical position for cleanface finish and at 1 2 wall finish depth Cleanface Finish Nailing Flange Settings 1 Leave vertical position of nailing flanges at factory setting see Figure 9 1 DETAIL A 2 I...

Page 10: ...opane tank smaller than 100 lbs may create pressure loss and insufficient fuel delivery which can cause sooting severe delayed ignition or other malfunctions ref NPFA 58 Any damage as a result of insu...

Page 11: ...alified installer approved and or licensed as required by the locality In the Commonwealth of Massachusetts installation must be performed by a licensed plumber or gas fitter Figure 11 3 Gas Stub 1 2...

Page 12: ...t all factory and field connections for gas leaks Note Even though soapy water is an effective leak test solution it is NOT recommended because soap residue can corrode pipes and fittings over time 1...

Page 13: ...against the adjoining section until fully engaged 3 Twist the section being attached CLOCK WISE running the dimples down and along the channels until seated at the ends of the channels The sections ar...

Page 14: ...L 2 1 4 2 1 0 1 2 1 2 2 2 1 4 3 2 1 6 4 t n e V f o t h g i e H s n o i t c e S t n e V f o r e b m u N s e h c n i t f 6 7 2 3 2 0 0 0 8 0 8 9 7 2 5 2 3 2 0 0 0 0 6 6 5 0 8 2 5 7 3 3 2 1 0 0 8 0 9 5...

Page 15: ...bove appliance vent outlet VENT RUN SUPPORT REQUIREMENTS Supporting Vertical Vent Runs Note Proper venting support is very important NEVER use the fireplace to support the weight of the venting Suppor...

Page 16: ...o slide the assembly up into the vent collar as shown in Figure 16 3 The vent restrictor is held in place by fric tion only The entire vent restrictor assembly must be up inside the vent collar with n...

Page 17: ...ofMill PacBlack 700 F high temperature sealant Catalog No 10K81 to the inner adaptor collar approximately 1 2 inch from the end 3 Pull and extend the inner flexible vent pipe 4 Slidetheinnerflexpipeov...

Page 18: ...provided Vent Restrictor if re quired see Page 16 A 90 elbow may NOT be attached directly to the appliance collar A minimum of 6 pipe must be used between the fireplace collar and a 90 elbow For more...

Page 19: ...screw c Apply non combustible caulking silicone caulking is acceptable around entire cir cumference to ensure a water tight seal LENNOX HEARTH PRODUCTS ELITE LINEAR VIEW DIRECT VENT GAS FIREPLACE MODE...

Page 20: ...rtical Firestop Spacer must be used anywhere vent pipe passes through a combustible floor or ceiling Horizontal Firestop Spacer must be used anywhere vent pipe passes through a combustible wall For fu...

Page 21: ...termination must have a minimum 6 152 mm clearance to any overhead combustible projection less than or equal to 2 1 2 64 mm For projections greater than 2 1 2 64 mm see Figure 21 1 For additional vent...

Page 22: ...U S 12 in Canada V L B J X V A G Inside Corner Detail B C C C 18 Ventilated Soffit Horizontal Termination Detail D Exterior Wall 6 Inside Corner See Item D in the Text Below V P V O N N Q NOTE Local...

Page 23: ...Attach termination adaptor See Figure 23 2 Attach the termination adaptor provided with the termination to the vent section or telescoping vent section or elbow in the same manner as the other vent co...

Page 24: ...1PH Junction Box Field Wired Factory Wired Power Supply Unswitched CAUTION Ground supply lead must be con nected to the wire attached to the green ground screw located on the outlet box Failure to do...

Page 25: ...can turn on suddenly Keep away from the appliance burner when operating the remote system or activating manual bypass of the remote system CAUTION Propertydamagehazard Excessive heat can cause propert...

Page 26: ...is turned off The receiver beeps 2 times Low Battery Detection Remote Control The life of the Remote Control batteries depends on many factors including battery quality and number of appliance ignitio...

Page 27: ...complete combus tion sooting and poor flame quality and will void the warranty Rear Floor Section Rear Ledge Tab Side Panel Center Lower Tab Reinstall front floor section 1 See Figure 27 2 Engage lowe...

Page 28: ...allelectricitytotheappliancebeforeinstallingmedia If media is not installed according to the installation instructions flame impingement and improper combustion could occur resulting in soot This appl...

Page 29: ...tempt to substitute the materials used on these doors or replace cracked or broken glass The glass door s of this appliance must onlybereplacedasacompleteunitaspro vided by the manufacturer Do not att...

Page 30: ...re also provided on a tag attached to one of the lower door brackets When first lighting the appliance it will take a few minutes for the gas line to purge itself of air Once purging is complete the p...

Page 31: ...tools Force or attempted repair may result in a fire or explosion D Do not use this appliance if any part has been under water Immediately call a qualified service technician to inspect the appliance...

Page 32: ...Guidelines If there is smoke or soot present first ensure that the flames are not impinging on any of the panels If the panels are properly posi tioned and a sooting condition still exists increase t...

Page 33: ...ES Make sure TOP and BOTTOM Nailing Flanges are attached to fireplace in the correct VERTI CAL position for Surround finish and the correct HORIZONTAL position for the wall finish material thickness s...

Page 34: ...rd abuts lip Combustible Wall Finish Material Top Non Combustible Fiber Board provided with fireplace Wall Stud Insulation and combustible material NOT ALLOWED in clearance zones around vent component...

Page 35: ...rez la t l commande et nettoyez la soigneuse ment pour liminer la poussi re et les traces de graisse ou d huile Collez l tiquette sur le bo tier de la t l commande Figure B Choisissez la langue qui es...

Page 36: ...4 5VF 10 Firestop Spacer Vertical rigid 1 1 1 spacing 10 pk 96K92 SV4 5SP Support Plate Vent Sections Rigid Listed Secure Vent Components Cat Model Description 17M52 SV4 5HGS 1 TerminationGuard Square...

Page 37: ...sedflex 77L89 SFKIT24S Horiz Termination forflex with24inch 610 mm compressedflex 77L90 SFKIT36S Horiz Termination forflex with36inch 914 mm compressedflex 77L91 SFKIT48S Horiz Termination forflex wit...

Page 38: ...ever use substitute materials Use of non approved parts can result in poor performance and safety hazards and may void the warranty Parts with item numbers are illustrated on the next page Item No Des...

Page 39: ...are those listed on the previous page LENNOX HEARTH PRODUCTS ELITE LINEAR VIEW DIRECT VENT GAS FIREPLACE MODELS LDV42 LDV54 INSTALLATION INSTRUCTIONS 25 1 67 5 D B R E V 00 4 Power 120V Out Fan Aux O...

Page 40: ...eserves the right to make changes at any time without notice in design materials specifications and prices and also to discontinue colors styles and products Consult your local distributor for firepla...

Reviews: