NOTE: DIAGRAMS AND ILLUSTRATIONS ARE REPRESENTATIVE AND ARE NOT DRAWN TO SCALE.

www.LennoxHearthProducts.com

13

VENTINg 

INSTALLATION

APPROVED VENT COMPONENTS

These  appliances  are  designed,  tested,  and 

listed  for  installation  and  operation  with  the 

following vent components, which are labeled 

for identification:

• 

Secure Vent™

 direct-vent system compo-

nents by Security Chimneys International.

• 

Secure flex™

 flexible vent components by 

Security Chimneys International.

• 

Z-fLEx™

 model GA venting systems listed 

to  UL1777  and  ULCS635  by  Flexmaster 

Canada Limited.

Do  NOT  use  any  other  manufacturers’  vent 

components with these appliances. 

See “Installation Accessories” at the back of 

this manual for catalog numbers.

gENERAL VENTINg INfORMATION  

AND IMPORTANT NOTICES 

• 

These  instructions  should  be  used  as  a 

guideline  and  do  not  supersede  local 

codes in any way. Install venting accord-

ing  to  local  codes,  these  instructions,  

and  the  current  National  fuel  gas  Code 

(ANSI-Z223.1)  in  the  USA  or  the  current 

standards of CAN/CSA-B149.1 in Canada. 

• 

Ensure that clearances are in accordance 

with  local  installation  codes  and  the  re-

quirements of the gas supplier.

  Dégagement conforme aux codes d’in-

stalla tion locaux et aux exigences du 

foumisseunde gaz.

• 

Use only approved vent components. 

See 

“Approved  Vent  Components”  (on  this 

page),  and  “Installation  Accessories”  at 

the back of this manual.

• 

These fireplaces must be vented directly 

to the outside.

• 

The vent system may not service multiple 

appliances and must never be connected 

to a flue serving a solid fuel burning appli-

ance.

• The vent pipe is tested to be run inside an 

enclosed wall (such as a chase). There is no 

requirement for inspection openings in the 

enclosing wall at any of the joints in the vent 

pipe.

•  Secure  Vent™  components  are  shown  in 

these figures; Secure Flex™ pipe also may 

be used.

Figure 13-1

Align dimples in upper vent 

section with inlets of locking 

incline channels on lower vent 

section (or appliance collar). 
Twist upper vent section 

ClOCKWISE until arrows  

and dimples align.

Dimple

Locking  

Incline  

Channel

Connected Vent 

Sections

Arrow

Arrow

Lower Vent Section or Appliance Collar

ATTAChINg SECURE VENT™ 

COMPONENTS

Secure Vent

™ direct-vent system components 

are  unitized  concentric  pipe  components 

featuring positive twist-lock connections (see 

Figure 13-1

).  

To attach venting components:

1. Attach  the  dimpled  end  of  one  section  to 

the incline channel end of the other section, 

making sure to align the four dimples with 

the inlets of the four incline channels.

2. Push the section being attached against the 

adjoining section until fully engaged.

3. Twist  the  section  being  attached  CLOCK-

WISE, running the dimples down and along 

the channels until seated at the ends of the 

channels. 

The sections are properly seated 

when the arrow on one section aligns with 

the dimple on the other section

.

The  unitized  design  of 

Secure  Vent 

compo-

nents will engage and seal both the inner and 

outer  pipe  without  the  need  for  sealant  or 

screws. If desired, however, a #6 x 1/2" screw 

may be used at each joint (not required).

Remember to maintain minimum  

clearances to combustibles!

See CLEARANCES section in this manual.

 

NOTICE: 

It  is  important  to  install 

horizontal  runs  on  a  steady,  (i.e.,  no 

“dips”),  slightly  positive  incline  of 

approximately 1/4 inch rise-per-foot (20 

millimeters  rise-per-meter)  horizontal, 

in  a  direction  away  from  the  fireplace. 

(Slightly  smaller  rise-per-foot  run  ratios 

are  acceptable.)  Use  a  carpenter’s  level 

to measure from a constant surface, and 

adjust support straps as necessary.

fIRESTOP/SPACER  

REqUIREMENTS

Vertical  firestop/Spacer  must  be 

used  anywhere  vent  pipe  passes 

through  a  combustible  floor  or 

 ceiling.
horizontal firestop/Spacer must be 

used  anywhere  vent  pipe  passes 

through a combustible wall.

•  Use 

Secure  Vent

™  Firestop/Spacer  with 

Secure Vent

™ vent pipe.

•  Use 

Secure  flex

™  Firestop/Spacer  with 

Secure flex

™ vent pipe.

•  See "

Installation Accessories

" at the back of 

this manual for catalog numbers.

Installing Vertical (Ceiling)  

firestop/Spacer

1. 

Install 

vertical firestop/spacer 

at all ceiling 

joists. 
• If living space is above the ceiling, install 

firestop/spacer on bottom side of ceiling. 

• If attic space is above the ceiling, install 

firestop/spacer on top side of joist. 

2. 

Route  vent  sections  through  the  framed 

ceiling opening (see 

Page 9

), and secure 

firestop/spacer  with  8d  nails  (or  other 

appropriate fasteners) at each corner. 

3. 

Install 

attic insulation shield (REqUIRED) 

to keep insulation materials from touching 

vent pipe.

  (Attic  insulation  shield  may  be  used  to 

obtain  required  clearances  to  combus-

tibles.  See  “

Installation  Accessories

”  at 

the back of this manual for ordering infor-

mation). 

  Note:  Caulk  firestops  only  where  pipe 

penetrates an outside wall, attic, or other  

unconditioned space.

Installing horizontal (Exterior Wall) 

firestop/Spacer

See 

Figure  23-1

.  Install 

horizontal  firestop/

spacer

 over the opening at the exterior side 

of the framing, long side up, with the 3-inch 

spacer clearance at the top, and nail into place. 

(The firestop/spacer also may be installed over 

the opening on the interior side of framing).

  

WARNINg

Under no circumstances may sepa-

rate sections of concentric flexible 

vent pipe be joined together.

LENNOX HEARTH PRODUCTS  •  ELITE LINEAR VIEW DIRECT-VENT GAS FIREPLACE (MODELS LDV42, LDV54)  •  INSTALLATION INSTRUCTIONS

Summary of Contents for ELITE LDV42N

Page 1: ...is or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from...

Page 2: ...allation Instructions this manual Care and Operation Instructions Safety in Operation Warnings Warranty Vent restrictor assembly Remote control kit handheld remote control transmitter remote control r...

Page 3: ...proper installation or use of this appliance can cause serious injury or death from fire burns explosion or carbon monoxide poisoning Do not attempt to alter or modify the construction of the applianc...

Page 4: ...e ON OFF function only Efficiencies Fireplace Model Natural Gas Propane AFUE EnerGuide P4 AFUE EnerGuide P4 ldv42 66 7 54 2 69 6 59 4 ldv54 71 9 63 2 72 1 65 5 AFUE Annual Fuel Utilization Efficiency...

Page 5: ...with certain vent runs 16 Reinstall baffle if removed for vent restrictor installation 28 Install media 27 Install glass door 29 12 Verify appliance operation 30 Lighting instructions 31 Air shutter a...

Page 6: ...of the mantel UNPROTECTED Side Wall See Figure 6 4 for minimum clearances to unprotected side walls FINISH SURROUND IMPORTANT The factory supplied non com bustible fiber board MUST be installed aroun...

Page 7: ...fireplace the nailing flanges MUST be adjusted according to finish cleanface or surround and wall finish material thickness This is critical to ensure proper fireplace location especially if installi...

Page 8: ...or dimension information only Fireplace must be adequately framed and supp A Required frame opening width 1 2 of A horizontal centerline of fireplace and vent framing opening B Required frame opening...

Page 9: ...vertical position for cleanface finish and at 1 2 wall finish depth Cleanface Finish Nailing Flange Settings 1 Leave vertical position of nailing flanges at factory setting see Figure 9 1 DETAIL A 2 I...

Page 10: ...opane tank smaller than 100 lbs may create pressure loss and insufficient fuel delivery which can cause sooting severe delayed ignition or other malfunctions ref NPFA 58 Any damage as a result of insu...

Page 11: ...alified installer approved and or licensed as required by the locality In the Commonwealth of Massachusetts installation must be performed by a licensed plumber or gas fitter Figure 11 3 Gas Stub 1 2...

Page 12: ...t all factory and field connections for gas leaks Note Even though soapy water is an effective leak test solution it is NOT recommended because soap residue can corrode pipes and fittings over time 1...

Page 13: ...against the adjoining section until fully engaged 3 Twist the section being attached CLOCK WISE running the dimples down and along the channels until seated at the ends of the channels The sections ar...

Page 14: ...L 2 1 4 2 1 0 1 2 1 2 2 2 1 4 3 2 1 6 4 t n e V f o t h g i e H s n o i t c e S t n e V f o r e b m u N s e h c n i t f 6 7 2 3 2 0 0 0 8 0 8 9 7 2 5 2 3 2 0 0 0 0 6 6 5 0 8 2 5 7 3 3 2 1 0 0 8 0 9 5...

Page 15: ...bove appliance vent outlet VENT RUN SUPPORT REQUIREMENTS Supporting Vertical Vent Runs Note Proper venting support is very important NEVER use the fireplace to support the weight of the venting Suppor...

Page 16: ...o slide the assembly up into the vent collar as shown in Figure 16 3 The vent restrictor is held in place by fric tion only The entire vent restrictor assembly must be up inside the vent collar with n...

Page 17: ...ofMill PacBlack 700 F high temperature sealant Catalog No 10K81 to the inner adaptor collar approximately 1 2 inch from the end 3 Pull and extend the inner flexible vent pipe 4 Slidetheinnerflexpipeov...

Page 18: ...provided Vent Restrictor if re quired see Page 16 A 90 elbow may NOT be attached directly to the appliance collar A minimum of 6 pipe must be used between the fireplace collar and a 90 elbow For more...

Page 19: ...screw c Apply non combustible caulking silicone caulking is acceptable around entire cir cumference to ensure a water tight seal LENNOX HEARTH PRODUCTS ELITE LINEAR VIEW DIRECT VENT GAS FIREPLACE MODE...

Page 20: ...rtical Firestop Spacer must be used anywhere vent pipe passes through a combustible floor or ceiling Horizontal Firestop Spacer must be used anywhere vent pipe passes through a combustible wall For fu...

Page 21: ...termination must have a minimum 6 152 mm clearance to any overhead combustible projection less than or equal to 2 1 2 64 mm For projections greater than 2 1 2 64 mm see Figure 21 1 For additional vent...

Page 22: ...U S 12 in Canada V L B J X V A G Inside Corner Detail B C C C 18 Ventilated Soffit Horizontal Termination Detail D Exterior Wall 6 Inside Corner See Item D in the Text Below V P V O N N Q NOTE Local...

Page 23: ...Attach termination adaptor See Figure 23 2 Attach the termination adaptor provided with the termination to the vent section or telescoping vent section or elbow in the same manner as the other vent co...

Page 24: ...1PH Junction Box Field Wired Factory Wired Power Supply Unswitched CAUTION Ground supply lead must be con nected to the wire attached to the green ground screw located on the outlet box Failure to do...

Page 25: ...can turn on suddenly Keep away from the appliance burner when operating the remote system or activating manual bypass of the remote system CAUTION Propertydamagehazard Excessive heat can cause propert...

Page 26: ...is turned off The receiver beeps 2 times Low Battery Detection Remote Control The life of the Remote Control batteries depends on many factors including battery quality and number of appliance ignitio...

Page 27: ...complete combus tion sooting and poor flame quality and will void the warranty Rear Floor Section Rear Ledge Tab Side Panel Center Lower Tab Reinstall front floor section 1 See Figure 27 2 Engage lowe...

Page 28: ...allelectricitytotheappliancebeforeinstallingmedia If media is not installed according to the installation instructions flame impingement and improper combustion could occur resulting in soot This appl...

Page 29: ...tempt to substitute the materials used on these doors or replace cracked or broken glass The glass door s of this appliance must onlybereplacedasacompleteunitaspro vided by the manufacturer Do not att...

Page 30: ...re also provided on a tag attached to one of the lower door brackets When first lighting the appliance it will take a few minutes for the gas line to purge itself of air Once purging is complete the p...

Page 31: ...tools Force or attempted repair may result in a fire or explosion D Do not use this appliance if any part has been under water Immediately call a qualified service technician to inspect the appliance...

Page 32: ...Guidelines If there is smoke or soot present first ensure that the flames are not impinging on any of the panels If the panels are properly posi tioned and a sooting condition still exists increase t...

Page 33: ...ES Make sure TOP and BOTTOM Nailing Flanges are attached to fireplace in the correct VERTI CAL position for Surround finish and the correct HORIZONTAL position for the wall finish material thickness s...

Page 34: ...rd abuts lip Combustible Wall Finish Material Top Non Combustible Fiber Board provided with fireplace Wall Stud Insulation and combustible material NOT ALLOWED in clearance zones around vent component...

Page 35: ...rez la t l commande et nettoyez la soigneuse ment pour liminer la poussi re et les traces de graisse ou d huile Collez l tiquette sur le bo tier de la t l commande Figure B Choisissez la langue qui es...

Page 36: ...4 5VF 10 Firestop Spacer Vertical rigid 1 1 1 spacing 10 pk 96K92 SV4 5SP Support Plate Vent Sections Rigid Listed Secure Vent Components Cat Model Description 17M52 SV4 5HGS 1 TerminationGuard Square...

Page 37: ...sedflex 77L89 SFKIT24S Horiz Termination forflex with24inch 610 mm compressedflex 77L90 SFKIT36S Horiz Termination forflex with36inch 914 mm compressedflex 77L91 SFKIT48S Horiz Termination forflex wit...

Page 38: ...ever use substitute materials Use of non approved parts can result in poor performance and safety hazards and may void the warranty Parts with item numbers are illustrated on the next page Item No Des...

Page 39: ...are those listed on the previous page LENNOX HEARTH PRODUCTS ELITE LINEAR VIEW DIRECT VENT GAS FIREPLACE MODELS LDV42 LDV54 INSTALLATION INSTRUCTIONS 25 1 67 5 D B R E V 00 4 Power 120V Out Fan Aux O...

Page 40: ...eserves the right to make changes at any time without notice in design materials specifications and prices and also to discontinue colors styles and products Consult your local distributor for firepla...

Reviews: